DOI QR코드

DOI QR Code

Performance Analysis for Open-loop Geothermal System with Spill-way technology by Real-scale Experiment

관정간 도수통로를 설치한 개방형 지열 시스템의 냉방성능 실험

  • Kim, Hong kyo (Department of Architectural Engineering Pusan National University) ;
  • Bae, Sangmu (Department of Architectural Engineering Pusan National University) ;
  • Nam, Yujin (Department of Architectural Engineering Pusan National University) ;
  • Jeoun, Oun (GGK Company Limited) ;
  • Oh, Jong Hyun (GGK Company Limited) ;
  • Lee, Byong Ho (Korea Groundwater and Geothermal energy Assosiation)
  • Received : 2017.12.27
  • Accepted : 2018.03.09
  • Published : 2018.04.10

Abstract

A ground-source heat pump system (GSHP) is more energy efficient than other heat-source systems because it uses annual constant underground and water temperatures. Especially, two-well geothermal systems using groundwater as the heat source can achieve higher performance than closed-loop geothermal systems. However, performance of two-well geothermal systems is decreased by occurring overflow according to scale during long-term operations. Therefore, this study presents a two-well pairing geothermal system that controls the groundwater level of a diffusion well. In addition, a two-well pairing geothermal system and an SCW geothermal system were installed, and a comparative analysis of cooling performance depending on system operation under the same load conditions was conducted. The result was that the average heat pump coefficient of performance (COP) of the two-well pairing system was 6.5, and the entire system COP was 4.3.

Keywords

Acknowledgement

Supported by : 국토교통부

References

  1. Han, J. S., Han, H. S., and Han, C., 2010, Geothermal Energy : Geothermal Heating and Cooling, Geothermal Generation, Hanlimwon, Korea.
  2. Ministry of Land, Infrastructure, and Transport, 2012, Guidelines for design of road antifreezing layer.
  3. Sciacovelli, A., Guelpa, E., and Verda, V., 2014, Multi-scale modeling of the environmental impact and energy performance of open-loop groundwater heat pumps in urban areas, Applied Thermal Engineering, Vol. 71, pp. 780-789. https://doi.org/10.1016/j.applthermaleng.2013.11.028
  4. Park, Y. Y., Mok, J. K., Jang, B. J., Park, Y. C., and Lee, J. Y., 2013, Influence of open and closed loop geothermal cooling and heating systems on hydrogeological properties, Journal of the geological society of Korea, Vol. 49, No. 6, pp. 649-659. https://doi.org/10.14770/jgsk.2013.49.6.649
  5. Russo, S. L. and Civita, M. V., 2009, Open-loop groundwater heat pumps development for large buildings : A case study, Geothermics, Vol. 38, pp. 335-345. https://doi.org/10.1016/j.geothermics.2008.12.009
  6. Kim, W. J., Lee, S. G., Jeon, J. S., and Kim, M. S., 2016, Improved Design Method of Open Loop Geothermal System and its Applications, New & Renewable Energy, Vol. 12, pp. 122-133. https://doi.org/10.7849/ksnre.2016.12.12.4.122
  7. Bae, S. M., Kim, H. K., Kim, H. W., and Nam, Y. J., 2017, Hydraulic feasibility study on the open-loop geothermal system using a pairing technology, The International Journal of The Korea Institute of Ecological Architecture and Environment, Vol. 17, No. 3, pp. 119-124.
  8. Bae, S. M., Kim, H. K., Kim, H. W., and Nam, Y. J., 2017, Study on the Underground Thermal Environment around Wells for a Design Method of Open-Loop Geothermal System, Vol. 13, No. 1, pp. 14-20. https://doi.org/10.17664/ksgee.2017.13.1.014
  9. Cho, J. H., Nam, Y. J., and Kim, H. C., 2016, Performance and Feasibility Study of a Standing Column Well (SCW) System Using a Deep Geothermal Well, energies, Vol. 9, No. 2, pp. 108-120. https://doi.org/10.3390/en9020108
  10. Lim, H. J., Kong, H. J., and Sohn, B. H., 2017, Cooling Performance of Geothermal Heat Pump Using Surface Water Heat Exchanger, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 29, No. 6, pp. 316-326. https://doi.org/10.6110/KJACR.2017.29.6.316
  11. Kim, J. S. and Nam, Y. J., 2013, A Study of the Influence of Groundwater Level on the System Performance of Open Loop Geothermal System, Transactions of the Korea society of Geothermal Energy Engineers, Vol. 9, No. 3, pp. 1-10. https://doi.org/10.17664/KSGEE.2013.9.3.001
  12. Nam, Y. J., 2011, Numerical Analysis for the Effect of Ground and Groundwater Conditions on the Performance of Ground Source Heat Pump Systems, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 23, No. 5, pp. 321-326. https://doi.org/10.6110/KJACR.2011.23.5.321
  13. Nguyen, A., Pasquier, P., and Marcotte, D., 2015, Influence of groundwater flow in fractured aquifers on standingcolumn wells performance, Geothermics, Vol. 58, pp. 39-48. https://doi.org/10.1016/j.geothermics.2015.08.005
  14. Chen, X., Zhang, G., Peng, J., Lin, X., and Liu, T., 2006, The performance of an open-loop lake water heat pump system in south China, Applied Thermal Engineering, Vol. 26, pp. 2255-2261. https://doi.org/10.1016/j.applthermaleng.2006.03.009
  15. Kim, J. H., Kim, J. Y., Hong, W. H., and Ahn, C. H., 2008, A Study on the Heating Performance of SCW Type Geothermal Heat Pump System for Residential House, Journal of the Korean Housing Association, Vol. 19, No. 5, pp. 11-18.
  16. Park, J. H., Kim, J. Y., Hong, W. H., and Ahn, C. H., 2008, Research on the Cooling Performance Evaluation of Groundwater Heat Pump System for Residence House, Journal of The Architectural Institute of Korea Planning & Design, Vol. 24, No. 3, pp. 273-280.