Abstract
In this study, a small-scale siphon breaker experimental facility was designed to examine the validity of the Siphon Breaker Simulation Program (SBSP). To design the experimental facility, the simulation results of the C factor, Chisholm B coefficient, and Undershooting Height (UH) were obtained by SBSP. The major parts of the experimental facility were the upper tank, lower tank, downcomer, and Siphon Breaker Line (SBL). The area of the Upper tank was $0.09-m^2$ with a height of 0.65-m. The height of the downcomer was 1.6-m. Pressure transmitters and an electronic scale were used to obtain the experimental results. The experimental variables were the sizes of Loss of Coolant Accident (LOCA) and SBL. The experimental results were analyzed by UH. The SBSP well predicted the UH with an error of 2.5%. Overall, it is possible to design siphon breakers with various scales using SBSP.
본 연구는 Siphon Breaker Simulation Program(SBSP)을 이용하여 소규모 사이펀 차단기 실험장치를 설계 및 제작하고, 실험 수행 후 그 결과를 이용하여 다양한 규모의 사이펀 차단기에 대한 SBSP의 적용 가능성을 평가하기 위해 진행되었다. 실험장치 설계를 위하여 C factor와 Chisholm B 계수, Undershooting Height(UH)에 대한 시뮬레이션 결과값을 SBSP로 도출하였다. 실험장치의 중요파트는 upper tank, lower tank, downcomer, Siphon Breaker Line(SBL) 등이며, upper tank는 넓이 $0.09-m^2$, 높이 0.65-m의 크기로 제작되었고, downcomer 높이는 1.6-m로 제작되었다. 실험결과 분석을 위하여 압력계, 차압계, 전자저울이 사용되어 압력과 차압, 유량에 대한 정보를 도출하였다. 실험에서 사용된 실험변수는 Loss Of Coolant Accident(LOCA) 크기와 SBL 크기이며, LOCA는 30-mm와 38-mm에 대해서, SBL은 6/16-inch와 8/16-inch에 대해서 실험이 진행되었다. 실험의 결과로 유량과 압력, 그리고 UH를 도출하였으며, 실험결과를 SBSP의 시뮬레이션 결과와 비교, 분석하였다. UH 측면에서 SBSP가 수조의 총 높이 대비 2.5 %의 오차로 실험결과를 잘 예측하는 것을 관찰하였다. 그러므로 SBSP를 이용한 다양한 규모의 사이펀 차단기 설계가 가능한 것을 확인하였다.