DOI QR코드

DOI QR Code

New Three-Phase Static Transfer Switch using AC SSCB

AC SSCB를 이용한 새로운 3상 Static Transfer Switch

  • Song, Seung-Min (Dept. of Electrical Eng., Pukyong Nat. University) ;
  • Kim, Jin-Young (Dept. of Electrical Eng., Pukyong Nat. University) ;
  • Kim, In-Dong (Dept. of Electrical Engineering, Pukyong National University)
  • Received : 2018.01.18
  • Accepted : 2018.04.30
  • Published : 2018.05.01

Abstract

These days, widespread use of sensitive loads and distributed generators makes static transfer switch (STS) an essential component in power circuits to achieve a good power quality for AC Grids. In case of a short-circuit fault, previous STS cannot break the fault current. However, the proposed STS has the capability of breaking it quickly as a circuit breaker. Also if there are power quality problems such as Sag/Swell, the proposed STS can quickly transfers the load to the good quality source. Furthermore it is proved that the transfer time of the proposed STS is within one half of period of 3-phase source frequency regardless of the type of load. It is anticipated that the proposed STS may be utilized to realize many stable and reliable AC grid systems.

Keywords

References

  1. Chan-Nan Lu and Cheng-Chieh Shen, "Estimation of Sensitive Equipment Disruptions Due to Voltage Sags," IEEE Trans. Power Delivery, vol. 22, No. 2, pp. 1132-1137, Apr. 2007. https://doi.org/10.1109/TPWRD.2007.893433
  2. IEC 62040-3, "Uninterruptible power systems (UPS)-Part 3: Method of specifying the performance and test requirements", International Electrotechnical Commission, (1999).
  3. R. W. De Doncker, W. T. Eudy, J. A. Maranto, H. Mehta, and J. W. Schwartzenberg, "Medium voltage subcycle transfer switch," Power Qual. Assur., pp. 46-51, July/ Aug. 1995.
  4. J. W. Schwartzenberg and R. W. De Doncker, "15 kV medium voltage static transfer switch," in Proc. IEEE IAS 30th Annu. Meeting, Orlando, FL, pp. 2515-2520, Oct. 1995.
  5. H. Mokhtari, S. B. Dewan, and M. R. Iravani, "Analysis of a static transfer switch with respect to transfer time," in IEEE PES-2000 Summer Meeting, IEEE Trans. on Power Delivery, submitted for publication.
  6. Giuseppe Parise and Luigi Parise, "Unprotected Faults of Electrical and Extension Cords in AC and DC Systems," IEEE Trans. Ind. Appl., vol. 50, No. 1, pp. 4-9, Jan. 2014. https://doi.org/10.1109/TIA.2013.2271605
  7. C. Abbey, D. Cornforth, N. Hatziargyriou, K. Hirose, A. Kwasinski, E. Kyriakides, G. Platt, L. Reyes and S. Suryanarayanan, "Powering Through the Storm: Microgrids Operation for More Efficient Disaster Recovery," IEEE Power and Energy Magazine, vol. 12, pp. 67-76, May/June 2014. https://doi.org/10.1109/MPE.2014.2301514
  8. C37.09, IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis, 1999
  9. Jin-Young Kim, Seung-Min Song, Seung-Soo Choi, In-Dong Kim and Sun Kyu Choi "New AC solid-state circuit breaker with simple charging and rebreaking capabilities," In Industrial Electronics Society, IECON pp. 3866-3871, Oct.2016
  10. IEC 61000-4-30 Standard, "Testing and Measurement Techniques-Power Quality Measurement Methods", First Edition, 2003.