Abstract
As a result of the recent revision of the 'Guideline for Installation and Management of Fire Prevention Facility in Road Tunnels', the thermal buoyancy has to be taken into account when calculating the capacity of jet fans for smoke control in tunnel fires. However, there is no detailed methodologies for considering thermal buoyancy, so further study is needed. In this study, the thermal buoyancy in the tunnel is calculated by 3-D numerical simulation to consider the thermal buoyancy in case of fire in tunnels, and the relationship between heat buoyancy and vehicle drag, And the method of calculating the capacity of the jet fan for smoke control in tunnels. According to the analysis results, heat buoyancy acts as a resistance force in the case of a down-slope tunnel, and the pressure rise of jet fan for smoke control is not simply determined by the value of heat buoyancy at the entrance of the tunnel and the value of the vehicle drag at the exit. And it is analyzed that it is necessary to carry out a comprehensive review according to the location of the fire vehicle in tunnels.
최근 '도로터널 방재시설 설치 및 관리지침'의 개정으로 인해 터널 내 제연용 제트팬의 용량 산정 시에는 열부력을 고려하도록 규정하고 있다. 그러나 열부력을 고려하는 세부방법론에 대한 규정이 없어, 이에 대한 세부적인 추가 연구가 필요한 실정이다. 본 연구에서는 터널 내 화재 시 열부력을 고려하기 위하여 3차원 수치해석 시뮬레이션을 수행하여 터널 내열부력을 계산하고, 화재차량의 진행방향에 따라 열부력과 차량항력의 관계, 즉, 화재차량의 위치에 따른 터널 내 제연용 제트팬 용량 산정방법에 대하여 검토를 수행하였다. 분석결과에 따르면, 하향경사 터널의 경우에는 열부력이 터널 내 저항력으로 작용하며, 터널 내 화재연기를 제연하기 위해 필요한 제연팬의 승압력은 단순히 터널 입구부의 열부력 값과 출구부의 차량항력값에 의해 단순히 결정되지 않으며, 터널 내 화재차량의 위치에 따라 종합적인 검토가 필요한 것으로 분석되었다.