DOI QR코드

DOI QR Code

Experimental Study on a Low-Temperature Hot Water Capillary Radiant Floor Heating System

저온온수 모세유관 바닥복사 난방시스템의 성능에 관한 실험적 연구

  • Cho, Jinkyun (Energy & Environment Business Division, KCL(Korea Conformity Laboratories)) ;
  • Park, Beungyong (Energy & Environment Business Division, KCL(Korea Conformity Laboratories)) ;
  • Lee, Yongjun (Eco-Facade Eng. Lab., BEL Technology) ;
  • Chong, Wonho (Youone Engineering Co., Ltd.)
  • 조진균 (한국건설생활환경시험연구원) ;
  • 박병용 (한국건설생활환경시험연구원) ;
  • 이용준 ((주)비이엘테크놀로지) ;
  • 정원호 (유원엔지니어링(주))
  • Received : 2017.10.26
  • Accepted : 2017.12.15
  • Published : 2018.02.10

Abstract

Radiant floor heating systems with capillary tubes are energy saving systems in which hot water is circulated into capillary tube with a small diameter. In this study, the heating performance of capillary tube system is investigated in an experimental study and a simulation model. The results of the study showed that, the capillary tube radiant floor heating system maintains a more stable floor surface temperature in comparison a PB pipe system. In terms of energy consumption, the capillary tube radiant floor heating system proved to be more efficient than the PB pipe heating system at $40^{\circ}C$ of low temperature hot water supply. The difference between water temperature and room temperature can be held low for heating which saves energy. Low temperature radiant floor heating system with capillary tubes have significant advantages such as health improvement, low energy cost, optimum use of heat source(boiler) and higher operational efficiency.

Keywords

References

  1. Xie, D., Wang, Y., Wang, H., Mo, S., and Liao, M., 2016, Numerical analysis of temperature non-uniformity and cooling capacity for capillary ceiling radiant cooling panel, Renewable Energy, Vol. 87, pp. 1154-1161. https://doi.org/10.1016/j.renene.2015.08.029
  2. Seo, Y. J., Lee, J. U., Kim, J. O., Kim, T. Y., and Leigh, S. B., 2011, An Empirical Study of Capillary Tube Radiant Floor Cooling System Using Geothermal Energy, Proceeding of KIAEBS 2011 Autumn Annual Conference, pp. 12-15.
  3. Li, Q., Wu, J., Liu, H., Pan, T., and Li, Yin., 2015, Experimental Research on Office Building Solar Capillary Heating System, Procedia Engineering Vol. 121, pp. 2021-2028. https://doi.org/10.1016/j.proeng.2015.09.202
  4. Hong, H. and Kim, Y. K., 2011, Control and Thermal Comfort by Low Temperature Ondol Heating, Proceeding of SAREK 2011 Summer Annual Conference, pp. 62-65.
  5. Kang, W., Zhao, M., Liu, X., Meng, X., Zhang, L., and Hu, W., 2015, Experimental investigation on a ceiling capillary radiant heating system, Energy Procedia, Vol. 75, pp. 1380-1386. https://doi.org/10.1016/j.egypro.2015.07.220
  6. Chen, T. Y., 2002, Application of adaptive predictive control to a floor heating system with a large thermal lag, Energy and Buildings, Vol. 34, No. 1, pp. 45-51. https://doi.org/10.1016/S0378-7788(01)00076-7
  7. Cho, S. H. and Zaheer-Uddin, M., 2003, Predictive control of intermittently operated radiant floor heating systems, Energy Conversion and Management, Vol. 44, No. 8, pp. 1333-1342. https://doi.org/10.1016/S0196-8904(02)00116-4
  8. Jin, W. F., Rhie, M. K., Yeo, M. S., and Kim, K. W., 2004, A study on the individual room control of radiant floor heating system in apartment buildings, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 16, No. 5, pp. 421-429.
  9. Choi, J. M., Lee, K. N., Ryu, S. R., Kim, Y. Y., Yeo, M. S., and Kim, K. W., 2007, A study on the required supply water temperature calculating method for the control of multizone radiant floor heating system, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 19, No. 1, pp. 77-85.
  10. Park, S. H., Jang, Y. S., and Kim, E. J., 2017, Simple Modeling of Floor Heating Systems based on Optimal Parameter Settings, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 29, No. 9, pp. 472-481.
  11. Lee, Y. J., Jin, W., Yeo, M. S., and Kim, K. W., 2005, An Experimental Study on the Application of Polypropylene Capillary Tube Cooling System, Korean Journal of Air-Conditioning and Refrigeration Engineering Vol. 17, No. 9. pp. 89-95.
  12. Lee, M. B., 2003, New approach to Heating and Cooling with Polypropylene capillary tubing mat system, Proceeding of SAREK 2003 Winter Annual Conference, pp. 241-244.