DOI QR코드

DOI QR Code

A Probabilistic Study on Seismic Response of Seismically Isolated Nuclear Power Plant Structures using Lead Rubber Bearing

LRB 면진장치를 적용한 원전구조물의 지진응답에 따른 확률론적 연구

  • Kim, Hyeon-Jeong (Department of Civil Engineering, Kangwon National University) ;
  • Song, Jong-Keol (Department of Civil Engineering, Kangwon National University) ;
  • Moon, Ji-Ho (Department of Civil Engineering, Kangwon National University)
  • Received : 2017.08.14
  • Accepted : 2018.01.29
  • Published : 2018.03.01

Abstract

The seismically isolated nuclear power plants shall be designed for design basis earthquake (DBE) and considered to ensure safety against beyond design basis earthquake (BDBE). In order to limit the excessive displacement of the seismic isolation system of the seismically isolated structure, the moat is installed at a certain distance from the upper mat supporting the superstructure. This certain distance is called clearance to stop (CS) and is calculated from the 90th percentile displacement of seismic isolation system subjected to BDBE. For design purposes, the CS can be obtained simply by multiplying the median displacement of the seismic isolation system against DBE by scale factor with a value of 3. The DBE and BDBE used in this study were generated by using 30 sets of artificial earthquakes corresponding to the nuclear standard design spectrum. In addition, latin hyper cube sampling was applied to generate 30 sets of artificial earthquakes corresponding to maximum - minimum spectra. For the DBE, the median displacement and the 99th percentile displacement of the seismic isolation system were calculated. For the BDBE, the suitability of the scale factor was assessed after calculating the 90th percentile displacement of the seismic isolation system.

Keywords

References

  1. American Society of Civil Engineers (ASCE). Seismic design criteria for structures, systems, and components in nuclear facilities. ASCE 43-05. c2005.
  2. Huang YN, Whittaker AS, Kennedy RP, Mayes RL. Assessment of base-isolated nuclear structures for design and beyond-design basis earthquake shaking. Technical Report MCEER0-09-0008. c2009.
  3. Computer and Structures, Inc. SAP2000 linear and nonlinear static and dynamic analysis and design of three-dimensional structures. CSI, Berkeley. California. c2004.
  4. Mazzoni S, McKenna F, Scott MH, Fenves GL. OpenSEES: open system of earthquake engineering simulation, pacific earthquake engineering center. Univ. of Calif., Berkeley (http://opensees.berkeley.edu). c2007.
  5. Lee SJ, Park KS, Lee JH, Lee IW. Guidelines of designing LRB for a cable-stayed bridge to reduce seismic responses. Conference Proceeding of the Korean Society of Civil Engineers. 2003;914-920.
  6. Song JK, Son MK. Effect of bouc-wen model and earthquake characteristics for responses of seismically isolated nuclear power plant by lead-rubber bearing. EESK J Earthquake Eng. 2017;21(2): 95-103.
  7. Hancock J, Watson-Lamprey J, Abrahamson NA, Bommer JJ, Markatis A, McCoy E, Mendis R. An improved method of matching response spectra of recorded earthquake ground motion using wavelets. Journal of Earthquake Engineering. 2006;10(S1):67-89.
  8. Seok CG, Song JK. Seismic performance evaluation of seismically isolated nuclear power plants considering various velocity-dependent friction coefficient of friction pendulum system. EESK J Earthquake Eng. 2016;20(2):125-134.
  9. Huang YN, Whittaker AS, Luco N. Maximum spectral demands in the near fault region. Earthquake Spectra. 2008;24(1):319-341. https://doi.org/10.1193/1.2830435
  10. Stewart JP, Abrahamson NA, Atkinson GM, Baker JW, Boore DM, Bozorgnia Y, Campell KW, Comartin CD, Idriss IM, Lew M, Mehrain M, Moehle JP, Naeim F, Sabol TA. Representation of bidirectional ground motions for design spectra in building codes. Earthquake Spectra. 2011;27(3):927-937. https://doi.org/10.1193/1.3608001
  11. Boore DM, Watson-Lamprey J, Abrahamson NA. Orientation-independent measures of ground motion. Bulletin of the Seismological Socirty of America. 2006;96(4A):1502-1511. https://doi.org/10.1785/0120050209
  12. American society of civil engineers, seismic analysis of safetyrelated nuclear structures. ASCE, Structural Engineering Institute. ASCE/SEI 4-16, Reston, Virginia. c2017.
  13. Korea electric power industry code. KEPIC-STC seismic design isolations. Korea Electric Association. Forthcoming.
  14. Kammerer AM, Whittaker AS, Constantinou MC. Technical considerations for the seismic isolation of nuclear facilities, NUREG-XXXX, United States Nuclear Regulatory Commission (USNRC). Washington DC. c2012.
  15. Kim BS, Song JK. Seismic responses of seismically isolated nuclear power plant structure considering post-yield stiffness of EQS bearing. EESK J Earthquake Eng. 2016:20(5):319-329.