DOI QR코드

DOI QR Code

독립형 신재생발전 시스템의 효율적인 운영을 위한 배터리 용량산정에 관한 연구

A Study on Sizing of Battery for Effective Operation of Stand-alone Renewable Generation System

  • Shin, Hee-Sang (Korean Intellectual Property Office) ;
  • Hue, Jae-Sun (Hyosung Power & Industrial systems Research Center) ;
  • Yun, Sang-Yun (Department of Electrical Engineering Chonnam National University)
  • 투고 : 2018.02.14
  • 심사 : 2018.02.26
  • 발행 : 2018.03.01

초록

This paper presents the method of ESS energy capacity calculation for stand-alone renewable energy generation system consisting of photovoltaic energy. There is almost no power from photovoltaic system during sunless days. So this source is very weak in terms of the power supply reliability. To improve problem of power supply, battery is mainly used Energy Storage System(ESS). The number of sunless days and Depth of Discharge(DOD) is important factor to determine energy capacity of battery. However, a many study for economical design is required due to the high cost of ESS. In this paper, we propose the new method of ESS energy capacity calculation by applying different DOD for operation with and without sun. We determine the Battery capacity using higher DOD of operation during sunless day than the DOD of the normal operation. And we carried out an economic analysis of the calculation results.

키워드

참고문헌

  1. F. Valenciaga, P. F. Puleston, and P. E. Battaiotto, "Power Control of a Solor/Wind Generation System without Wind Measurement : A Passivity/Sliding Mode Approach," IEEE Trans. on Energy Conversion, vol. 18, no. 4, pp. 501-507, Dec. 2003. https://doi.org/10.1109/TEC.2003.816602
  2. Korea Institute of Machinery & Materials, "Modeling, Analysis and Design Tech. Development of Hybrid Generation System with Wind Turbine and Diesel Generator," 2011.
  3. KEPCO, A Study on Standards of Renewable Energy for Remote Island, Ministry of Knowledge Economy Report, 2012.
  4. R. H. Wai, W. H. Wang, and C. Y. Lin, "Highperformance stand-alone photovoltaic generation system," IEEE Trans. on Industrial Electronics, vol. 55, no. 1, pp. 240-250, Jan. 2008. https://doi.org/10.1109/TIE.2007.896049
  5. Woo-Hee Lee, Mi-Young Lee, Jun-Ha Lee, and Hoong-Joo Lee, "Calculation of capacity of solar cell and batter for stable solar system design," Journal of academia-industrial technology, vol. 6, no. 5, pp. 396-400, 2005.
  6. Hee-Sung Moon, Gyu-Yeong Choe, Jong-Soo Kim, and Byoung-Kuk Lee, "Comparison and Analysis of Battery Capacity Estimation Method of Domestic Stand-Alone Photovoltaic System," KIEE spring conference, 2009.
  7. Byoung-Soo, Chio, "The Study on Stand Alone Pico Grid System Utilizing Renewable Energy," doctor's thesis, Dept. Electric. Eng., Univ. Soongsil, 2012.
  8. Hee-Sung Moon, Gyu-Yeong Choe, Jong-Soo Kim, and Byoung-Kuk Lee, "Photovoltaic System Operation Optimal Technique Considering Climate Condition and Residential Loads Pattern," the trans. of KIEE, vol. 58, No. 12, 2009.
  9. Anurag Chauhan n, R.P.Saini, "A review on Integrated Renewable Energy System based power generation for stand-alone applications : Configurations, storage options, sizing methodologies and control," Renewable and Sustainable Energy Reviews, vol. 38, pp. 99-120, 2014. https://doi.org/10.1016/j.rser.2014.05.079
  10. Soon-Hyoung LEE, "Photovoltaic Power Generating system," kidari, pp. 103 Apr. 2008.
  11. Sung-Min Cho, "Optimal BESS Sizing for Customer using New Model Considering Efficiency and Life Cycle," doctor's thesis, Dept. Electric. Eng., Univ. Soongsil, 2012.