ACL and DCL are have been conventionally used for reducing harmonic current on the input side of an ACMD. The current distortion ratio ITHD using ACL and DCL is only 35% to 85%, therefore to satisfy the IEEE Std. 519 requirements, the line filters has been focused as an alternative means. Those are installed between the AC power supply and the input of the ACMD, and must meet the IEEE Std. 519, be economical and be compact. To contribute to the widespread of using these line filters, we discussed concerning its topologies, simulation results, prototype test results as well as the cost evaluations. It included not only the proposed (NHHF) new hybrid harmonic filters which have both merits of simplicity and economic but also the past (BBHF) broadband harmonic filters and (HHF) hybrid harmonic filters.

키워드

참고문헌

  1. Byoungju Park, Hansang Lee, Gilsoo Jang, "Development of Novel Passive Harmonic Filter," Transaction of KIEE, 55A-1-6.
  2. Alexander Kusko, Marc T. Thompson, "Power Quality in Electrical Systems," Mc Graw Hill, pp. 79-81, 83, 2007.
  3. IEEE Std. 519-1992, IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems.
  4. IEEE Std. 1531-2003, IEEE Guide for Application and Specification of Harmonic Filters.
  5. IEEE Std. C57.110-1998, IEEE Recommended Practice for Establishing Transformer Capability When Supplying Nonsinusoidal Load Currents.
  6. IEEE Std. 1459-2000, IEEE Trial-Use Standard Definitions for Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions.
  7. Appliance DESIGN, "The Impact of Variable Speed Drives on Electrical System," A bnp Publication. pp. 19-20, 2015.
  8. Automation and Control Solutions, "AC and DC Chokes in Variable Frequency Drives", Honeywell, pp. 1-2, 2014.