DOI QR코드

DOI QR Code

Classification of cold regions and analysis of the freeze-thaw repetition cycle based on heat transfer quantity by freezing test

실내동결시험을 통한 열류량 분석에 따른 동결-융해 조건 분석 및 한랭지역의 분류

  • An, Jai-Wook (Research Institute for Infrastructure Performance, Korea Infrastructure Safety Corporation) ;
  • Seo, Jeong-Eun (Research Institute for Infrastructure Performance, Korea Infrastructure Safety Corporation) ;
  • Jung, Min-Hyung (Research Institute for Infrastructure Performance, Korea Infrastructure Safety Corporation) ;
  • Seong, Joo-Hyun (Research Institute for Infrastructure Performance, Korea Infrastructure Safety Corporation)
  • 안재욱 (한국시설안전공단 시설성능연구소) ;
  • 서정은 (한국시설안전공단 시설성능연구소) ;
  • 정민형 (한국시설안전공단 시설성능연구소) ;
  • 성주현 (한국시설안전공단 시설성능연구소)
  • Received : 2018.08.14
  • Accepted : 2018.09.28
  • Published : 2018.11.30

Abstract

Tunnels constructed in cold regions can cause serious defects such as cracks and leaks due to external temperature changes in the portals and vents. In order to prevent the freezing damage of the tunnel, appropriate measures should be applied to the section where the freeze damage is concerned. However, the specific criteria and contents for judging whether or not the anti-freeze measures are applied are not presented. In this study, the laboratory freezing tests on the temperature changes of the concrete specimens under freezing conditions were carried out. And the freeze-thaw repetition cycle (F), which can judge the possibility of freezing damage, were presented based on the heat transfer quantity (W) by experimental results of case studies. Also, we propose a classification of cold regions considering the climatic characteristics of Korea for using it to efficient design and maintenance.

한랭지역에 건설된 터널은 내 외부의 온도변화에 의해 갱구부 또는 환기구와 같이 특정한 구간에서 외부 온도변화의 영향으로 균열, 누수 등을 비롯한 심각한 결함이 발생할 수 있다. 이러한 동결-융해로 인한 터널의 결함을 방지하기 위해서는 동결 피해가 우려되는 구간에 대해서 적절한 동결 피해 방지 대책을 적용하여야 하지만 동결-융해 조건을 판단하는 구체적인 기준은 제시되어 있지 않다. 본 연구에서는 국내 터널의 정밀안전진단 결과를 통해 강원지역의 동결피해 현황을 분석하였으며 향후 한랭지역 터널의 동결피해 저감을 위한 설계 및 유지관리에 활용할 수 있도록 동결-융해 반복일수(F) 조건에 따른 국내 동결피해 가능지역을 분류하고자 한다. 따라서 한랭지역 터널의 동결피해 사례분석과 국내 외 동해환경 평가기준을 바탕으로 콘크리트 시험체의 온도변화에 대한 실내실험을 실시하였으며 실험적 검토결과를 기반으로 시간 및 온도변화에 따른 열류량(W) 분석을 실시하였다. 최종적으로 열류량(W) 분석결과와 국내의 기후특성을 고려하여 동결-융해 반복일(F)에 대한 조건을 제안하였으며, 동절기 동결피해에 대비하여 효율적인 설계 및 유지관리에 활용할 수 있도록 국내 한랭지역을 분류하였다.

Keywords

TNTNB3_2018_v20n6_957_f0001.png 이미지

Fig. 1. Amount of leakages in 2012 compared to 2007 for sample tunnel

TNTNB3_2018_v20n6_957_f0002.png 이미지

Fig. 2. Defect point by span of road tunnel in Gang-won area

TNTNB3_2018_v20n6_957_f0003.png 이미지

Fig. 3. Concrete lining test specimen

TNTNB3_2018_v20n6_957_f0004.png 이미지

Fig. 4. Temperature change of concrete lining specimen No. 1, 2

TNTNB3_2018_v20n6_957_f0005.png 이미지

Fig. 5. Example of temperature distribution in winter season (2012~2013)

TNTNB3_2018_v20n6_957_f0006.png 이미지

Fig. 6. Cold region classification

Table 1. Criteria for durability of concrete structures (Concrete Structural Criteria, 2012)

TNTNB3_2018_v20n6_957_t0001.png 이미지

Table 2. Durability evaluation by relative dynamic modulus of elasticity (KS F 2456)

TNTNB3_2018_v20n6_957_t0002.png 이미지

Table 3. Evaluation criteria for freeze/thaw

TNTNB3_2018_v20n6_957_t0003.png 이미지

Table 4. Mix proportion of concrete

TNTNB3_2018_v20n6_957_t0004.png 이미지

Table 5. Time (min) to reach freezing temperature of concrete lining specimen No. 1, 2

TNTNB3_2018_v20n6_957_t0005.png 이미지

Table 6. Heat transfer quantity analysis

TNTNB3_2018_v20n6_957_t0006.png 이미지

Table 7. Results of tunnel lining temperature change by duration due to ambient air temperature

TNTNB3_2018_v20n6_957_t0007.png 이미지

Table 8. Freeze/thaw repetition cycle (F) by area

TNTNB3_2018_v20n6_957_t0008.png 이미지

References

  1. Broch, E., Grov, E., Davik, K.I. (2002), "The inner lining system in Norwegian traffic tunnels", Tunneling and Underground Space Technology, Vol. 17, No. 3, pp. 305-314. https://doi.org/10.1016/S0886-7798(02)00026-3
  2. Cheong, H.M. (2013), "Degree of damage risk by freeze and thaw of concrete structures in Korea", Proceedings of the Korea Concrete Institute, Vol. 25, No. 1, Yeosu, pp. 89-90.
  3. Eurocode EN 1990 : 2002 A1 (2005), Basis of structural design, pp. 16.
  4. FHWA (Federal Highway Administration) (1996), Recommended HPC grade for given exposure condition.
  5. Hong, S.S., Kim, Y.S., You, B.H. (2015), A Study on the Frost Penetration Depth in Pavements, KICT 2016-007, Korea Institute of Civil Engineering and Building Technology, pp. 64.
  6. Jin, H.W., Hwang, Y.C. (2017a), "Experimental study on internal temperature change induced by heating element attached to tunnel ling surface", Journal of the Korean Geo-Environmental Society, Vol. 18, No. 11, pp. 35-40.
  7. Jin, H.W., Hwang, Y.C. (2017c), "Heat transfer test of tunnel lining with heat insulation", Journal of the Korean Geo-Environmental Society, Vol. 18, No. 7, pp. 5-12. https://doi.org/10.14481/jkges.2017.18.1.5
  8. Jin, H.W., Kim, T.S., Hwang, U.C. (2017b), "Analysis of temperature change of tunnel lining with heating element", Journal of the Korean Geo-Environmental Society, Vol. 18, No. 1, pp. 5-12. https://doi.org/10.14481/jkges.2017.18.1.5
  9. Kim, D.Y., Lee, H.S., Sim, B.K. (2011), "A study on the design of tunnel lining insulation based on measurement of temperature in tunnel", Journal of Korean Tunnelling and Underground Space Association, Vol. 13, No. 4, pp. 319-345. https://doi.org/10.9711/KTAJ.2011.13.4.319
  10. Kim, N.Y., Shim, J.W. (2013), "Case studies on the tunnel frost due to the low temperature", Proceedings of the 2013 Spring Geosynthetics Conference, Daegu, pp. 107-110.
  11. Midas IT (2013), Understanding and Using Practical Finite Element Analysis, pp. 2-3.
  12. MOLIT (Ministry of Employment and Labor) (2004), Concrete standard specification, Durability, pp. 14-15.
  13. MOLIT (Ministry of Employment and Labor) (2012), Concrete structural criteria, Grade According to Exposure of Concrete, pp. 77-78.
  14. MOLIT (Ministry of Employment and Labor) (2018), Detailed instructions for the safety and maintenance of facilities, Performance Evaluation, pp. 107-108.
  15. Park, K.H., An, J.W., Park, S.H., Yoon, T.G. (2017), "A study on the development of maintenance system for tunnel with freezing-thawing damage", Geotechnical hazard Mitigations: Experiment, Theory and Practice, Proceedings of the 5th International Conference on Geotechnical Engineering for Disaster Mitigation and Rehabilitation, Taipei, pp. 121-135.
  16. SciTech (2013), Heat Transfer in Practice, pp. 2-500.