DOI QR코드

DOI QR Code

Effect of Rack Compartment using Barriers on Reducing the Fire Spread

차단막에 의한 랙크 구획화가 화재확산 저감에 미치는 영향

  • Cho, Gyu-Hwan (Korea Institute of Civil Engineering and Building Technology, Fire Research Institute) ;
  • Yeo, In-Hwan (Korea Institute of Civil Engineering and Building Technology, Fire Research Institute)
  • 조규환 (한국건설기술연구원 화재안전연구소) ;
  • 여인환 (한국건설기술연구원 화재안전연구소)
  • Received : 2018.01.11
  • Accepted : 2018.01.30
  • Published : 2018.02.28

Abstract

A barrier installed within a rack plays a significant role in delaying the initial spread of fire but it can be an obstacle to a ceiling-type sprinkler installed for extinguishing fires and for supplying fire extinguishing water. An in-rack sprinkler and a barrier can be applied at the same time, but a study on a barrier's ability to delay fire spread or its effect on the in-rack sprinkler is needed. Accordingly, this study examined the effect of a barrier on the delay of fire spread and the in-rack sprinkler according to installation conditions through the reduced scale fire test. As a result, the delay in fire spread increased more than four times when a horizontal barrier and a vertical barrier were installed at the same time. The temperature was also increased two to three times with the compartment, resulting in the early operation of the in-rack sprinkler.

랙크 내 설치되는 차단막은 초기 화재확산을 지연시키는데 큰 역할을 담당하고 있으나 소화를 목적으로 설치되는 천장형 스프링클러의 입장에서는 소화수의 원활한 공급에 장애물로서 비춰질 수도 있다. 이에 In-Rack 스프링클러와 차단막을 동시에 적용하는 방법 등이 제시되고 있으나 차단막의 설치조건에 따른 화재확산 지연성능 및 In-Rack 스프링클러에 미치는 영향 등에 관한 연구는 부족한 실정이다. 이에 본 연구에서는 축소모델 화재실험을 통해 차단막의 설치조건에 따른 화재확산 지연성능과 In-Rack 스프링클러에 미치는 영향 등을 분석하였다. 그 결과, 랙크 내에 수평과 수직 차단막을 동시에 설치한 경우, 4배 이상의 화재확산 지연성능이 발휘되는 것을 확인하였으며, 구획화로 인한 구획 내 온도 상승 또한 약 2~3배 가량 높은 것으로 나타나 In-Rack 스프링클러가 조기에 작동될 수 있도록 유도하는 긍정적인 효과 또한 존재하는 것으로 나타났다.

Keywords

Acknowledgement

Supported by : 소방청

References

  1. H. Ingason, "An Experimental Study of Rack Storage Fires", Brandforsk Project 602-971 SP Report 2001:19, SP Swedish National Testing and Research Institute (2001).
  2. K. J. Overholt, M. J. Gollner, J. Perricone, A. S. Rangwala and F. A. Williams, "Warehouse Commodity Classification from Fundamental Principles. Part II: Fire Heights and Fire Spread", Fire Safety Journal, Vol. 46, No. 6, pp. 317-329 (2011). https://doi.org/10.1016/j.firesaf.2011.05.002
  3. H. Ingason, "In-rack Fire Plumes", Fire Safety Science, Vol. 5, pp. 333-344 (1997). https://doi.org/10.3801/IAFSS.FSS.5-333
  4. L. Ken, P. Rich, H. Jason, D. John, W. Steve and K. Matt, "Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers", UL LLC (2013).
  5. Matthew J. Klaus, "Automatic Sprinkler Systems Handbook 13ed.", Principal Fire Protection Engineer National Fire Protection Association (2016).
  6. T. Hirano, G. Hashimoto, S. Sugawa, K. Hasegawa, T. Ryohei, S. Ijima and R. Shibayaki, "A Review Report of Fire Sprinkler System for a Rack Warehouse", Fire Research Station-010807 (1997).
  7. NFPA 13: Standard for the Installation of Sprinkler Systems (2013).
  8. Sprinkler Protection for High Bay and Automated Storage in Warehouse Type Storage Facilities, Viking (2010).
  9. I. H. Yeo and G. H. Cho, "Application of Horizontal Barrier on a Rack to Reduce Fire Spread", Korean Institute of Fire Science & Engineering, Vol. 31, No. 4, pp. 71-79 (2017). https://doi.org/10.7731/KIFSE.2017.31.4.071
  10. W. H. Kim and Y. J. Lee, "An Improvement of Fire Safety Code for Rack-Type Warehouse in Korea", Korean Institute of Fire Science & Engineering, Vol. 28, No. 6, pp. 69-75 (2014).
  11. G. H. Cho and I. H. Yeo, "Evaluation on Fire Spread Speed of Standard Rack in Korea for Performance based Fire Extinguishing System", Korean Institute of Fire Science & Engineering, Vol. 30, No. 6, pp. 84-91 (2016). https://doi.org/10.7731/KIFSE.2016.30.6.084
  12. FM Global-Property Loss Prevention Data Sheets 8-1, Commodity Classification (2014).
  13. N. J. Alvares, H. K. Hasegawa, K. Hout, A. C. Fernandez-Pello and J. White, "Analysis of a Run-away High Rack Storage Fire", Fire Safety Science, Vol. 4, pp. 1267-1278 (1994).
  14. J. H. Mammoser Iii and F. Battaglia, "A Computational Study on the use of Balconies to Reduce Flame Spread in High-rise Apartment fires", Fire Safety Journal, Vol. 39, No. 4, pp. 277-296 (2004). https://doi.org/10.1016/j.firesaf.2003.11.011
  15. Suzuki, Takeshi, et al., "An Experimental Study of Ejected Flames of a High-rise Building-Effects of Depth of Balcony on Ejected Flames", Fire Safety Science, Vol. 4, pp. 363-374 (2000).
  16. M. Nilsson, A. Mossberg, B. Husted and J. Anderson, "Protection Against External Fire Spread-Horizontal Projections or Spandrels?", In 14th International Fire Science & Engineering Conference, Vol. 2, pp. 1163-1174.