DOI QR코드

DOI QR Code

Evaluation of actual Energy consumption & Simulation of Gas Engine VRF System and Comparison with Electric VRF System

가스 엔진 VRF시스템의 에너지 실사용량 & 시뮬레이션 평가와 전기 구동 VRF 시스템과의 성능비교에 관한 연구

  • Received : 2017.07.04
  • Accepted : 2017.08.08
  • Published : 2017.08.30

Abstract

Purpose: As the recent climate environment changes so rapidly, environmental problems such as hot weather and fine dust have occurred, and interest in environmental policies and technology development is increasing in countries around the world. Similarly in the Architecture, researches to reduce greenhouse gas emissions and to reduce energy application are actively conducted. Looking at previous studies, it is analyzed that the electric VRF is more energy efficient than the gas engine VRF. However, energy costs have changed due to recent price hikes and discounts on gas charges due to high electricity consumption in summer. Method: In this study, the actual building of Gas Engine VRF system was modeled using SketchUp program, and EnergyPlus was used to simulate actual building. Also, Electric VRF system was simulated, and compared with Gas Engine VRF system. Result: The total secondary energy requirement of Electric VRF system was 19.6% less than that of the Gas Engine VRF system, But when analyzing with primary energy requirement, EHP used 15.8% more energy. CO2 emissions were also estimated to be 16.9% more EHP. Energy costs were 14.8% more in Electric VRF systems, because their electricity charges are 0.6 to 160% more expensive than gas charges.

Keywords

References

  1. 김동균, 전종욱, 김강수, "EnergyPlus의 시뮬레이션 결과와 실제 냉방에너지 사용량의 비교 분석 및 GHP와 EHP의 에너지 성능비교에 관한 연구", 대한건축학회지회 논문집-계획계, 2011.05 // (Kim, Dong-Kyun, Jeon, Jong-Ug, Kim, Kang-Soo, Comparison of Actual Cooling Energy Consumption with Calculated Cooling Energy Consumption and Analysis of Energy Performance between GHP and EHP, Architectural Institute Of Korea, 2011.05)
  2. 김영일, "중용량 공조에서 EHP와 GHP의 경제성 비교, 설비공학논문집, 2010 .03 // (Kim, Young-Il, The Economic Comparison of EHP and GHP for Medium Capacity Air-conditioning, The Society Of Air-Conditioning And Refrigerating Engineers Of Korea, 2010.03)
  3. Lee, Woo-Nam, Kim, Hyeong-Jung, Park, Jong-Bae, Cho, Ki-Seon, Son, Sung-Young, Economic analysis of heating and cooling systems from the various perspectives: Application to EHP and GHP in Korea, Renewable and Sustainable Energy Reviews, 2012
  4. M&V Guidelines : Measurement and Verification for Federal Energy Projects Version 3.0, U.S. Department of Energy
  5. Richard Raustad, Creating Performance Curves for Variable Refrigerant Flow Heat Pumps in EnergyPlus, Florida Solar Energy Center, 2012
  6. 16 Technical guidebook, Aisin, 2016
  7. 윤갑천, 전종욱, 김강수, "에너지시뮬레이션에서의 부하요소가 건물에너지사용량에 미치는 영향 분석", 한국생태환경건축학회, 2011 .08 // (Yoon, Kap-Chun, Jeon, Jong-Ug, Kim, Kang-Soo, Analysis on the Impact of Load Factors in Building Energy Simulation Affecting Building Energy Consumption, Korea Instituts of Ecological Architecture and Environment, 2011. 08)
  8. D.H. Bennett, P.Koutrakis, Determining the infiltration of outdoor particles in the indoor environment using a dynamic model, Journal of Aerosol Science, 2006
  9. Air Conditioning System City Multi Data Book-R410A series, Mitsubishi Electric, 2013
  10. "건축물 에너지효율등급 인증제도 운영규정", 한국에너지공단, 2016 // (Evaluation of energy efficiency of building Certification system operation regulations, Korea Energy Agency, 2012)
  11. 석유환산톤(TOE) 및 이산화탄소배출량(tCO2)자동계산, 한국에너지공단, http://co2.kemco.or.kr/toe/toe.aspx
  12. 탄소배출계수, 한국환경산업기술원, http://www.epd.or.kr/lci/co2.asp
  13. 배출권시장, 한국거래소, http://marketdata.krx.co.kr/
  14. 서울도시가스, http://www.seoulgas.co.kr/front/payment/gasPayTable.do
  15. 한국전력공사, http://cyber.kepco.co.kr/