Abstract
The present study numerically investigates the effect of obstacles located in the trajectory of fire plume flow on heat flow characteristics by using Fire Dynamics Simulation (FDS) software in an underground combined cycle power plant (CCPP). Fire size is taken as 10 MW and two different locations of fire source are selected depending on the presence of an obstacle. As the results, when the obstacle is in the trajectory of fire plume, hot plume arrives at the ceiling about 5 times slower in the upper of the fire in comparison to the results without obstacle. In addition, the average propagation time of ceiling jet increases by about 70 % with the distance from the ceiling in the upper of the fire, and it increases mainly about 4 times at the distance of 10 m. Consequently, it is noted that the analysis of heat flow characteristics in the underground CCPP considering fire scenarios is essential to develop the fire detection system for initial response on evacuation and disaster management.
본 연구에서는 Fire Dynamics Simulation (FDS)를 이용하여 화재 기류 전파 경로 상에 플랜트 설비 유무가 공간 내 열유동 특성에 미치는 영향을 알아보기 위해 화원 위치에 따른 지하 복합 발전 플랜트 내 화재 해석을 수행하였다. 화원의 크기는 10 MW이며, 화원 상부의 장애물(설비)의 유무에 따라 화원 위치가 천장 및 화원 상부에서의 열 기류 선단의 전파 특성을 미치는 영향을 정량적으로 비교분석하였다. 결과로서, 화원 상부에 장애물이 있을 경우, 화재 기류가 화원 상부 천장에 도달하는 시간이 장애물이 없을 때에 비해 약 5 배가량 증가하였다. 화원 상부 천장 벽면의 천장 기류 시작 지점으로부터 거리에 따른 각 지점에서 열 기류 선단의 전파 시간의 평균적으로 장애물이 없는 경우에 비해 약 70% 가량 증가하였으며, 특히 10 m 지점에서는 4 배 가까이 증가하였다. 이는 장애물이 화원으로부터 발생하는 수직 열기류의 흐름을 방해하고, 장애물 뒤 쪽에 불안정한 후류가 형성되었기 때문이다. 따라서 지하복합 발전 플랜트 내 피난 및 재난 관리의 초기 대응 목적의 화재 감지 설비 시스템 설계 시 화재 시나리오에 따른 열유동 분석이 중요할 것으로 판단된다.