초록

Recently there is a growing interest in the airborne spread of virus. In particular, there is growing interest in secondary infection through the air in the hospital. The distribution of air-born virus depends on ventilation system installed in a hospital. In this study, simulations were carried out to predict the move of air-born virus by ventilation system at hospital. Simulation results showed that pressure distribution was -372.05Pa ~ -3.45 Pa at 1st floor incase of only used mechanical exhaust at bathroom, shower stall, storage, kitchen etc.. if ventilation switch from used mechanical exhaust to mechanical exhaust & mechanical supply. Simulation results showed that pressure distribution was -336.44Pa at stair hall < -0.2Pa at bathroom < mean 1.19Pa at other room. So simulation results showed that using all of the mechanical supply and mechanical exhaust was more effective then the mechanical exhaust for maintain the pressure distribution in hospital. It was also showed that when using the mechanical supply and mechanical exhaust more effectively prevention of air born virus diffusion.

키워드

참고문헌

  1. S. G. Choi, J. K. Hong, 2005, The study on the performance estimation of UVC air sterilizer for preventing transmission of air borne contagion ,v.17n.6. , Journal of SAREK
  2. S. G. Choi, W. H. Lee, J. K. Hong, 2006, A Study on the Multizone Modeling for Preventing Transmission of Air Borne Contagion , v.18 n.11., Journal of SAREK
  3. K. b. Jeong, S. G. Choi, 2009, UV Immune System of Personalized Space, v.21n.01 , Journal of SAREK
  4. S. G. Choi, 2010, A Study of air Sterilization System in Personalized Office Using Simulation, v.22n.06 , Journal of SAREK
  5. S. G. Choi, 2012, A Study on CFD analysis of indoor microbe transport for microbiological safety, v.14, n.3, Journal of the Korea Safety Management and Science
  6. S. G. Choi, 2012, A Study on CFD analysis of indoor airborne microbe transport in car for microbiological safety, v.15, n.4, Journal of the Korea Safety Management and Science
  7. ANSYS Inc., CFX Uer's Guide, 2011, ANSYS Inc
  8. Kowalski, W. J., Bahnfleth, W. P., Whittam D. L., Severin, B.F., Whittam,T.S,. Mathematical modelling of ultraviolet germicidal irradiation for air disinfection, Quantitative Microbiology 2, 249-270, 2000. https://doi.org/10.1023/A:1013951313398
  9. Bratbak, G. A., Dundas, I. 1984. Bacterial dry matter content and biomass estimations. Appl. Environ. Microbiol., 48, 755-757.