DOI QR코드

DOI QR Code

Heat Transfer and Sterilization Characteristics of an ERV Element Made of Hwang-to Paper

황토지로 제작된 전열교환소자의 전열특성 및 항균특성에 관한 연구

  • Received : 2016.11.11
  • Accepted : 2017.02.09
  • Published : 2017.02.28

Abstract

To increase the enthalpy exchange efficiency of ERV elements, the moisture exchange character must be improved. The moisture exchange efficiency depends on material characteristics. The material used for ERV is Hwang-to paper based on Han-ji which is Korean traditional paper. The paper has excellent performance in moisture exchange and heat transfer compared with polymer and other papers. To have an anti bacteria performance and to improve moisture exchange performance of Han-ji, Hwang-to is added to the Han-ji. The enthalpy exchange efficiency of the Hwang-to paper shows 5% greater than that of the conventional paper. In case of Escherichia Coli, the reduction rate of bacteria is 96.6% and in case of Pseudomonas, the reduction rate of bacteria is 97.5%. The ERV element made of Hwang-to paper has a great possibility as an ERV element.

Keywords

References

  1. D. W. Bearg, 1993, "Indoor air quality and HVAC Systems", Lewis Publishers.
  2. J. Min and M. Su, 2010, "Performance analysis of a membrane-based enthalpy exchanger: Effect of the membrane properties on the exchanger performance", Journal of Membrane Science, No. 348, pp. 376-382. https://doi.org/10.1016/j.memsci.2009.11.032
  3. J. Min and M. Su, 2010, "Performance analysis of a membrane-based enthalpy exchanger: Effect of the membrane spacing and thickness on the ventilator performance", Applied Thermal Engineering, No. 30, pp. 991-997. https://doi.org/10.1016/j.applthermaleng.2010.01.010
  4. Y. Mayu, S. Hiroaki, T. Takashi, O. Makoto and T. Hirokuni, 2010, "The study on total heat exchange ventilation system in cold region. Part. 2 Examination of heat exchange element property and structure", Proceedings of the Architectural Institute of Japan Symposium, No. 41492, pp. 999-1000.
  5. Y. Mayu, S. Hiroaki, T. Takashi, O. Makoto and T. Hirokuni, 2010, "The study on total heat exchange ventilation system in cold region. Part.3 Calculation of heat exchange efficiency and development for new heat exchange element", Proceedings of the Architectural Institute of Japan Symposium, No. 060, pp. 239-242.
  6. N. H. Kim, E. J. Lee, K. S. Song and W. K. Oh, 2010, "Thermal performance of an enthalpy exchanger made of paper at different outdoor temperatures and humidities", Transaction of the Korean Society of Mechanical Engineers: B, Vol. 34, No. 7, pp. 697-702. https://doi.org/10.3795/KSME-B.2010.34.7.697
  7. K. H. Kim and J. J. Yee, 2008, "A study on operating method by energy evaluation and performance evaluation of heat recovery ventilator according to outdoor conditions", Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 20, No. 1, pp. 57-64.
  8. S. Y. Choi, J. J. Yee, M. J. Park, S. K. Kim, and K. H. Kim, 2009, "A performance prediction on the element cores of total heat recovery ventilator according to outdoor conditions", Journal of Architectural Institute of Korea, Vol. 25, No. 2, pp. 241-248.
  9. C. H. Bae, Y. H. Lim, J. Y. Park, K. M. Kwak, E. S. Ju, Y. S. Kim, and J. Y. Kim, 2005, "A Study on the Characteristics of Total Heat Exchanger under Various Conditions", Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No. 10, pp. 891-897.
  10. R. L. Webb, "Heat Exchanger Design", Lecture Overhead Materials, 1994.
  11. ASHRAE, "Method of Testing Air to Air Heat Exchangers", Ashrae Handbook 84-1991, 1991
  12. JIS B 8628, 2000, Air to air heat exchangers.
  13. H. M. Jung, H. Y. Choi, H. Z. Hwang, M. H. Hong and M. H. Kim, 1997, "The research on the general properties of Red-Clay", Proceedings of Architectural Institute of Korea, Vol. 17, No. 2, pp. 1251-1255.
  14. KS M 7020, 2001, Paper and board - Determination of air permeability(medium range) - Part 5: Gurley method, Korean Standard.