초록

This study aimed to develop a method to optimize residual chlorine concentrations in the process of providing water supply. To this end, this study developed a model capable of optimizing the chlorine input into the clearwell in the purification plant and the optimal installation location of rechlorination facilities, and chlorine input. This study applied genetic algorithms finding the optimal point with appropriate residual chlorine concentrations and deriving a cost-optimal solution. The developed model was applied to SN purification plant supply area. As a result, it was possible to meet the target residual chlorine concentration with the minimum cost. Also, the optimal operation method in target area according to the water temperature and volume of supply was suggested. On the basis of the results, this study derived the most economical operational method of coping with water pollution in the process of providing water supply and satisfying the service level required by consumers in the aspects of cost effectiveness. It is considered possible to appropriately respond to increasing service level required by consumers in the future and to use the study results to establish an operational management plan in a short-term perspective.

키워드

참고문헌

  1. Ayvaz, M. T. and Kentel, E. (2014) Identification of the best booster station network for a water distribution system. Journal of Water Resources Planning and Management, 141(5), 04014076. DOI: 10.1061/(ASCE)WR.1943-5452.0000473.
  2. Boccelli, D., Tryby, M., Uber, J. and Summers, S. (2003) A reactive species model for chlorine decay and THM formation under rechlorination conditions. Water Research, 37(11), 2654-2666. DOI: 10.1016/S0043-1354(03)00067-8.
  3. Chu, C. W., Lin, M. D. and Tsai, K. T. (2008) Optimal scheduling of booster chlorination with immune algorithm, 2008 International Conference on Convergence and Hybrid Information Technology (ICCIT 2008), Pusan, Korea, IEEE, DOI: 10.1109/ICCIT.2008.411.
  4. Ekos Research Associates INC, (2011) Perceptions of drinking water quality in first nations communities and general population, Ekos Research Associates, Ontario, Canada, p.129.
  5. Kim, D. H., Lee, D. J., Kim, K. P., Bae, C. H. and Joo, H. E. (2010) Computing the dosage and analysing the effect of optimal rechlorination for adequate residual chlorine in water distribution system. Journal of Korean Society of Environmental Engineers, 32(10), 916-927.
  6. Kramer, H., Douglas, R. A. and Ulmann, R. M. (1959) The diffusivity of chlorine in water. Chemical Engineering Science, 10(3), 190-191. https://doi.org/10.1016/0009-2509(59)80046-4
  7. K-water, (2014) 2013 Statistics of waterworks, K-water, Daejeon, p.1766.
  8. LeChevallier M. W., Welch N. J. and Smith D. B. (1996) Full-scale studies of factors related to coliform regrowth in drinking water. Applied and Environmental Microbiology. 62(7), 2201-2211.
  9. Lee, J. S, (2007) Hydraulics, Goomibook, Seoul, p.725.
  10. Munavalli, G. R. and Mohan-Kumar, M. S. (2003) Optimal scheduling of multiple chlorine sources in water distribution systems. Journal of Water Resources Planning and Management, 129(6), 493-504. DOI: 10.1061/(ASCE)0733-9496(2003)129:6(493).
  11. Ohar, Z. and Ostfeld, A. (2014) Optimal design and operation of booster chlorination layout in water distribution systems. Water Research, 58, 209-220. DOI: 10.1016/j.watres.2014.03.070.
  12. Ostfeld, A. and Salomons, E. (2006) Conjunctive optimal scheduling of pumping and booster chlorine injections in water distribution systems. Engineering Optimization, 38(3), 337-352. DOI: 10.1080/03052150500478007.
  13. Powell, J., West, J., Hallam, N., Forster, C. and Simms, J. (2000) Performance of Various Kinetic Models for Chlorine Decay. Journal of Water Resources Planning and Management, 126(1), 13-20. DOI: 10.1061/(ASCE)0733-9496(2000)126:1(13).
  14. Prasad, T., Walters, G. and Savic, D. (2004) Booster disinfection of water supply networks : Multiobjective approach. Journal of Water Resources and Management, 130(5), 367-376. DOI: 10.1061/(ASCE)0733-9496(2004)130:5(367).
  15. Rossman, L. A., Boulos P. F. and Altman, T. (1993) Discrete Volume-Element Method of for Network Water Quality Models. Journal of Water Resource Planning and Management, 119(5), 505-517. DOI: 10.1061/(ASCE)0733-9496(1993)119:5(505).
  16. Sert, C. (2009) Booster disinfection in water distribution networks, Master Thesis, Middle East Technical Univ., Ankara, Turkey.
  17. Tryby, M. E., Bocelli, D. L., Uber, J. G. and Rossman, L. A. (2002) Facility location model for booster disinfection of water supply networks, Jounal of Water Resources Planning and Management, 128(5), 322-333. DOI: 10.1061/(ASCE)0733-9496(2002)128:5(322).
  18. Wang, H. and Guo, W. (2010) Ant colony optimization for booster chlorination stations of water distribution systems, 2010 International Conference on Computer Application and System Modeling (ICCASM 2010), Taiyuan, China, IEEE, DOI: 10.1109/ICCASM.2010.5619048.
  19. Wang, H., Guo, W., Xu, J., and Gu, H. (2010) A hybrid PSO for optimizing locations of booster chlorination stations in water distribution systems, 2010 International Conference on Intelligent Computation Technology and Automation (ICICTA 2010), Changsha, China, IEEE, DOI: 10.1109/ICICTA.2010.505.