DOI QR코드

DOI QR Code

개선된 Dry Air와 SF6의 혼합비에 따른 절연파괴 특성 연구

A Study on Characteristics of Insulation Breakdown by the Mixing Ratio of enhanced Dry Air and SF6

  • 투고 : 2015.12.01
  • 심사 : 2016.01.06
  • 발행 : 2016.03.31

초록

It is very desirable that a mixture gas possessing excellent insulation performance is suggested for insulation on increasing high voltage. This paper proposes a $SF_6$ mixture gas based on the factors including dielectric strength, environmental impact and economic feasibility of manufacture for the insulation in eco-friendly power equipment. A suitable-$SF_6$ content was determined to improve the dielectric strength in $N_2$ and Dry Air. The examination results of the factors revealed that a $SF_6$/Dry Air mixture gas possessing the $SF_6$ content was more appropriate than a $SF_6/N_2$ mixture gas to the eco-friendly power equipment. In addition to the selection of the suitable $SF_6$ mixture gas, insulation characteristics as a function of $SF_6$ content were described from electron-detachment mechanism.

키워드

참고문헌

  1. L. G. Christophorou, J. K. Olthoff and R. J. Van Brunt, "Sulfur Hexafluoride and the Electric Power Industry", IEEE Electr. Insul. Mag., Vol. 13, No. 5, pp. 20-24, 1997. https://doi.org/10.1109/57.620514
  2. H. Toyota, S. Matsuoka, and K. Hidaka, "Measurement of Sparkover Voltage and Time Lag Characteristics in $CF_3I-N_2$ and $CF_3I$-Air Gas Mixtures by using Steep-Front Square Voltage", Electr. Eng. Jpn., Vol. 157, No. 2, pp. 1-7, 2006.
  3. T. Rokunohe, Y. Yagihashi, K. Aoyagi, T. Oomori and F. Endo, "Developrrent of $SF_6$-free 72.5 kV GIS", IEEE Trans. Power Deliv., Vol. 22, No. 3, pp. 1869-1876, 2007. https://doi.org/10.1109/TPWRD.2007.899273
  4. H. Saito, K. Nagatake, H. Komatsu, Y. Takeshi, Y. Matsui, k. Katslmata, and M. Sakaki, "Development of 72/84kV Dry Air-Insulated Dead Tank VCB", Electr. Eng. Jpn., Vol. 177, No. 1, pp. 1-10 2011.
  5. Y. Hoshina, M. Sato, M. Shiiki, M. Hanai and E. Kaneko, "Lightning impulse breakdown characteristics of $SF_6$ alternative gases for gas-insulated switchgear", IEE Proc.-Sci. Meas. Technol., Vol. 153, No. 1, pp. 1-6, 2006. https://doi.org/10.1049/ip-smt:20050007
  6. 大陽日酸東関東株式会社, "六フッ化硫($SF_6$)の回収技術", J . Vac. Soc. Jpn, Vol. 52, No. 7, pp. 397-399, 2009. https://doi.org/10.3131/jvsj2.52.397
  7. H. Okubo, A. Beroual, "Recent Trend and Future Perspectives in Electrical Insulation Techniques in Relation to Sulfur Hexafluoride ($SF_6$) Substitutes for High Voltage Electric Power Equipment," IEEE Electr. Insul. Mag., Vol. 27, No. 2, pp. 34-42, 2011.
  8. T. Takuma, O. Yamamoto and S. Hamada, "GASES AS A DIELECTRIC," Gaseous Dielectrics X, pp. 195-204, 2004.
  9. N. H. Malik and A. H. Qureshi, "BREAKDOWN GRADIENTS IN $SF_6{^-}N_2$, $SF_6{^-}AIR$, $SF_6{^-}CO_2$ MIXTURES", IEEE Trans. Electr. Insul., Vol. EI-15, No. 5, pp. 413-418, 1980. https://doi.org/10.1109/TEI.1980.298335
  10. T. Watanabe and T. Takuma, "The Breakdown Voltage and Discharge Extension of Long Gaps in Nitrogen-$SF_6$ and Air-$SF_6$ Gas Mixtures", J. Appl. Phys., Vol. 48, pp. 3281-3287, 1977. https://doi.org/10.1063/1.324208
  11. X. Q. Qiu, I. D. Chalmers, P. Coventry, "A Study of Alternative Insulating Gases to $SF_6$", J. Phys. D: Appl. Phys., Vol. 32, pp. 2918-2922, 1999. https://doi.org/10.1088/0022-3727/32/22/314
  12. H. Okubo, T. Yamada, K. Hatta, N. Hayakawa, S. Yuasa and S. Okabe, "Partial discharge and breakdown mechanisms in ultra-dilute $SF_6$ and PFC gases mixed with $N_2$ gas", J. Phys. D: Appl. Phys., Vol. 35, pp. 2760-2765, 2002. https://doi.org/10.1088/0022-3727/35/21/311
  13. L. G. Christophorou, J. K. Olthoff and D. S. Green, "A Search for Possible Universal-Application Gas Mixtures", Gaseous Dielectrics VIII, pp. 361-366, 1998.
  14. T. Rokunohe, Y. Yagihashi, F. Endo, and T. Oomori, "Fundamental Insulation Characteristics of Air, $N_2$, $CO_2$, $N_2/O_2$ and $SF_6/N_2$ Mixed Gases", Electr. Eng. Jpn., Vol. 155, No. 3, pp. 9-17, 2006.
  15. J. H. Seok, J. H. Beak, D. Y. Lim, S. Bae, K. C. Kim and W. Z. Park, "A Study on Characteristics of Insulation Breakdown and Surface Discharge by the Mixing Ratio of Dry $Air/O_2$ gas mixtures", J Korean Inst. IIIum. Electr. Install. Eng., Vol. 29, No. 6, pp. 49-57, 2015.
  16. J. H. Mason, "Discharges", IEEE Trans. Electr. Insul, Vol. EI-13, No. 4, pp. 211-238, 1978. https://doi.org/10.1109/TEI.1978.298074
  17. D. Y. Lim and S. Bae, "Study on Oxygen/Nitrogen Gas Mixtures for the Surface Insulation Performance in Gas Insulated Switchgear", IEEE Trans. Dielectr. Electr. Insul., Vol. 22, No. 3, pp. 1567-1576, 2015. https://doi.org/10.1109/TDEI.2015.7116352
  18. L. G. Christophorou and L. A. Pinnaduwage, "Basic Physics of Gaseous Dielectrics", IEEE Trans. Dielectr. Electr. Insul., Vol. 25, No. 1, pp. 55-74, 1990. https://doi.org/10.1109/14.45234
  19. S. Pancheshnyi, "Effective ionization rate in nitrogen-oxygen mixtures", J. Phys. D: Appl. Phys., Vol. 46, No. 15, 155201, 2013. https://doi.org/10.1088/0022-3727/46/15/155201
  20. G. Wormeester, S. Pancheshnyi, A. Luque, S. Nijdam and U. Ebert, "Probing photo-ionization: simulations of positive streamers in varying $N_2:O_2{^-}mixtures$", J. Phys. D: Appl. Phys., Vol. 43, 505201, pp. 1-13, 2010.
  21. J. K. Olthoff, R. J. Van Brunt, Y. Wang, R. L. Champion and L. D. Doverspike, "Collisional Electron Detachment and Decomposition Rates of $SF_6{^-}$, SF5- and F- in $SF_6$: Implications for Ion Transport and Electrical Discharges", J. Chem. Phys. Vol. 91, pp. 2261-2268, 1989. https://doi.org/10.1063/1.457646
  22. R. Morrow, "Theory of electrical corona in $SF_6$", Nucl. Instr. and Meth. in Phys. Res. A 382, pp. 57-65, 1996. https://doi.org/10.1016/S0168-9002(96)00504-9
  23. H. Kojima, O. Kinoshita, N. Hayakawa, F. Endo, H. Okubo, M. Yoshida and T. Ogawa, "Brekdown Characteristics of $N_2O$ Gas Mixtures for Quasi Uniform Electric Field under Lightning Impulse Voltage", IEEE Trans. Dielectr. Electr. Insul., Vol. 14, No. 6, pp. 1492-1497, 2007. https://doi.org/10.1109/TDEI.2007.4401233
  24. D. Y. Lim, E. H. Choi, S. T. Choi, B. J. Choi, K. S. Lee and S. Bae, "Surface Flashover Characteristics on Poor Contact in $N_2/O_2$ Mixture Gas under Non-Uniform Field", J Korean Inst. IIIum. Electr. Install. Eng., Vol. 29, No. 8, pp. 63-69, 2015.