DOI QR코드

DOI QR Code

A Study on the Properties Analysis of an Iron Fittings Type CSST Damaged by the PCITS

PCITS에 의해 소손된 강이음쇠형 CSST의 특성 해석에 관한 연구

  • 이장우 (전주대학교 소방안전공학과) ;
  • 최충석 (전주대학교 소방안전공학과)
  • Received : 2016.07.22
  • Accepted : 2016.08.16
  • Published : 2016.08.31

Abstract

This study analyzed the structural and electrical characteristics of an iron fittings type Corrugated Stainless Steel Tubing (CSST) damaged by the Primary Current Injection Test System (PCITS). CSST consists of cladding, tube, nuts, clamp ring, flare cap, socket, and ball valve. For an evaluation of the dielectric withstand voltage, the area between the live part and non-live part of the CCST shall withstand a voltage of 220 V AC for one minute. For an evaluation of the insulation performance by 500 V DC, it is required that the insulation exceed more than $1M{\Omega}$ before the temperature rise test, $0.3M{\Omega}$ after the test. Although the average resistance of the product was $11.5m{\Omega}$, that of the product damaged at a current of 130 A by the PCITS was $11.50m{\Omega}$. Furthermore, parts of the cladding were melted and black smoke appeared when a current of 130 A applied for 10 s. After 60 s, most parts were heated and turned red. At 120 s, the parts that turned red had widened. Although it did not form a normal distribution because the P value was 0.019 with a confidential interval of 95%, it revealed outstanding characteristics with an AD (Anderson-Darling) value of 0.896 and a standard deviation of 0.5573.

본 논문에서는 대전류공급장치(PCITS)에 의해 소손된 강이음쇠형(iron fittings type) 금속플렉시블호스(CSST)의 구조 및 전기적 특성을 해석하였다. CSST는 보호 피막, 튜브, 너트, 클램프 링, 플레어 캡, 소켓, 볼 밸브 등으로 구성되어 있다. CSST의 내전압 평가는 전기 충전부와 비충전부 사이에 교류 전압 220 V를 1분간 인가하여 견뎌야 한다. 직류 500 V에 의한 절연 성능의 평가는 온도 상승 시험 전에 $1M{\Omega}$ 이상, 시험이 끝난 후에는 $0.3M{\Omega}$ 이상을 요구한다. 정상 제품의 평균 저항은 $11.5m{\Omega}$이었으나 PCITS로 130 A를 흘려 소손된 제품의 평균 저항 $11.50m{\Omega}$이었다. 또한 130 A가 약 10 s 흘렀을 때 튜브의 보호 피막이 일부 용융되었고, 검정색의 연기가 발생하였다. 60 s 경과되면 튜브의 대부분이 적색으로 발열되며, 전류가 120 s 흘렀을 때는 적열 범위가 넓어졌다. 95%의 신뢰 구간(CI)의 검증에서 P 값은 0.019로 정규 분포를 갖지 못하였으나 Anderson-Darling (AD) 통계량은 0.896, 표준 편차는 0.5573 등으로 양호한 특성을 나타냈다.

Keywords

References

  1. Ministry of Public Safety and Security, "Fire Statistic Status", National Fire Date System (2016).
  2. Korea Gas Safety Corporation, "Gas Statistic", pp. 3-9 (2016).
  3. Korea Standard Association, "KS D 3589 Extruded Polyethylene Coated Steel Pipes" (2014).
  4. Korea Standard Association, "KS D 3514 Polyethylene (PE) Pipes for the Supply of Gaseous Fuel" (2016).
  5. Korea Standard Association, "KS D 3631 Extruded Polyethylene Coated Steel Pipes" (2015).
  6. Korea Gas Safety Corporation, "KGS AA 534 Facilities . Technology . Inspection Code for Manufacture of Polyvinyl Chloride Hoses for Gases" (2015).
  7. Korea Gas Safety Corporation, "KGS AA 535 Facilities . Technology . Inspection Code for Manufacture of Corrugated Stainless Steel Tubing for Gases" (2016).
  8. Korea Standard Association, "KS D 3625 Metallic Flexible Hoses for Gas" (2014).
  9. Korean Fire Protection Association, "NFPA 921 Gaide for Fire & Explosion Investigation", pp. 313-316 (2009).
  10. Korea Standard Association, "KS D 3698 Cold Rolled Stainless Steel Plates Sheet and Strip" (2015).
  11. K. M. Moon, Y. H. Kim, J. D. Kim, M. H. Lee and J. G. Kim, "Electrochemical Evaluation of Corrosion Property of Welding Zone of 304 Stainless Steel", Journal of Ocean Engineering and Technology, Vol. 23, No. 4, pp. 58-63 (2009).
  12. Korea Gas Safety Corporation, "KGS AB 133 Facilities . Technology . Inspection Code for Manufacture of CF (conventional flue) and BF (balanced flue) Type of Gas Boilers", p. 12 (2016).
  13. Korea Gas Safety Corporation, "KGS AB 131 Facilities . Technology . Inspection Code for Manufacture of FE (forced exhaust) and FF (forced flue or forced feedexhaust) Type of Boilers", p. 13 (2016).
  14. Korea Gas Safety Corporation, "KGS AB 333 Facilities . Technology . Inspection Code for Manufacture of Gas Oven Ranges", p. 9 (2016).
  15. Korea Gas Safety Corporation, "KGS AB 333 Facilities . Technology . Inspection Code for Manufacture of Gas Ovens", p. 10 (2016).
  16. Korea Standard Association, "KS B 8115 Gas Burning Oven Ranges", p. 12 (2013).
  17. Korea Standard Association, "KS B 8109 Gas Burning Hot Water Boiler", p. 10 (2014).
  18. J. H. Lee and C. S. Choi, "Carbonization Patten and Operation Characteristics of 1F a 2w MCCB Damaged by PCITS", Korean Institute of Fire Science & Engineering, Vol. 28, No. 5, pp. 8-13 (2014).