DOI QR코드

DOI QR Code

Diagnosis of Poor Contact Fault in the Power Cable Using SSTDR

SSTDR을 이용한 케이블의 접촉 불량 고장 진단

  • Kim, Taek-Hee (Electrical safety Research Institute, Korea Electrical Safety Co.) ;
  • Jeon, Jeong-Chay (Electrical safety Research Institute, Korea Electrical Safety Co.)
  • Received : 2016.07.01
  • Accepted : 2016.07.27
  • Published : 2016.08.01

Abstract

This paper proposes a diagnosis to detecting poor contact fault and fault location. Electrical fire by poor contact fault of power cable occupied a large proportion in the total electrical installations. The proposed method has an object to prevent electrical fault in advance. But detecting poor contact fault is difficult to detect fault type and fault location by using conventional reflectometry due to faults generated intermittently and repeatedly on the time change. Therefore, in this paper poor contact fault and fault conditions were defined. System generating poor contact fault produced for the experimental setup. SSTDR and algorithm of reference signal elimination heighten performance detecting poor contact fault on live power cable. The diagnosis methods of signal process and analysis of reflected signal was proposed for detecting poor contact fault and fault location. The poor contact fault and location had been detected through proposed diagnosis methods. The fault location and error rate of detection were verified detecting accuracy by experiment results.

Keywords

References

  1. Korea Electrical Safety Corporation, "A Statistical Analysis on the Electrical Accident", 2014
  2. Paul Smith, "Spread spectrum time domain reflectometry", Ph. D. dissertation, Dept. Elect. Comput.Eng., Utah Univ., Logan, 2003
  3. P. Smith, C. Furse, and J. Gunther, "Analysis of spread spectrum time domain reflectometry for wire fault location", IEEE Sensors J., Vol. 5, No. 6, pp. 1469-1478, Dec. 2005. https://doi.org/10.1109/JSEN.2005.858964
  4. Cynthia Furse, Paul Smith, Mehdi Safavi and Chet Lo, "Feasibility of Spread Spectrum Sensors for Location of Arcs on Live Wires", IEEE Sensors Journal, Vol. 5, No. 6, pp. 1445-1450, Dec. 2005. https://doi.org/10.1109/JSEN.2005.858900
  5. Jin-man Kim, Bong-Hyuk Choi, Jin-woo Jo, Won-bum Jo, "Low-cost CAP-type TDR Exploration Techniques for Leak Detection", KSCE, Vol. 33, No. 4, pp. 1479-1487 July 2013. https://doi.org/10.12652/Ksce.2013.33.4.1479
  6. Cae-Kyun Jung, Jun-woo Park, Kyung-hee Mun, Byung-mo Yang, Ji-won Kang, "Validation of Propagation Velocity through TDR Test in HVDC Submarine Cables", KIEE, Vol. 58, No. 10, pp. 1888-1894, Oct 2009.
  7. Chun-gu Lee, Tae-sung Yun, Jin-bae Park, "Localization of Concentric Neutrals Corrosion on Live Underground Power Cable Based on Time-Frequency Domain Reflectometry", KIEE, Vol. 62, No. 2, pp. 239-245, Feb 2013.
  8. Jeong-chay Jeon, Taek-hee Kim, Jae-Geun Yoo, "Fault Detection of Low-voltage Cable using Time-Frequency Correlation in SSTDR", KIEE, Vol. 64, No. 3, pp. 498-504, March 2015
  9. Jeong-chay Jeon, Taek-hee Kim, "Cable Fault Detection Improvement of STDR Using Reference Signal Elimination", KAIS, Vol. 17, No. 3, pp. 450-456, March, 2016
  10. IEEE Standards Board, IEEE Recommended Practice for Monitoring Electric Power Quality, IEEE Std 1159-1995, pp.4-16, June 14, 1995
  11. Cynthia Furse, Paul Smith, "Spread Spectrum Time Domain Reflectometry for Locating Intermittent Faults", IEEE SENSORS JOURNAL, Vol. 5, No. 6, DECEMBER 2005
  12. Taek-hee Kim, Jeong-chay Jeon, Jae-gean Yoo, "Performance Improvement of STDR using the Removal of a Reference Signal", KIEE Summer Conference, pp. 1527-1528, July 2015
  13. Chirag R. Sharma, Cynthia Furse and Reid R. Harrison, "Low-Power STDR CMOS Sensor for Location Faults in Aging Aircraft Wiring", IEEE Sensors Journal, Vol.7, No.1, pp. 43-50, Jan. 2007 https://doi.org/10.1109/JSEN.2006.886866