Zero Sequence Impedance of Yg-Yg Three Phase Core Type Transformer

Yg-Yg 3상 내철형 변압기의 영상분 임피던스 분석

  • Jo, Hyunsik (Department of Electrical Engineering, Chungnam National University) ;
  • Cho, Sungwoo (Department of Electrical Engineering, Chungnam National University) ;
  • Shin, Changhoon (Department of Electrical Engineering, Chungnam National University) ;
  • Cha, Hanju (Department of Electrical Engineering, Chungnam National University)
  • Received : 2015.12.16
  • Accepted : 2016.04.29
  • Published : 2016.06.01

Abstract

In this paper, zero sequence equivalent circuit of Yg-Yg three phase core-type transformer is analyzed. Many problems by iron core structure of the three phase transformer due to asymmetric three phase lines, which includes line disconnection, ground fault, COS OFF, and unbalanced load are reported in the distribution system. To verify a feasibility of zero sequence impedance of Yg-Yg type three phase transformer, fault current generation in the three phase core and shell-type Yg-Yg transformer is compared by PSCAD/EMTDC when single line ground fault is occurred. As a result, shell-type transformer does not affect the flow of fault current, but core-type transformer generate an adverse effect by the zero sequence impedance. The adverse effect is explained by the zero sequence equivalent circuit of core-type transformer and Yg-Yg type three phase core-type transformer supplies a zero sequence fault current to the distribution system.

Keywords

References

  1. Dong-Yeol SHIN, Yong-woo Park and Hanju Cha, "A Case Study on Malfunction of OCGR and Inaccuracy of Watt-hour Meter in Distributed Generation System", The Transactions of the Korean Institute of Electrical Engineers, vol. 57, No. 8, pp. 1349-1355, August, 2008.
  2. Tae-Hoon Kim and Jun-Yeal Park, "Winding Method of Transformer for Zero-Sequence and Negative-Sequence Harmonic Elimination", The Transactions of the Korean Institute of Electrical Engineers, vol. 63, No. 7, pp. 896-902, July, 2014. https://doi.org/10.5370/KIEE.2014.63.7.896
  3. Dong-Yeol Shin, Donghyun Yun and HanJu Cha, "Problem Analysis by Iron Core Structure of the Transformer on Asymmetric three Phase lines and Prevention Measures", The Transactions of the Korean Institute of Electrical Engineers, vol. 61, No. 10, pp. 1536-1541, October, 2012. https://doi.org/10.5370/KIEE.2012.61.10.1536
  4. Yong-Cheol Kang, Soon-Hong So, Jong-Min Park, Mu-Sun Lee, Sung-Il Jang and Yong-Gyun Kim, "Current Differential Relaying Algorithm for Power Transformer Protection Operating in Conjunction with a CT Compensating Algorithm", The Transactions of the Korean Institute of Electrical Engineers, vol. 56, No. 11, pp. 1873-1878, November, 2007.
  5. KS C IEC 60076-8 Power transformer - Guideline for Applying
  6. Distributed power distribution grid connected technologies Guideline, KEPCO, Distribution Construction Department, March, 2010.

Cited by

  1. Stand-Alone Microgrid Inverter Controller Design for Nonlinear, Unbalanced Load with Output Transformer vol.7, pp.4, 2018, https://doi.org/10.3390/electronics7040055