DOI QR코드

DOI QR Code

Section Voltage Calculation while a Loop Operation by Tie-Switch Close in a Distribution Management System

배전운영 시스템에서 상시개방 연계 스위치 투입에 의한 루프 운전 중 구간전압 계산 방법

  • Received : 2015.05.28
  • Accepted : 2016.01.15
  • Published : 2016.03.01

Abstract

Generally, an electrical distribution configuration is a radial system with one-way current in a distribution management system (DMS). All feeders in a DMS have tie-switches to make radial system. Sometimes, DMS should change a tie-switch for operation. In that case, the tie-switch has to be closed first; then a switch is opened as another tie-switch in order to prevent blackout for customers. At the moment when the tie-switch is closed, distribution system is operated in a loop state, not radial. Before the loop operation, DMS operator has to check any expected events for stable distribution system operation; and the most important event is a mis-operation of a protection relay. In addition, DMS operator should check voltage profile violation but a calculation method of section voltages had not been used. Thus, this paper proposes a calculation method of section voltages at a loop operation in a DMS. The proposed calculation algorithm is verified by Matlap Simulink.

Keywords

References

  1. Yuntao Ju, Wenchuan Wu, Boming Zhang, Hongbin Sun, "Loop-analysis-based continuation power flow algorithm for distribution networks," IET Generation, Transmission & Distribution, Vol 8, pp. 1284-1292, 2014. https://doi.org/10.1049/iet-gtd.2013.0529
  2. V. Glamocanin, V. Filipovic, "Open loop distribution system design." IEEE Transactions on Power Delivery, Vol. 8, pp. 1900-1906, 1993. https://doi.org/10.1109/61.248300
  3. Ji-Yuan Fan, Lan Zhang, J.D. McDonald, "Distribution network reconfiguration: single loop optimization," IEEE Transactions on Power Systems, Vol 11. pp. 1643-1647, 1996. https://doi.org/10.1109/59.535709
  4. W.H. Kersting, "The Simulation of Loop Flow in Radial Distribution Analysis Programs," IEEE Transactions on Industry Applications, Vol. 51, pp. 1928-1932, 2015. https://doi.org/10.1109/TIA.2014.2354513
  5. Jun Qiu, H. Chen, A.A. Girgis, "Dynamic modeling and parameter estimation of a radial and loop type distribution system network," IEEE Transactions on Power Systems, Vol. 8, pp. 483-490, 1993. https://doi.org/10.1109/59.260836
  6. Jong-Fil Moon, Jin-Seok Kim, "Voltage Sag Analysis in Loop Power Distribution System With SFCL," IEEE Transactions on Applied Superconductivity, Vol. 23, part 2, 2013.
  7. M.A., Sayed, T. Takeshita, "Line Loss Minimization in Isolated Substations and Multiple Loop Distribution Systems Using the UPFC," IEEE Transactions on Power Electronics, Vol. 29, pp. 5813-5822, 2014. https://doi.org/10.1109/TPEL.2014.2301833
  8. M. A. Sayed, T. Takeshita, "All Nodes Voltage Regulation and Line Loss Minimization in Loop Distribution Systems Using UPFC," IEEE Transactions on Power Electronics, Vol. 26, pp. 1694-1703, 2011. https://doi.org/10.1109/TPEL.2010.2090048
  9. Chao-Shun Chen, Cheng-Ta Tsai, Chia-Hung Lin, Wei-Lin Hsieh, Te-Tien Ku, "Loading Balance of Distribution Feeders With Loop Power Controllers Considering Photovoltaic Generation," IEEE Transactions on Power Systems, Vol. 26, pp. 1762-1768, 2011. https://doi.org/10.1109/TPWRS.2010.2102052
  10. S. Kazemi, M. Fotuhi-Firuzabad, M. Sanaye-Pasand, M. Lehtonen, "Impacts of automatic control systems of loop restoration scheme on the distribution system reliability," IET Generation, Transmission & Distribution, Vol. 3, pp. 891-902, 2009. https://doi.org/10.1049/iet-gtd.2008.0658
  11. J. Brozek, "Hybrid algorithm for optimisation of m-loop electric power distribution networks," IEE Proceedings-Generation, Transmission and Distribution, Vol. 151, pp. 246-251, 2004. https://doi.org/10.1049/ip-gtd:20040052
  12. C.-J. Chou, C.-W. Liu, "Assessment of Risks From Ground Fault Transfer on Closed-Loop HV Underground Distribution Systems With Cables Running in a Common Route," IEEE Transactions on Power Delivery, Vol. 28, pp. 1015-1023, 2013. https://doi.org/10.1109/TPWRD.2012.2235150
  13. Jong Kwan Lee, "A New Method Calculating the Loop Current at Normal-Open-Point for Uninterruptible Load Transfer in Electrical Distribution System," Master thesis of Chungbuk National University, 2015.