DOI QR코드

DOI QR Code

Suggestions of Design Method for a Horizontal Straight Ground Heat Exchanger

수평 직선형 지중 열교환기 설계 방안 제안

  • Kim, Min-Jun (Department of Civil and Environmental Engineering, KAIST) ;
  • Lee, Seung-Rae (Department of Civil and Environmental Engineering, KAIST) ;
  • Yoon, Seok (Radioactive Waste Disposal Division, KAERI) ;
  • Jeon, Jun-Seo (Department of Civil and Environmental Engineering, KAIST)
  • 김민준 (KAIST 건설및환경공학과 대학원) ;
  • 이승래 (KAIST 건설및환경공학과 대학원) ;
  • 윤석 (한국원자력연구원 방사성폐기물처분연구부) ;
  • 전준서 (KAIST 건설및환경공학과 대학원)
  • Received : 2016.08.10
  • Accepted : 2016.11.02
  • Published : 2016.12.01

Abstract

This paper presents a design method for the horizontal straight ground heat exchanger (GHE) based on the Kavanaugh design method. In order to examine suitability of the suggested design method, a horizontal line type GHE was installed in a steel box of which the size was $5m{\times}1m{\times}1m$ filled with dried Joomunjin standard, and a thermal response test (TRT) was conducted for 21 hours. A numerical analysis was performed for a simulation of a peak month operation and for its verification by finite element method (FEM). According to the simulation results, it was concluded that the suggested design method for a horizontal straight GHE is reliable for the estimation of a design length.

Keywords

References

  1. Chang, K. S., Kim, M. J., and Kim, Y. J., 2016, A study on the Thermal Characteristics of Horizontal Ground Heat Exchanger using Thermal Response Test, Journal of the Korea Academia-Industrial cooperation Society, Vol. 17, No. 3, pp. 24-30. https://doi.org/10.5762/KAIS.2016.17.3.24
  2. Congedo, P. M., Colangelo, G., and Starace, G., 2012, CFD simulation of horizontal ground heat exchangers: A comparison among different configurations, Applied Thermal Engineering, Vol. 33-34, pp. 24-32. https://doi.org/10.1016/j.applthermaleng.2011.09.005
  3. Yoon, S., Lee, S. R., and Go, G. H., 2016, Evaluation of thermal efficiency in different types of horizontal ground heat exchangers, Energy and Buildings, Vol. 105, pp. 100-105.
  4. International Ground Source Heat Pump Association., 2011, Ground Source Heat Pump Residential and Light Commercial Design and Installation Guide.
  5. Kavanaugh, S., and Rafferty, K., 1997, Ground-source heat pumps: Design of geothermal systems for commercial and institutional buildings, ASHRAE, USA.
  6. Gaia Geothermal Ground Loop Design Software, GLD2012.
  7. Ministry of Commerce, Industry and Energy., 2007, Development of design package for ground loop heat exchanger of ground source heat pump system.
  8. Bose, J. E., Parker, J. D., and McQuiston, F. C., 1985, Design/data manual for closed-loop ground-coupled heat pump system, ASHRAE, 3-40p.
  9. Kusuda, T. and Achenbach, P. R., 1965, "Earth temperatures and thermal diffusivity at Selected stations in the U.S." ASHRAE Transactions, Vol. 71, Part 1.
  10. New and Renewable Center of Korea Energy Management Corporation, 2015, New and renewable energy equipment guideline.
  11. Kim, M. J., Lee, S. R., Yoon, S., and Go, G. H., 2016, Thermal performance evaluation and parametric study of a horizontal ground heat exchanger Geothermics, Vol. 60, pp. 134-143. https://doi.org/10.1016/j.geothermics.2015.12.009
  12. Yoon, S., Lee, S. R., Go, G. H., Jianfeng, X., Park, H., and Park, D., 2014, Thermal transfer behavior in two types of W-shaped ground heat exchangers installed in multilayer soils, Geomechanics and Engineering, Vol. 6, No. 1, pp. 79-98. https://doi.org/10.12989/gae.2014.6.1.079
  13. Comsol Inc., 2015, Comsol Multiphysics reference manual Version. COMSOL 5.1. USA.