DOI QR코드

DOI QR Code

마찰진자시스템의 마찰계수 변화에 따른 면진된 원전구조물의 거동특성 비교

Seismic Performance Evaluation of Seismically Isolated Nuclear Power Plants Considering Various Velocity-Dependent Friction Coefficient of Friction Pendulum System

  • 석철근 ((주)티이솔루션, 풍동실험팀) ;
  • 송종걸 (강원대학교 토목공학과)
  • 투고 : 2015.06.26
  • 심사 : 2016.01.05
  • 발행 : 2016.03.01

초록

In order to improve seismic safety of nuclear power plant (NPP) structures in high seismicity area, seismic isolation system can be adapted. In this study, friction pendulum system (FPS) is used as the seismic isolation system. According to Coulomb's friction theory, friction coefficient is constant regardless of bearing pressure and sliding velocity. However, friction coefficient under actual situation can be changed according to bearing pressure, sliding velocity and temperature. Seismic responses of friction pendulum system with constant friction and various velocity-dependent friction are compared. The velocity-dependent friction coefficients of FPS are varied between low-and fast-velocity friction coefficients according to sliding velocity. From the results of seismic analysis of FPS with various cases of friction coefficient, it can be observed that the yield force of FPS becomes larger as the fast-velocity friction coefficient becomes larger. Also, the displacement response of FPS becomes smaller as the fast-velocity coefficient becomes larger.

키워드

참고문헌

  1. Wu SC, Yang SM. Dynamics of Mechanical Systems with Coulomb Firciton, Stiction, Impact and Constraint Addition-Deletion- II : Planar Systems. Mechanism and Machine Theory, Vol. 21, 1986.
  2. Constantinou MC, Whittaker AS, Kalpakidis Y, Fenz DM, Warn GP. Performance of Seismic Isolation Hardware under Service and Seismic Loading, MCEER-07-0012, Multidisciplinary Center for Earthquake Engineering Research, State Univ. of New York, Buffalo, NY. c2007.
  3. American Association of State Highway and Transportation Officials. Guide Specification for Seismic Isolation Design. AASHTO. Washington. DC. c2010.
  4. Lysmer J, Ostadan F, Chin CC. A system for analysis of soilstructure interaction, SASSI 2000 theoretical manual. UC Berkeley. c1999.
  5. Mazzoni S, McKenna F, Scott MH, Fenves GL. OpenSees: Open System of Earthquake Engineering Simulation, Pacific Earthquake Engineering Center, Univ. of Calif., Berkeley. Available from: http://opensees.berkeley.edu, [cited 2007].
  6. Federal Emergency Management Agency. NEHRP Commentary on the Guidelines for the Seismic Rehabilitation of Buildings(FEMA 274) Ch. 9. Seismic Isolation and Energy Dissipation, 9-1-9-60, Oct, 1997.
  7. Hancock J, Watson-Lamprey J, Abrahamson NA, Bommer JJ, Markatis A, McCoy E, Mendis R. An improved method of matching response spectra of recorded earthquake ground motion using wavelets. Journal of Earthquake Engineering. 2006;10(S1): 67-89.
  8. Koh. Generation of Target Power Spectral Density Function using Design Response Spectrum, Master's thesis Hanyang University. c2007.
  9. Ronald L. Mayes, Fazard Naeim, The Seismic Design Handbook 2nd Edition Ch.14 Design of Structures with Seismic Isolation. Kluwer Academic Publishers. c2001 p.725-755.
  10. American Society of Civil Engineers, ASCE 7-10; Minimum Design Loads for Buildings and other Structures, ASCE, Reston. c2010.
  11. Nobuo Murota, Maria Q.Feng and Gee-Yu Liu. Experimental and Analytical Studies of Base Isolation System for Sesimic Protection of Power Transformers, MCEER-05-0008, Multidisciplinary Center for Earthquake Engineering Research, 2007.
  12. Kim DK, Kim WB, Suh YP, Moon DS, Kim JY. Seismic Performance Evaluation for MCR of Nuclear Power Plant Isolated by FPS. Proceedings of EESK Conference, Earthquake Engineering Society of Korea. c2003. p.453-460.
  13. Lee KJ, Kim KS, Suh YP. Dynamic Property Evaluation of Friction Pendulum Isolation Bearing. Proceedings of EESK Conference. Earthquake Engineering Society of Korea. c2003. p.465-472.
  14. Mokha, Constaninou and Reinhorn, Experimental Study and Analytical Prediction of Earthquake Response of A Sliding Isolation System With A Spherical Surface. National Center For Earthquake Engineering Research. c1990.

피인용 문헌

  1. A Probabilistic Study on Seismic Response of Seismically Isolated Nuclear Power Plant Structures using Lead Rubber Bearing vol.22, pp.2, 2018, https://doi.org/10.5000/EESK.2018.22.2.045