DOI QR코드

DOI QR Code

Electric Leakage Point Detection System of Underground Power Cable Using Half-period Modulated Transmission Waveform and Earth Electric Potential Measurement

반주기 변조된 송신파형과 대지전위 측정을 이용한 지중 케이블 누전 고장점 탐지 시스템

  • Jeon, Jeong Chay (Electrical Safety Research Institute, Korea Electrical Safety Co.) ;
  • Yoo, Jae-Geun (Department of Electrical Engineering, Jeju International University)
  • Received : 2016.09.02
  • Accepted : 2016.11.02
  • Published : 2016.12.01

Abstract

The precise detection of electric leakage point of underground power cable is very important to reduce cost and time of maintenance and prevent electric shock accident through expedite repair of electric leakage point. This paper proposes a electric leakage point detection system underground power cable using of half-period modulated transmission waveform and earth electric potential measurement. The developed system is composed of transmitter to generate the wanted pulse waveform, receiver to measure and display earth electric potential by the transmitted pulse in electric leakage point and PC Software program to display of GPS coordinate on detection cable line. The performance of the electric leakage point detection system was tested in the constructed underground cable leakage detection test bed. The test results on signal generation voltage precision of signal transmitter, mean detection earth voltage, mean detection leakage current and electric leakage point detection error showed the developed system can be used in electric leakage point detection underground power cable.

Keywords

References

  1. Jung-Ho Lee, "Current Status and Future Prospection of Underground Power Cable Distribution", Korea Electric Association Electrical Journal, Vol. 376, pp. 22-25, 2008
  2. Chong-Min Kim, Woon-Ki Han, et al., "Analysis of Electrical Shock Accidents and Check Results in Domestic and Foreign Low-Voltage Handhole", Journal of the Korean Institute of Illuminating an Electrical Installation Engineers, Vol. 22, 2008
  3. Han-Sang Kim, et al., "A Study on the safety assesment and countermeasure on the low-voltage handhole installed in the road", pp. 86-106, The Ministry of Knowledge Economy, 2007
  4. Hyoung-Jun Gil, et al., "Effect for Ground Impedance Measurement of Counterpoise by Position of Auxiliary Probe and Frequency", Proceedings of KIEE Spring Annual Conference, pp. 158-160, 2010.
  5. Jae-Hee Jung, et al., "Development of the Electric Leakage for Street Lights underground cables", Proceedings of the Korean Institute of Industrial Safety Conference, pp. 305-311, April, 2004.
  6. Thomas Virgil Lathrop, Jamestown, N.C., "Method and apparatus for detecting faults in buried insulated conductors", US Patent 3991363, Bell Telephone Laboratories, 1975. Combinational and Sequential Circuits," ACM/IEE Design Automation Conf., pp. 253-259, 1992.
  7. Jae-Hyun Kim, et al., "The Realization of Magnetic Field Sensor for Underground Cables Locating Systems", Proceedings of KIEE Autumn Annual Conference, pp. 127-129, 2010.
  8. Jae-Hyun Kim, et al., "The measurement of the half period modulated pulse on earth for detection of a underground electric leakage point", Journal of the KICS, Vol. 12, No. 11, pp. 5123-5127, 2011