DOI QR코드

DOI QR Code

A Case Study of Harmonic Resonance & Black Start in Weak Feed Power System

Weak Feed 전력계통의 블랙스타트와 고조파 공진 사례연구

  • Park, Young-Chul (Dept. of Business Development, Korea Southern Power Co., LTD.) ;
  • Lee, Eun-Seob (Dept. of Instrumentation & control, Korea Southern Power Co., LTD.) ;
  • Son, Hyo-Soo (Dept. of Electrical Engineering, Inha University) ;
  • Lee, Seok-Hyun (Dept. of Electrical Engineering, Inha University)
  • Received : 2015.03.19
  • Accepted : 2015.11.26
  • Published : 2016.01.01

Abstract

In order to recover the power system during the wide power outage or power failure in the power plant, black start system should be properly operated without any problem. Especially power for black start in the geographically isolated areas of electric island is supplied from small emergency start-up generator, and loads are aux systems of gas turbines such as SFC(Static frequency converter). This paper introduces the international practices to overcome the voltage drop problem with harmonics of the system having the DC output such as SFC during black start in weak feed system and analyzes the relationship between house load inputs and harmonics. By varying the house load and input of power supply, this paper identified boundaries between weak feed and strong feed power. In order to verify the theory of stable condition in weak feed power system with DC output, house load is simulated using ETAP. Additionally MATLAB was used for harmonic analysis between the load inertia moment and non load inertia moment.

Keywords

References

  1. H. J. Lee, K. S. Lee, S. M. Park, "Analysis of Harmonic Resonance during Restoration of Primary Restorative Transmission System", KIEE Summer conference, pp.220-222, 2005.
  2. IEEE recommended Practices and Requirement for Harmonic Control in Electric power Systems, IEEE Group, IEEE Standard 519, 1992.
  3. P. Kunder, N. J. Balu, M. G. Lauby, "Power System Stability and Control", Mcgraw-Hill, Inc., pp.528-533, 1994.
  4. IEC 1000-3-6 Electromagnetic compatibility(EMC)-Part 3: Limits, section 6 : Assessment of emission limits for distorting in MV and HV power systems, Basic EMC publication, 1996
  5. J. Y. Choi, D. J. Won, "Black start and Synchronization of Microgrid Considering Distributed Generation Control", KIIEE, Vol.62, No.7, pp.898-904, 2013.
  6. C. H. Lim, K. S. Lee, W. K. Yu, H. J. Lee, "A Study on the Analysis of Damping Loads Prevent Harmonic Resonance", KIIEE, Vol59, No.2, pp.262-266, 2010.
  7. R. Ghandehari, A. Shoulaie, "Evaluating Voltage Notch Problems Arising from AC/DC Converter Operation", IEEE Trans. Power Electron., vol. 24, no. 9, pp. 2111-2119, Sep. 2009. https://doi.org/10.1109/TPEL.2009.2021058
  8. H. J. Lee, S. M. Park, "Analysis of Reactive Power Capability for Salient Synchronous Generators, and its Application to Primary Restorative Systems", KIEE, Vol.56, No.1, pp.14-17, 2007.
  9. N. Mohan, T. M. Undeland, W. P. Robbins, "Power Electronics", John Wiley & Sons, Inc., pp.138-153, 2003.
  10. Su-Mi Lee, Yeong-Han Chun, "Assessment of Optimal Constitution Rate of Windturbine and Photovoltaic Sources for STable Operation of Microgrid", KIEE, Vol.59, No.2, pp.272-276, 2010.