RTDS-based Model Component Development of a Tri-axial HTS Power Cable and Transient Characteristic Analysis

  • Ha, Sun-Kyoung (Dept. of Electrical Engineering, Changwon National University) ;
  • Kim, Sung-Kyu (Dept. of Electrical Engineering, Changwon National University) ;
  • Kim, Jin-Geun (Dept. of Electrical Engineering, Changwon National University) ;
  • Park, Minwon (Dept. of Electrical Engineering, Changwon National University) ;
  • Yu, In-Keun (Dept. of Electrical Engineering, Changwon National University) ;
  • Lee, Sangjin (Division of Energy & Electrical Engineering, Uiduk University) ;
  • Kim, Jae-Ho (Dept. of Fire and disaster prevention, Daejeon University) ;
  • Sim, Kideok (Korea Electrotechnology Research Institute)
  • 투고 : 2013.08.29
  • 심사 : 2015.05.12
  • 발행 : 2015.09.01

초록

The transient characteristics of the tri-axial High Temperature Superconducting (HTS) power cable are different from those of a conventional power cable depending on whether the cable is under a steady or transient state due to the quench. Verification using simulation tools is required to confirm both the characteristics of the cable and the effect of the cable when it is applied to a real utility. However, a component for the cable has not been provided in simulation tools; thus the RTDS-based model component of the tri-axial HTS power cable was developed, and a simulation was performed under the transient state. The considered properties of model component include resistance, reactance and temperature. Simulation results indicate the variation of HTS power cable condition. The results are used for the transient characteristic analysis and stability verification of the tri-axial HTS power cable. In the future, the RTDS-based model component of the cable will be used to implement the hardware-in-the-loop simulation with a protection device.

키워드

1. Introduction

High Temperature Superconducting (HTS) power cables are compact and have high current density. So these cables are expected to effectively solve the problems caused by increases in electricity demand and limited space. A tri-axial HTS power cable with a mutually layered structure of three phases has advantages, including a reduced amount of HTS wires and a small cryogenic surface area compared with other HTS power cables. One tri-axial HTS power cable can take the place of 18 large conventional copper cables operating at the same voltage level [1, 2]. Before using the tri-axial HTS power cable in a commercial installation, the system should be analyzed using simulation tools in order to confirm both the characteristics and the effects of the cable. The transient characteristics of the tri-axial HTS power cable are different from those of other HTS power cables as well as conventional copper power cables depending on the structure and whether the cable is under a steady or transient state due to the quench [3].

In this paper, for the simulation analysis, a tri-axial HTS power cable model component was developed for a Real-Time Digital Simulator (RTDS). The considered properties of the model component include the resistance, reactance, and temperature variations of the HTS wires and Liquid Nitrogen (LN2). The cable resistance was obtained based on a characteristic equation of superconductor [4], and it was also changed by the operating current, critical current, and temperature of the cable. The reactance was determined based on its structure and properties, such as permittivity. The temperature variations were calculated considering the heat value and heat transfer. The model component was applied to a model power system, and a simulation was performed under a transient state using the RTDS. The simulation results showed the effect of the tri-axial HTS power cable on the power system, such as the fault current of the three phases, and the characteristic variations in the tri-axial HTS power cable, such as quench resistance and the surface temperature of the HTS wires under fault conditions. The simulation results are presented and discussed in detail. The approach presented in the RTDS-based model component of the cable will be used to implement the hardware-in-the-loop simulation with a protection device. Also, this work can be used for other types of HTS power cables to investigate their transient characteristics.

 

2. RTDS-based Model Component Development

2.1 Tri-axial HTS power cable

The tri-axial HTS power cable, which has a multi-layer structure, contains a core, three-conducting layers, and a shield layer in a cryostat. The conducting layers are twisted clockwise and counter-clockwise along the same axis. The conducting layers are insulated using cryogenic dielectric material, which comprises PolyPropylene Laminated Paper (PPLP). In order to obtain the superconducting state of the cable, it is refrigerated by LN2 , which is injected into the inner core pipe and refluxed through the outer cryostat [5]. Fig. 1 describes the structure of the tri-axial HTS power cable. This structure has the advantages of effectiveness and economic feasibility, but it also has disadvantages in terms of the insulation design and the imbalance of the three-phase currents. The detailed design processes are referred to in previous papers [6, 7]. Table 1 indicates the design parameters of the cable.

Fig. 1.Structure of the tri-axial HTS power cable

Table 1.Parameters of the tri-axial HTS power cable

Table 2 shows the parameter-dimensions of the tri-axial HTS power cable [8]. In Table 2, the flow rate, the LN2 temperature of the input terminal, and the pressure of the input terminal are obtained by considering the relation formulas of the pressure loss, flow rate, and the LN2 temperature variations along with the length [9].

Table 2.Parameter-dimensions of the tri-axial HTS power cable

The parameters given in Table 2 are required to calculate LN2 temperature and the LN2 temperature is used to calculate the HTS wire surface temperature of three phases and then the surface temperature is used for the cable resistance calculation. These parameters were applied to the developed model component in the RSCAD/RTDS.

2.2 Modeling process of the model component in RTDS

RTDS is a fully digital electromagnetic transient power system simulator that operates in real time. Furthermore, the RTDS provides fast, reliable, accurate, and cost-effective results for power systems with complex high-voltage alternating currents as well as high-voltage direct current networks [10]. It can also be used to implement hardware in a loop simulation because it operates in real time.

The principal output results of the model component for a tri-axial HTS power cable are the resistance and reactance. The reactance is simply obtained using an equation based on the cable shape [6]. However, the resistance should be calculated considering the operating temperature, current and critical current because it changes according to both the cable shape and cable state. In addition, these results provide the temperature variations of the HTS wire and LN2, and the required cooling capacity after the transient state.

Thus the inductance and capacitance were calculated using the following Eqs. [11]. Lself is the self-inductance (1), Mij is the mutual inductance (2) and Cij is the capacitance (3).

where ri is the radius of the inner layer, rj is the radius of the outer layer, μ0 is the permeability of the free space, lpi and lpj are the winding pitches of each layer, ai and aj are the 1(clockwise) and the −1(counter-clockwise) winding directional factors of the i-layer and the j-layer, respectively. D is the current return path, ε0 is the permittivity of the free space, and εr is the relative permittivity of the dielectric material which is PPLP. Its permittivity is 2.2 [6].

The resistance of the cable was calculated based on a characteristic equation of superconductor (4). The equation was obtained by experiment and it requires the critical current, operating current, and temperature [4]. Also this resistance was calculated considering the parallel connection with a base metal.

where R is the cable resistance, Ic is the critical current, K is the temperature, and I is the operating current.

The temperature was calculated using the heat value Eq. (5) and the heat transfer Eq. (6) [11]. The calculation of the LN2 temperature was divided into two parts, i.e., the injected LN2 and refluxed LN2 , and it was assumed to operate under the peak temperature value along with the length of each path and the radial axis transfer.

LN2 temperature of input terminal is 66 K as shown in Table 2, and LN2 peak temperature values along with the length of inner pipe and outer pipe are 75.3 K and 76.2 K, respectively. These were calculated based on a reference [9].

The authors assumed that all electrical power loss was converted into thermal energy because the cable didn’t have any mechanical loss. The generated heat value was calculated using the current and the resistance of the conductor as in (5).

where I is the conductor current, R is the conductor resistance, t is the time step.

The heat transfer rate of the cable layers was calculated using the heat conduction equation of a hollow cylinder as in (6) [12].

where L is the length of the cable, (T1 –T2) is the temperature difference between the cable layers, r1 is the radius of the inner layer, r2 is the radius of the outer layer and k is the thermal conductivity of the materials. The thermal conductivity of PPLP is 0.2 W/mK. The heat transfer rate of in-between phases (a, b, and c) and shield layers of the cable shown in Fig. 1 were calculated in every time step using the parameters given in Table 3.

Table 3.The parameters for the surface temperature calculations

Fig. 2 illustrates overall procedure of the calculation algorithm for the surface temperature of the cable layers in detail. As shown in Fig. 2, the heat value Qgen and the transfer value Qcondt are accumulated every time step (△H= Qgen + Qcondt) in order to evaluate the temperature variation value △T as in (7).

Fig. 2.Calculation algorithm of the surface temperature

where m is the mass, C is the specific heat. Finally the surface temperature of the cable layer Ts will be integrated for the required time duration as in (8).

where n is the iteration number.

Shield layer resistance was calculated using the specific resistance Eq. (9) and it was also changed by the temperature.

where Ccu is the specific resistance, T is the temperature.

 

3. Application of the Model Component

3.1 Configuration of a 22.9 kV/ 50 MVA class power system

The developed model component was applied to a 22.9 kV class power system model, which consisted of a 5 km distribution line made of ACSR (aluminum conductor steel reinforced) 160 and a 50 MVA load [3]. The impedance of the distribution line was 0.506 + j0.0025 Ω. The fault logic was in front of the load. This power system’s circuit diagram is shown in Fig. 3. The developed component took the operating current and gave the variable inductance, capacitance, and resistance in the power system circuit.

Fig. 3.Configuration of a 22.9 kV/50 MVA class power system in the RTDS

3.2. Transient state characteristic analysis

The simulation was performed under a transient state to analyze both the characteristics of the cable and the effect of the cable when it is applied to a real utility. The simulation was implemented on a three-phase fault. The rated current was 1.26 kArms, and the DC critical currents of each layer were 2.75 kA, 3.1 kA, and 3 kA at 77 K, respectively. The fault resistance was 1.59 Ω. The three-phase fault was initiated at 0.2 s and lasted for 0.066 s.

Fig. 4 and Fig. 5 indicate the simulation results of the three-phase fault according to the electrical and thermal characteristics of the cable. Fig. 4(a) and (b) show the current and cable resistance, indicating the root mean square value. Fig. 5(a) and (b) show the temperatures of the surface of each phase and the LN2 . In these results, variations in the surface temperature and resistance are important.

Fig. 4.Simulation results of the three-phase fault; (a) Fault current; (b) Resistance of the HTS power cable under transient condition

Fig. 5.Thermal characteristics of the tri-axial HTS power cable under the three-phase fault; (a) Surface temperatures of each phase; (b) Peak temperature of LN2

As soon as a fault was initiated, the fault current reached 9.2 kArms, and as a result, the resistance increases due to the quench and the peak temperature of the LN2 slight increased by 0.17 K. Although the DC critical current of phase B was higher than that of other phases as given in Table 1, the quench resistance of phase B was not small, as depicted Fig. 4 (b). This phenomenon was caused by the decrease of critical current of phase B. The decrease was caused by the degradation of the cooling system by the structural characteristic of the cable. If the surface temperatures increase higher than the boiling point of LN2, bubbles would have influence on the electrical insulation properties. This process is prevented by the cooling system control and the additional stabilizer that can bypass the fault current.

Fig. 6 shows the shield layer current. The shield layer also has resistance and reactance. The resistance is 0.441 Ω at 77 K and the cooling characteristic is the same as phase A layer because the layer is in direct contact with the refrigerant. Unbalanced currents flow through the shield layer, and the unbalance current is caused by not only inherent imbalance and the different critical currents of each phase but also the unbalance faults. In this case, although the unbalance current occurred, the current and resistance were small, so the shield layer did not affect the other phase.

Fig. 6.Shield layer current of the HTS power cable under transient condition

 

4. Conclusion

This paper illustrated the structure and transient characteristics of a tri-axial HTS power cable. The RTDS-based model component of the cable was developed to investigate the transient characteristics of the cable, and it was applied to a power system model. The transient simulation was performed on a three-phase fault. The simulation results of the three-phase fault with the tri-axial HTS power cable represent the fault current, cable resistance, surface temperature of each phase, and peak temperature of LN2. These results indicated that the tri-axial HTS power cable could suffer catastrophic loss of superconductivity (quench) during a major transient event.

As a result, by developing the model component, a real-time simulation of the power system with the tri-axial HTS power cable was possible. The RTDS-based model component of the cable will be used to implement the hardware-in-the-loop simulation with a protection device. This work will also effectively be used to develop model components of other types of HTS power cables and to analyze their transient characteristics in connection with real power systems.

참고문헌

  1. D. Lindsay, M. Roden, R. Denmon, D. Willen, B. Mehraban, and A. Keri, “Installation and commissioning of triax hts cable,” JICABLE, A3-2, 2007.
  2. Website: http://www.supercables.com/
  3. J. H. Bang, H. H. Je, J. H. Kim, K. Sim, J. Cho, J. Y. Yoon, M. Park, and I. K. Yu, “Critical Current, Critical Temperature and Magnetic Field Based EMTDC Model Component for HTS Power Cable,” IEEE Trans. Appl. Supercond., Vol. 17, pp. 1726-1729, 2007. https://doi.org/10.1109/TASC.2007.898034
  4. J. H. Bang, M. Park, and I. K. Yu, "HTS power cable component for PSCAD/EMTDC," Patent Publication, 10-2007-1016246, 2007.
  5. S. K. Ha, S. K. Kim, J. G. Kim, M. Park, I. K. Yu, S. Lee, K. Sim, and A. R. Kim, "Transient Characteristic Analysis of a Tri-axial HTS Power Cableusing PSCAD/EMTDC." IEEE Trans. Appl. Supercond., to be published.
  6. S. K. Ha, S. K. Kim, J. G. Kim, M. Park, I. K. Yu, S. Lee, and K. Sim, "Development of an impedance matching program for balancing the distribution in a tri-axial HTS power cable," The International Conferenceon Superconductivity and Magnetism, to be published.
  7. S. K. Kim, S. K. Ha, J. G. Kim, S. Kim, M. Park, I. K. Yu, S. Lee, K. Sim, "Design and AC loss analysis of a 22.9 kV/50 MVA class tri-axial HTS power cable ," The International Conference on Superconductivity and Magnetism, to be published.
  8. H. S. Yang, D. L. Kim, S. H. Sohn, J. H. Lim, Y. S. Choi, and S. D. Hwang, “Hybrid Cooling System Installation for the KEPCO HTS Power Cable,” IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1292-1295, 2010. https://doi.org/10.1109/TASC.2010.2044036
  9. C. H. Lee, D. H. Kim, C. D. Kim, K. S. Kim, and I. S. Kim, “An optimal cooling method for long HTS power transmission cable,” The Korea Institute of Applied Superconductivity and Cryogenics, vol. 6, no. 3, pp. 56-61, 2004.
  10. G. H. Kim, M. Park, and I. K. Yu, “RTDS-based real time simulations of grid-connected wind turbine generator systems,” in APEC2010, Feb. 2010, pp. 2085-2090.
  11. J. H. Lee, G. Cha, “AC loss calculation of a multi-layer HTS transmission cable considering the twist of each layer,” IEEE Trans. Appl. Supercond. 1, 2433-2436, 2001.
  12. Incropera, Dewitt, Bergman, Lavine White, Introduction to heat transfer, fifth ed., John wiley & Sons, New York, 2007.