DOI QR코드

DOI QR Code

Design and Feedback Performance Analysis of the Inverter-side LC Filters Used in the DVR System

DVR시스템에 사용되는 인버터부의 LC필터 설계와 피드백 성능분석

  • Received : 2015.05.07
  • Accepted : 2015.05.22
  • Published : 2015.06.01

Abstract

Voltage sags are considered the dominant disturbances affecting power quality. Dynamic voltage restorers(DVRs) are mainly used to protect sensitive loads from the electrical network voltage disturbances such as sags or swells and could be used to reduce harmonic distortion of ac voltages. The typical DVR topology essentially contains a PWM inverter with LC Filter, an injection transformer connected between the ac voltage line and the sensitive load, and a DC energy storage device. For injecting series voltage, the PWM inverter is used and the passive filter consist of inductor(L) and capacitor(C) for harmonics elimination of the inverter. However there are voltage pulsation responses by the characteristic of the LC passive filter that eliminate the harmonics of the PWM output waveform of the inverter. Therefore, this paper presented design and feedback performance of LC filter used in the DVRs. The voltage control by LC filter should be connected in the line side since this feedback method allows a relatively faster dynamic response, enabling the elimination of voltage notches or spikes in the beginning and in the end of sags and strong load voltage THD reduction. Illustrative examples are also included.

Keywords

References

  1. R. S. Weissbach, G. G. Karady, and R. G. Farmer, "Dynamic voltage compensation on distribution feeders using flywheel energy storage," IEEE Trans. Power Delivery, vol. 14, pp. 465-471, Apr. 1999. https://doi.org/10.1109/61.754090
  2. Fitzer, C., Arulampalam, A., Barnes, M., Zurowski, R., "Mitigation of saturation in dynamic voltage restorer connection transformers," Power Electronics, IEEE Trans. Vol. 17, No.6, pp. 1058-1066, Nov. 2002 https://doi.org/10.1109/TPEL.2002.805584
  3. A. Kara, P. Dahler, D. Amhof, H. Gruning, "Power supply quality improvement with a dynamic voltage restorer (DVR)," IEEE Applied Power Electronics Conference and Exposition, pp.986-993,1998.
  4. N.H. Woodley, A. Sundaram, T. Holden, T.C. Einarson, "Field experience with the new platformmounted DVR/sup TM/, "IEEE International Conference on PowerCon 2000, pp. 1323-1328, 2000.
  5. M.H. Haque, " Voltage sag correction by dynamic voltage restorer with minimum power injection," IEEE Power Engineering Review, Volume: 21 Issue: 5, pp.56-58, May 2001. https://doi.org/10.1109/MPER.2001.4311368
  6. Jin-Geun Shon, "Series Voltage Compensation Systems for Voltage Sag by Using an Environmentally Friendly Ultra-capacitor", The Transactions of KIEE, Vol. 58-4, pp.763-769, 2009.
  7. Jin-Geun Shon, "Development of On-Line Type Voltage Sag Compensation Systems by Using a Supercapacitor", The Transactions of KIEE, Vol. 58-2, pp.101-107, 2009.