DOI QR코드

DOI QR Code

불평형부하 시 독립형 인버터의 데드타임 보상기법

Dead Time Compensation of Stand-alone Inverter Under Unbalanced Load

  • Jeong, Jinyong (Dept. of Electrical Engineering, Chungnam National Univ.) ;
  • Jo, Jongmin (Dept. of Electrical Engineering, Chungnam National Univ.) ;
  • Lee, Junwon (Dept. of Electrical Engineering, Chungnam National Univ.) ;
  • Chae, Woo-Kyu (Korea Electric Power Research Institute, KEPCO) ;
  • Cha, Hanju (Dept. of Electrical Engineering, Chungnam National University)
  • 투고 : 2014.08.28
  • 심사 : 2014.11.22
  • 발행 : 2015.04.20

초록

Stand-alone inverter supplies constant voltage to loads. However, when a three-phase stand-alone inverter supplies unbalanced load, the generated output voltages also become unbalanced. The nonlinear characteristics of inverter dead time cause a more serious distortion in the output voltage. With unbalanced load, voltage distortion caused by dead time differs from voltage distortion under balanced load. Phase voltages in the stationary reference frame include unbalanced odd harmonics and then, d-q axis voltages in the synchronous reference frame have even harmonics with different magnitude, which are mitigated by the proposed multiple resonant controller. This study analyzes the voltage distortion caused by unbalanced load and dead time, and proposes a novel dead time compensation method. The proposed control method is tested on a 10-kW stand-alone inverter system, and shows that total harmonic distortion (THD) is reduced to 1.5% from 4.3%.

키워드

참고문헌

  1. T. H. Han, J. H. Lee, H. J. Kim, and B. M. Han, "Optimized design and coordinated control for stand-alone DC micro-grid," Transactions of Korean Institute of Power Electronics, Vol. 18, No. 1, pp. 63-71, Feb. 2013. https://doi.org/10.6113/TKPE.2013.18.1.63
  2. J. M. Choe, S. G. Ra, D. H. Han, Y. J. Lee, and G. H. Choe, "Design and test of ESS DC-DC converter using zinc-bromine redox flow battery for stand-alone microgrid," Transactions of Korean Institute of Power Electronics, Vol. 19, No. 2, pp. 106-115, Apr. 2014. https://doi.org/10.6113/TKPE.2014.19.2.106
  3. P. Li, B. Dan, K. Yong, and C. Jian, "Research on three-phase inverter with unbalanced load," Paper presented at APEC2004 Conference on February 22-26, 2004. Anaheim, California, Conf., pp. 128-133, Feb. 2004.
  4. K. H. Kim, N. J. Park, and D. S. Hyun, "Advanced synchronous reference frame controller for three-phase UPS powering unbalanced and nonlinear loads," Power Electronics Specialists Conference, PESC '05. IEEE 36th, pp. 1699-1704, 2005.
  5. J. W. Choi and S. K. Sul, "Inverter output voltage synthesis using novel dead time compensation," IEEE Transactions on Power Electronics, Vol. 11, No. 2, pp. 221-227, Mar. 1996. https://doi.org/10.1109/63.486169
  6. N. Mohan, T. M. Undeland, and W. P. Robbins, "Power electronics," Wiley, 2003.
  7. T. K. Vu, S. H. Lee, and H. J. Cha, "A new on-line dead-time compensator for single-phase PV inverter," Transactions of Korean Institute of Power Electronics, Vol. 17, No. 5, pp. 569-576, Oct. 2012.
  8. P. C. Loh and D. G. Holmes, "Analysis of multiloop control strategies for LC/CL/LCL-filtered voltage -source and current-source inverters," IEEE Transactions on Industry Applications, Vol. 41, No. 2, pp. 644-654, Mar./Apr. 2005. https://doi.org/10.1109/TIA.2005.844860
  9. S. H. Han, J. H. Park, H. G. Kim, H. N. Cha, T. W. Chun, and E. C. Nho, "Dead time compensation of grid-connected inverter using resonant controller," Transactions of Korean Institute of Power Electronics, Vol. 16, No. 6, pp. 409-415, Dec. 2012.