DOI QR코드

DOI QR Code

A New Dynamic VRF Heat Hump Simulation Including Frosting and Defrosting Models

착상 및 제상을 포함한 VRF 히트펌프의 동적 수치해석 모델

  • 박노마 (LG 전자 CTO HAE 연구센터 AE 연구소) ;
  • 신정섭 (LG 전자 CTO HAE 연구센터 AE 연구소) ;
  • 정백영 (LG 전자 CTO HAE 연구센터 AE 연구소) ;
  • 김병순 (LG 전자 CTO HAE 연구센터 AE 연구소)
  • Received : 2014.11.19
  • Accepted : 2014.12.02
  • Published : 2015.03.01

Abstract

In this study, a new dynamic VRF-type heat pump simulation model is proposed which incorporates frosting and defrosting models. Toward this end, a simple frosting model based on the perfect analogy, and lumped system based defrost model, are proposed. Then, frosting and defrosting models are incorporated into a dynamic heat pump model which adopts segment-by-segment local heat exchanger model and map-based variable speed compressor model. Thus, the model can naturally represent locally uneven frosting and defrosting on the heat exchanger surface. Developed simulation model is validated against available experimental data to show good agreement within 10% error for capacity and COP. Finally, developed dynamic heat pump model is applied to annual heating season simulation to show that seasonal COP of heat pump is degraded by 7% due to frosting and defrosting.

실외 열교환기의 착상 및 제상조건 하에서 VRF 멀티형 히트펌프의 동적 거동의 해석을 위한 시뮬레이션 기법이 제안되었다. 이를 위해 열전달-물질전달 완벽 상사 가정에 기반한 간단한 착상모델과 제상 모델이 제안되었다. 제안된 착제상 모델은 용량가변 압축기 모델과, 미소면적에 대한 열 및 모멘텀 평형에 근거한 열교환기 모델을 채택한 동적 사이클 해석모델에 적용되었다. 따라서, 제안된 모델은 공간에 대해 비균질 착상을 자연스럽게 예측할 수 있다. 개발된 동적 사이클 해석 모델은 실험결과와 비교하여 능력 및 효율을 10% 이내에서 잘 예측함을 확인하였다. 최종적으로, 개발된 모델은 표준적인 건물의 난방시즌 운전 해석에 적용되었으며, 착상 및 제상으로 인하여 동절기의 계절 성능계수를 7% 가량 하락 시킴을 보일 수 있었다.

Keywords

References

  1. Chang, Y.J. and Wang, A., 1997, "Generalized Heat Transfer Correlation for Louver Fin Geometry," Int. J Heat Mass Trans., Vol. 40, pp. 533-544. https://doi.org/10.1016/0017-9310(96)00116-0
  2. McAdams W.H., 1942, Heat Transmission, 2nd Ed., McGraw-Hill, New York.
  3. Gungor, K.E. and Winterton, R.H.S., 1987, "Simplified General Correlation for Saturated Flow Boiling and Comparisons with Data," Chem. Eng. Res. Des. Vol. 65, pp. 148-156.
  4. Park, N., Shin, J., Chung, B., 2013, A New Dynamic Heat Pump Simulation Model with Variable Speed Compressors Under Frosting Conditions, Proc. 2013 Int. Conf. Compressors and Their Systems, City College of London, UK.
  5. Kandula, M., 2011, "Frost Growth and Densification in Laminar Flow over Flat Surfaces," Int. J. Heat Mass Trans., Vol. 54, pp 3719-3731. https://doi.org/10.1016/j.ijheatmasstransfer.2011.02.056
  6. Na, B. and Webb, R.L., 2004, "New Model for Frost Growth Rate," Int. J. Heat Mass Trans., Vol. 47, pp. 925-936. https://doi.org/10.1016/j.ijheatmasstransfer.2003.09.001
  7. Lee, K.S., Jhee S, and Yang DK, 2003, "Prediction of the Frost Formation on a Cold Flat Surface," Int. J. Heat Mass Trans., Vol. 46, pp 3789-3796. https://doi.org/10.1016/S0017-9310(03)00195-9
  8. Lee, K.S., Kim, W.S. and Lee, T.H., 1997, "A One-Dimensional Model for Frost Formation on a Cold Flat Plate," Int. J. Heat Mass Trans., Vol. 40, pp. 4539-4365.
  9. Da Silva, L., Hermes, C.J.L. and Melo, C., 2011, "First-Principles Modeling of Frost Accumulation on Fan-Supplied Tube-Fin Evaporators," Appl. Thermal Eng., Vol. 31 pp. 2616-2621. https://doi.org/10.1016/j.applthermaleng.2011.04.029
  10. Xia, Y. and Jacobi, A.M., 2004, "An Exact Solution to Steady Heat Conduction in a Two-Dimensional Slab on a one-Dimensional Fin: Application to Frosted Heat Exchangers," Int. J. Heat Mass Trans., Vol. 47, pp. 3317-3326. https://doi.org/10.1016/j.ijheatmasstransfer.2004.01.019
  11. Liu, Z., Tang, G., and Zhao, F., 2003, "Dynamic Simulation of Air-Source Heat Pump During Hot-Gas Defrost," Applied Thermal Engineering, Vol. 23, pp. 675-685. https://doi.org/10.1016/S1359-4311(03)00002-4
  12. Homod, R.Z., Sahari, K.S.M., Almurib, H.A.F., and Nagi,, F.H., 2011, "Double Cooling Coil Model for Non-Linear HVAC System Using RLF Method," Energy and Buildings, Vol. 43, pp. 2043-2054. https://doi.org/10.1016/j.enbuild.2011.03.023