DOI QR코드

DOI QR Code

Survey on the Ratio of Kitchen to Total Space and Ventilation System Capacity of Kitchens through Case Studies in Korean Foods Restaurants

사례 조사를 통한 한식 음식점의 주방면적 비율과 환기시설의 적정성 조사

  • Chang, Hyeja (Major in Foodservice Management of Department of Food Science and Nutrition. Graduate School, Dankook University) ;
  • Choi, Gyunggi (Major in Foodservice Management of Department of Food Science and Nutrition. Graduate School, Dankook University) ;
  • Wang, Taehwan (Department of Food and Nutrition, College of Human Ecology, Yonsei University) ;
  • Kwak, Tongkyung (Department of Food and Nutrition, College of Human Ecology, Yonsei University)
  • 장혜자 (단국대학교 일반대학원 식품영양학과 급식외식경영학 전공) ;
  • 최경기 (단국대학교 일반대학원 식품영양학과 급식외식경영학 전공) ;
  • 왕태환 (연세대학교 생활과학대학 식품영양학과) ;
  • 곽동경 (연세대학교 생활과학대학 식품영양학과)
  • Received : 2014.08.28
  • Accepted : 2015.01.07
  • Published : 2015.02.28

Abstract

For the globalization of Korean food restaurants, the kitchens should be equipped with proper ventilation systems and space to keep clean and ensure food safety. This study aimed to examine the ratio of kitchen to total space of restaurant and the suitability of the ventilation systems employed at Korean food restaurants. Data were collected by on-site survey of 12 Korean foods restaurants in Seoul. Length and width of the restaurants were measured with scale. Temperatures and air velocity around the heating equipment, working area, and hood were measured with a thermal imaging camera anemometer and thermometer. Statistical analyses were conducted with the SPSS program. The average space of the restaurants was $25.7m^2$. The ratio of kitchen to space was 0.22 for restaurants sized $32m^2$, 0.28 for $33-66m^2$, 0.21 for $66.1-99m^2$, 0.16 for $99.1-148.5m^2$, and 0.35 for those above $148.5m^2$. Average maximum and minimum air velocity around the hood were 0.28 m/sec and 0.22 m/sec, respectively. Under these conditions, the temperature of the working area was $41^{\circ}C$, presenting an uncomfortable indoor temperature for kitchen employees to work. When classifying 3 groups based on the minimum and maximum air velocity, the temperatures near the cooking area and in the hood of the restaurants showed significant differences among the three groups. When the maximum air velocity was over 0.3 m/sec, the temperature of the cooking area was as $30.1^{\circ}C$, showing a significantly lower temperature (p<0.01). Based on these results, the kitchen space rate of 0.25 to the total space and a ventilation system maintaining a maximum air velocity over 0.3 m/sec were recommended for ensuring the food safety of Korean foods restaurants sized 66 to $99m^2$.

Keywords

References

  1. Chang HJ, Jang SH. 2011. A facility design model for 1300 capacity school foodservice with adjacency and bubble diagrams. Korean J Community Nutr 16(1):98-112 https://doi.org/10.5720/kjcn.2011.16.1.98
  2. Chang HJ, Kim JW, Ju SY, Go ES. 2012. How do the work environment and work safety differ between the dry and wet kitchen foodservice facilities? Nutr Res Pract 6(3): 366-374 https://doi.org/10.4162/nrp.2012.6.4.366
  3. Chang HJ, Kwak TK, Demicco FJ, Knabel SJ. 2005. A case study for developing a model for a HACCP-compliant kitchen in the foodservice industry. J Asian Reg Assoc Home Econ 12(3):179-189
  4. Chang HJ, Son HJ, Choi GG. 2009. Current status of functional areas space and suggestion of their equipment requirements for school foodservices in Gyeonggi province. J Korean Food Cook Sci 25(4):474-487
  5. Domenech E, Amorķs J, Perez-Gonzalvo M, Escriche I. 2011. Implementation and effectiveness of the HACCP and prerequisites in food establishments. Food Control 22(8): 1419-1423 https://doi.org/10.1016/j.foodcont.2011.03.001
  6. Food Sanitation Act. 2014. Enforcement decree of the food sanitation act article 21.
  7. Gregoire MB. 2010. Foodservice Organization: A managerial and systems approach. 7th ed. Pearson Education Inc, Upper Saddle River, NJ, USA pp 85-89
  8. Kim JS, Kwak NS, Jung JW, Yoon SM, Lee SH, Park JE, Jung JW. 2012. Study on the food hygiene management in Korean restaurant in response to climate change. Korea Institute for Health and Social Affairs. Seoul, Korea pp 15-59
  9. Kim TH, Chang HJ, Yoon JH. 2004. Design and layout of food service facilities. Sigmapress, Seoul, Korea pp 281-302
  10. Kim TH, Kim BS, Kim HG, Ahn HG, Choi YS. 2010. The principle of kitchen management. Kyomunsa. Gyeonggido, Korea pp 181-185
  11. Ko HS, Kim SK, Kim DK, Kim BJ. 2005. Importance perception on the sanitation and cleanliness of family restaurant employees. J Korean Food Cook Sci 21(2):155-162
  12. Kwak TK. 2013. Establishment of a sanitation management system for HACCP certification in restaurant kitchen settings. Ministry of Agriculture, Food and Rural Affairs. pp 6-9
  13. Kwak TK, Ryu ES, Lee HS, Ryu K, Choi SK, Hong WS, Jang MR, Shin ES, Moon HK, Chang HJ, Park SJ, Choe EH, Lee KE. 2008. Institutional foodservice operations. Shinkwang, Seoul, Korea pp 287-304
  14. Kwon OS, Ahn YS, Hwang EJ, Lee MJ, Moon SE, Chung JH. 2004. The epidemiological study of skin aging in a high temperature environment. Korean J Dermatol 42(8):997-1004
  15. Lee JC. 2005. Sanitary of the food service industry. Int J Tourism Hosp Res 19(2):343-355
  16. Lee SJ, Lee KG. 2012. Development of a computer-assisted quantitative microbial risk assessment (QMRA)-hazard analysis and critical control point (HACCP) program for food safety in restaurant. Food Engineering Progress 16(2):113-121
  17. Lim TH, Choi JH, Kang YJ, Kwak TK. 2013. The implementation of a HACCP system through u-HACCP $^{(R)}$ application and the verification of microbial quality improvement in a small size restaurant. J Korean Food Sci Nutr 42(3):464-477 https://doi.org/10.3746/jkfn.2013.42.3.464
  18. Matias JCO, Fonseca JMJ, Barata IG, Brojo FMRP. 2013. HACCP and OHS: Can each one help improve the other in the catering sector? Food Control 30(1):240-250 https://doi.org/10.1016/j.foodcont.2012.06.030
  19. Ministry of Education. 2014. The sanitation manual for school foodservice. Available from: http://www.sen.go.kr/web/services /bbs/bbsView.action?bbsBean.bbsCd=94&bbsBean.bbsSeq=3 149. Accessed March 20, 2013
  20. Ministry of Food and Drug Safety. 2009. Development of food safety manual and education contents for foodborne illness prevention in foodservcie operation. Ministry of Food and Drug Safety. pp 37-38
  21. Ministry of Food and Drug Safety. 2012. Food Poisoning Statistics System. Available from: http://www.kfda.go.kr/estat/ index.do?n MenuCode=28&type=4_2&yr=2011&opt=2& chart=Column2D&mode=data. Accessed April 20, 2012
  22. Park JC. 2003. A study on the improvement strategies for exhaust performance in commercial kitchen hoods. Korean J Air- Condit Refr Eng 15(5):439-445
  23. Park KJ, Lee KJ, Hardi BE, Lee J, Shin D. 2011. Smoke control according to the ventilation capacity in subway tunnel fire: I. FDS simulation. J Korean Inst Gas 15(3):31-38
  24. Park SH, Moon HK. 2012. Compliance with GMP and SSOP in college foodservices by comparison of elementary and middle and high school food services. J Korean Diet Assoc 18(3):248-265 https://doi.org/10.14373/JKDA.2012.18.3.248
  25. Powell DA, Jacob CJ, Chapman BJ. 2011. Enhancing food safety culture to reduce rates of foodborne illness. Food Control 22(2011):817-822 https://doi.org/10.1016/j.foodcont.2010.12.009
  26. Seoul Metropolitan Government. 2009. Korean restaurants' kitchen layout and sanitation facility standards development. Available from: http://lib.seoul.go.kr/search/detail/CATCRZ 000000064743?mainLink= /searchS/eaz&briefLink=/searchS/ eaz/result?st=SUBJ_A_sNo=0_A_sq=59_A_mainLink=%2Fs earchS%2Feaz. Accessed May 22, 2012
  27. Won CS, Park HJ, Jeon YK. 2006. A study on the sanitation standard of the restaurant food and beverage on HACCP. J Tourism Inf 22(3):21-42

Cited by

  1. 경기도 소재 고등학교 급식소의 위생·안전관리와 작업구역별 공기 품질 간의 관련성 vol.23, pp.4, 2015, https://doi.org/10.14373/jkda.2017.23.4.350