컴팩트형 VAV 공조기의 성능평가와 경제성 분석에 관한 연구

A Study on Economic Analysis and Performance Appraisal of Compact Type Variable Air Volume

  • 김동철 (서울과학기술대학교 주택대학원) ;
  • 정광섭 (서울과학기술대학교 건축학부) ;
  • 김영일 (서울과학기술대학교 건축학부)
  • Kim, Dong-Cheol (Graduate School of Housing, Seoul National University of Science and Technology) ;
  • Chung, Kwang-Seop (School of Architecture, Seoul National University of Science and Technology) ;
  • Kim, Young Il (School of Architecture, Seoul National University of Science and Technology)
  • 투고 : 2014.07.07
  • 심사 : 2014.10.23
  • 발행 : 2015.01.10

초록

Ceiling cooling and heating system that consider load arrangement and space in the ceiling needs to be developed. Therefore, experimental and economic changes were done to verify the performance of compact type VAV. The test results were as follow. 1) Noise test result, measuring approximately 50.4 dB~56.6 dB (before ceiling in landfill), had a better ceiling deadline than the current measure, about a 10 dB noise reduction, so that the office baseline (40~50 dB) noise was judged to be less than test. 2) For the static pressure test result, taking out an outside hydrostatic 25 mmAq, 24.8 mmAq was measured, respectively, at the point. 3) For the life-cycle cost analysis result, the initial investment cost, maintenance replacement costs, and maintenance costs increased 0.2%, but the energy savings ratio was 19.5% while the whole life cycle savings of 40 years LCC was reduced 11.9%.

키워드

참고문헌

  1. Jung, J. R., 2002, Evaluation of alternatives for building service system in high-rise building based on life cycle cost analysis, Ph.D. thesis, The Graduate School, Yonsei University, Seoul, Korea.
  2. Lim, H. W., Chung, K. S., and Kim, Y. L., 2011, An economic analysis of ice thermal storage system and absorption Chiller-heater for large capacity Air-conditioning application, Proceedings of the SAREK 2011 Summer Annual Conference, pp. 615-620.
  3. Kim, S. W., 2005, Manan Youth Training Center LCC simulation, Sahm-Shin Energy Environment Research Institute, Sahm-Shin Engineers, Inc.
  4. Choi, H. G., 2004, A case study on the economic analysis for a new technology-based ventilation system using LCC technique, The Graduate School, Chungang University, Seoul, Korea.
  5. Lemaire, A. D., 1993, Room air and contaminant flow, evaluation of computational methods, TNO Building and Construction Research, IEA Energy Conservation in Buildings and Community Systems Programme, Annex 20 Air flow patterns within buildings, Subtask-1 Summary Report.
  6. Fluent, 1998, Fluent Version 5.4 Manuals, Computational Dynamics Ltd., London.
  7. ANSI/ASHRAE Standard 55-1992, 1992, Thermal environmental conditions for human occupancy, ASHRAE.
  8. Facilities Engineering Manual, Korea Society of Facilities Engineers, pp. 21-23.
  9. Hawkins, A. N., Hosni, H. H., and Jones, B. W., 1995, A comparison of room air motion in a full size test room using different diffusers and operating conditions, ASHRAE Transactions, Vol. 101, pp. 81-100.

피인용 문헌

  1. Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2015 vol.28, pp.6, 2016, https://doi.org/10.6110/KJACR.2016.28.6.256