Abstract

This paper presents The performance analysis of inverter control type-industrial cooler with respect to refrigeration load and outdoor temperature. Aside from materials about simulations and foundation data regarding inverter control compressors, currently, data about commercial coolers with inverter control still lack information for performance comparison. Thus, in this paper, the experiments are done to see characteristics of condensation capacity, evaporation capacity, compressor power and COP with respect to outdoor temperature and load by using a commercial inverter control cooler model. As a result, COP difference of the inverter control cooler with respect to load is 30% at the outdoor temperature of $35^{\circ}C$, 29% at the outdoor temperature of $30^{\circ}C$, 34% at $25^{\circ}C$, respectively.

Keywords

References

  1. J. H. Choi, S. M. Baek, B. J. Jin, W. J. Choi, C. G. Moon, H. S. Lee and J. I. Yoon, 2009, "Performance characteristics of cooler controled capacity using hot-gas bypass," ICHMT CONV-09 Tunisia, pp. 502-505.
  2. J. I. Yoon, S. T. Oh, S. M. Baek, J. H. Choi, J. Y. Byun, S. K. Jeong and C. G. Moon, 2009, "Temperature control of industrial water cooler using hot-gas bypass," WCSET Bali-2009, pp.377-381.
  3. H. W. Kim, S. M. Baek, C. G. Moon, E. Kim, and J. I. Yoon, 2010, "The characteristics on the capacity control of inverter type in an industrial water cooler," ICCHT2010-5th Indonesia, pp.016-1-016-6.
  4. D. S. Yang, G. b. Lee and M. S. Kim, Y. M. Cho, 2004, "A Study on the capacity modulation of a variable speed vapor compression system using superheat at the compressor discharge," Proceedings of the SAREK 2004 Winter Annual Conference, p. 99.
  5. Cohen, R, J. F. Hnmilton and J. T. Pearson, 1974, "Possible energy conservation through the use of variable-capacity compressor", Proc. Purdue Compressor Technology Cong., Pursue, USA. pp. 50-54.
  6. Hua, Li, J. I. Yoon, and S. K. Jeong, 2004, "Dynamic characteristics of refrigeration system for control evaporator superheat and compressor capacity", The Korean Society for Power System Engineering, KSPSE The 2004 Spring Conference, pp. 170-174.
  7. Lida. K, T. Yamamoto, T. Kuroda and H. Hibi, 1982, "Development of an energy saving oriented variable-capacity system heat pump", ASHRAE Trans. pp. 441-449.

Cited by

  1. A Comparison of Operating Characteristics for Industrial Water Cooler with Variation of Control Methods vol.18, pp.6, 2014, https://doi.org/10.9726/kspse.2014.18.6.099