DOI QR코드

DOI QR Code

A Study on the Heat Transfer Characteristics of Various Construction of SCW Type Ground Heat Exchanger

다양한 형상의 SCW형 지중 열교환기 열전달 특성에 관한 연구

  • Chang, Keun-Sun (Department of Mechanical Engineering, SunMoon University) ;
  • Kim, Min-Jun (Department of Mechanical Engineering, Graduate School of SunMoon University)
  • 장근선 (선문대학교 기계공학과) ;
  • 김민준 (선문대학교 대학원 기계공학과)
  • Received : 2014.06.03
  • Accepted : 2014.08.06
  • Published : 2014.10.10

Abstract

This paper uses in-situ thermal response tests to present the characteristics of the ground thermal conductivities of three different SCW GHX. These SCW GHXs were installed in the same site in Seojong City. The three different cases are distinguished by the flow direction and the presence of a filler. The first type (A) is constructed for water to flow downstream. The second (B) and third (C) types are designed for water to flow upstream, and a filler is additionally inserted into the third type. The results of the in-situ thermal response tests, indicate that the ground thermal conductivity for types (A), (B) and (C) are of $4.84W/m{\cdot}K$, $3.40W/m{\cdot}K$, and $11.62W/m{\cdot}K$, respectively.

Keywords

References

  1. Kim, M. J. and Choi, C. H., 2013, A study on the KS (Korea Standard) of SCW type ground heat exchanger, Journal of Geothermal Energy, Vol. 9, No. 4, pp. 39-46.
  2. Ministry of Knowledge Economy, 2012, Standards of support, installation, and management for new and renewable energy system, Ministry of Knowledge Economy Announcement 2012-3.
  3. Choi, H. S., Choi, H. J., Lee, C. H., and Yun, M. S., 2013, A assessment ground thermal conductivity for SCW type ground heat exchanger design, Journal of Geothermal Energy, Vol. 9, No. 3, pp. 67-73.
  4. Kim, M. J. and Chang, K. S., 2013, SCW type ground heat exchanger analysis using borehole photo shoot, Journal of Geothermal Energy, Vol. 9, No. 4, pp. 47-54.
  5. Park, D. H., Kwak, D. Y., Kim, K. K., Park, S. S., and Na, S. M., 2010, Numerical simulation of standing column well, Proceedings, World Geothermal Congress 2010, Bali, Indonesia.
  6. Lee, S. H., Park, C. H., Yoon, T. I., An, K. M., and Choi, Y. S., 2010, An experimental study on the bleed effect of standing column well(SCW) type heat exchanger, Proceedings of the SAREK 2010 Winter Annual Conference, pp. 446-452.
  7. Zheng Deng, 2004, Modeling of standing column wells in ground source heat pump systems, Ph.D thesis, Oklahoma State University, OK, U.S.A.

Cited by

  1. Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015.27.7.380