DOI QR코드

DOI QR Code

A Synthetic Test Circuit for HVDC Thyristor Valve Test with Simplified Turn-Off Circuit of Auxiliary Thyristor

보조 사이리스터의 턴-오프 회로를 간소화한 HVDC 사이리스터 밸브 시험용 합성시험회로

  • Received : 2014.08.17
  • Accepted : 2014.08.28
  • Published : 2014.10.20

Abstract

This study proposes a new synthetic test circuit (STC) for HVDC thyristor valve tests. The conventional STC with a 2-phase chopper requires a 3-phase transformer, a 3-phase diode rectifier, and an IGBT to facilitate the off state of an auxiliary thyristor. In the proposed STC, these three components are replaced with one diode and one resistor, which result in the simplified implementation of the hardware of the STC. Simulation and experimental results demonstrate the validity of the proposed scheme.

Keywords

References

  1. Power electronic for electrical transmission and distribution systems - Testing of thyristor valves for static VAR compensators. (IEC 61954, 1999)
  2. Test circuits for HVDC thyristor valves. (Cigre Task Force 03 of Working Group 14.01, Technical Brochure 113, Apr. 1997)
  3. J. L. Wne, G. F. Tang, Y. F. Qiu, J. L. Zhu, K. P. 콤, G. ZH. Xu, "Research and Development of Synthetic Test Equipement for High Voltage Thyristor Valves," International Conference on Power System Technology, pp. 1-8, Oct. 2006.
  4. B. L. Sheng, E. Jansson, A. Blomberg, H. O. Bjarme, and D. Windmar, "A new synthetic test circuit for the operational tests of HVDC thyristor modules," APEC(Applied Power Electronics Conference and Exposition, 2001), Vol. 2, pp. 1242-1246, Sep. 2001.
  5. T. Bauer, H. P. Lips, G. Thiele, T. Tylutki, and M. Uder, "Operational tests on HVDC thyristor modules in a synthetic test circuit for the sylmar east restoration project," IEEE Transactions on Power Delivery, Vol. 12, No. 3, pp. 1151-1158, Jul. 1997.
  6. M. L. Woodhouse and T. Simanwe, "A new facility for testing HVDC and SVC thyristor valves," B4-309, CIGRE 2006.
  7. K. T. Kim, B. M. Han, J. H. Jung, E. C. Nho, Y. H. Chung, and S. T. Baek, "A new synthetic test circuit for testing thyristor valve in HVDC converter," Transactions of the Korean Institute of Power Electronics, Vol. 17, No. 3, pp. 191-197 Jun. 2012. https://doi.org/10.6113/TKPE.2012.17.3.191
  8. E. C. Nho, B. M. Han, Y. H. Chung, S. T. Baek, and J. H. Jung, "Synthetic test circuit for thyristor valve in HVDC converter with new high-current source," IEEE Transactions on Power Electronics, Vol. 29, No. 7, pp. 3290-3296, Jul. 2014. https://doi.org/10.1109/TPEL.2013.2279716

Cited by

  1. Improved Current Source using Full-Bridge Converter Type for Thyristor Valve Test of HVDC System vol.20, pp.4, 2015, https://doi.org/10.6113/TKPE.2015.20.4.363