Thermal Characteristics of Electric Wiring for Halogen Warm Lamp Group and Automatic Waterer Group at Stable

우사(牛舍)에서의 할로겐보온등군(群) 및 자동급수통군에 대한 전기배선의 열적 특성

  • Kim, Doo-Hyun (Department of Safety Engineering, Chungbuk National University) ;
  • Yoo, Sang-Ok (Department of Safety Engineering, Chungbuk National University) ;
  • Kim, Sung-Chul (Department of Safety Engineering, Chungbuk National University)
  • Received : 2014.04.21
  • Accepted : 2014.07.02
  • Published : 2014.08.31

Abstract

This study is analyzed for electrical fire danger by electric equipments through surveys of stable owners and the field investigation at 64 stable. Also, an experiment is performed to analyze the thermal characteristics of 4 types electric wiring according to the number of operating halogen warm lamp group and automatic waterer group in Beon-young stable in the Cheongwon location. The survey is done to investigate the occurrence of electrical fire, electric equipment, causes and dangerous equipment. As a result, halogen warm lamp group and automatic waterer group are found to have dangerous loads. In the field investigation, the mode of load capacity of the halogen warm lamp group and automatic waterer group was investigated. The mode of load capacity of halogen warm lamp group (over 3 years) is found 17A and that of the auto waterer group (10 years) is 16A. In this experiment, the halogen warm lamp group aged at least 3 years showed $109^{\circ}C$ while that aged less than 1 year appeared $83^{\circ}C$, showing the max gap of $26^{\circ}C$. The automatic waterer group aged 10 years showed $90^{\circ}C$ while that aged less than 1 year appeared $68^{\circ}C$, showing the max gap of $22^{\circ}C$. These findings indicate that the mode of load capacity needs to be considered in selecting and installing wiring for the electric equipment construction of halogen warm lamp group and automatic waterer group in stable.

Keywords

References

  1. National Fire Data System, "http://www.nfds.go.kr/", 2014.
  2. S. C. Kim and D. H. Kim, "Analysis of Characteristic for Electric Leakage Component at Stable Size", Journal of the Korea Society of Safety, pp.54-58, 2012.
  3. Nongmin Newspaper, "In Winter, Barn Fire, be Careful", 2009.
  4. Yonhap News, "General Fire Alarm Systems Installed in Housing Caused the Problem", 2009.
  5. D. H. Kim, S. C. Kim, S. O. Yoo, S. R. Kim and Y. B. Kim "A Study on Leakage Current Detecting System for Automatic Waterer using Livestock Barn", Journal of the Korea Society of Safety, Vol.26, No.4, pp. 34-40, 2011.
  6. Korea Electrical Safety Corporation, " Winter Livestock Barn Electricity Usage with Increased Electrical Fire Hazard", 2002.
  7. Korea Electrical Safety Corporation, "Livestock Barn Electrical Equipment Safety Inspection Results Report", 2010.
  8. Korean Industrial Standard, "KSC 3304", 2006.
  9. Korean Industrial Standard, "KS C IEC 60227 42", 2013.
  10. Korean Industrial Standard, "KSC 3328", 2006.
  11. Korean Industrial Standard,, "KSC 3611", 2006.
  12. Korea Electrical Safety Corporation, "Hand Book for Electrical Safety Management", pp.103-109, 2006.