DOI QR코드

DOI QR Code

Evaluation of Seismic Performance of 2-Story Fire Protection Sprinkler Piping System

화재방호계통 복층구조 스프링클러 파이프라인 내진성능 평가

  • Jeon, Jun-Tai (Department of Civil & Environmental Engineering, INHA Technical College) ;
  • Jung, Woo-Young (Department of Civil Engineering, GangNeung-WonJu National University) ;
  • Ju, Bu-Seog (Department of Civil Engineering, North Carolina State University)
  • Received : 2014.07.28
  • Accepted : 2014.09.28
  • Published : 2014.09.30

Abstract

Fire protection (sprinkler) piping system is an essential element for the energy supply and for the protection against the seismic-induced fire during and after an earthquake. The primary objective of this study was to understand the seismic performance of complex two-story piping system installed in a low-rise building subjected to bi-directional and three-directional earthquakes. The result of current study revealed that the displacement of the piping system in accordance with floor level was significantly different due to acceleration-sensitivity but the effect of the piping system due to the vertical direction earthquake was not significant.

화재방호계통 스프링클러 시스템의 경우 지진 발생 시 그리고 지진 발생 후에 유도되는 화재로부터 건물과 인명을 보호하고 에너지를 공급을 위한 필수 요소라 할 수 있다. 본연구의 주목적은 양방향 (x, y) 그리고 3축(x, y, z)방향의 지진의 영향을 받는 저층 건물에 설치된 복층구조 스프링클러 파이프라인의 거동과 내진성능을 평가 하고자 함이다. 결과적으로 건물의 비구조 요소인 스프링클러 파이프라인의 경우 각 층별로 다른 거동을 보이고 있으며, 또한 수직 방향의 지진의 경우 수평방향의 지진보다 파이프라인에 미치는 영향은 미미하다고 볼 수 있다.

Keywords

References

  1. Antaki, G. and Guzy, D. (1998). "Seismic Testing of Grooved and Threaded Fire Protection Joints and Correlation with NFPA Seismic Design Provisions." ASME Seismic Engineering, PVP-Vol. 364, pp.69-75.
  2. Chopra, A. K. (2001). Dynamics of Structures: Theory and Applications to Earthquake Engineering. Pearson Education, Prentice-Hall, Inc. USA.
  3. Ju, B. S. and Jung, W. Y. (2003). "Seismic fragility evaluation of multi-branch piping system installed in critical low-rise buildings." Disaster Advances, Vol.6(4), pp.59-65.
  4. Kircher, C. A. (2003). "It makes dollars and sense to improve nonstructural system performance." Proceeding of seminar on seismic design, performance, and retrofit of nonstructural components in critical facilities, Applied Technology Council-29-2, Newport Beach, California, pp.109-119.
  5. NFPA-13 (2007). Standard for the Installation of Sprinkler System. National Fire Protection Association, MA, 2007 Edition, USA.
  6. OpenSees (2011). Open System for Earthquake Engineering Simulation, available at: http://opensees,berkeley.edu
  7. PEER-NGA (2014). Pacific Earthquake Engineering Research Center: NGA Database, available at: http://peer,berkeley.edu/nga
  8. Sekizawa, A., Ebihara, M., and Notake H. (2002). "Development of Seismic-induced Fire Risk Assessment Method for a Building." Fire Safety Science-Proceedings of the Seventh International Symposium, Worcester Polytechnic Institute (WPI), Worcester, Massachusetts, pp309-320.
  9. Tian, Y., Fuchs, J., Mosqueda, G., and Filiatrault, A. (2010). "NEESR Nonstructural: Progress Report on Tests of Tee Joint Component of Sprinkler Piping System." NEESR-GC: Simulation of the Seismic Performance of Nonstructural Systems, University at Buffalo, State University of New York.

Cited by

  1. 경주지진에 의한 곡선교량의 내진 안전성 평가 vol.14, pp.1, 2018, https://doi.org/10.15683/kosdi.2018.03.31.43
  2. 지진격리장치를 적용한 복층구조파이핑 시스템의 내진성능평가 vol.14, pp.4, 2014, https://doi.org/10.15683/kosdi.2018.12.31.450