DOI QR코드

DOI QR Code

급배수시스템에서 잔류염소 농도 균등화를 위한 재염소 처리

Rechlorination for residual chlorine concentration equalization in distribution system

  • 투고 : 2014.01.14
  • 심사 : 2014.02.13
  • 발행 : 2014.02.15

초록

Three water treatment plants(WTPs) in Jeju island whose source water have different characteristics from those of the mainland of Korea were investigated. Coefficients of bulk water decay($k_b$) of free chlorine at $5^{\circ}C$ for ES, GJ, NW WTPs were $-0.003hr^{-1}$, $-0.002hr^{-1}$ and $-0.001hr^{-1}$ respectively based on bottle tests. To simulate the free chlorine variations in the distribution system using EPANET, ES WTP was chosen. Free chlorine concentrations of several sites were less than the drinking water quality standards(i.e., 0.1 mg/L); E5(0.03 mg/L), E6(0.02 mg/L), W21(0.02 mg/L) and W25(0.03 mg/L). To maintain more than 0.1 mg/L of free chlorine in the distribution system, at least 1.9 mg/L of chlorine was needed at the WTP, which suggested rechlorination was needed to supply palatable tap water to customers. Two sites, one that diverged into E5 and E6 in the east-line and another located before E21 in the west-line were selected for the appropriate rechlorination locations. The recommended rechlorination dosages were 0.42 mg/L for the east and 0.27 mg/L for the west. The simulated results indicated that the free chlorine could be reduced to 0.4 mg/L at the WTP with rechlorination, and taps with excessive free chlorine could be more stabilized(i.e., 0.1~0.4 mg/L).

키워드

참고문헌

  1. Ahn, J. Lee, S. Rho, B. Choi, Y. Choi, J. Kim, H. Park, T. Park, C. Koo, J. (2007) Modeling residual chlorine and THMs in water distribution system. J. of Korean Society of Water and Wastewater(KSWW), 29(6) 706-714.
  2. Cha, J. Kim, J. (2012) Leakage reduction through establishment of block system in Jeju city. J. of KSWW, 26(5) 693-703.
  3. Fisher, I. Kastl, G. Sathasivan, A. (2011) Evaluation of suitable chlorine bulk-decay models for water distribution systems, Wat. Res. 45, 4896-4908. https://doi.org/10.1016/j.watres.2011.06.032
  4. Hallam, N.B. West, J.R. Forster, C.F. Powell, J.C. Spencer, I. (2002) The decay of chlorine associated with the pipe wall in water distribution systems, Wat. Res. 36, 3479-3488. https://doi.org/10.1016/S0043-1354(02)00056-8
  5. Jeju special self-governing province, Division of water supply (2014) www.jejuwater.go.kr.
  6. Kim, D. Lee, D. Kim, K. Bae, C. Joo, H. (2010) Computing the dosage and analysing the effect of optimal rechlorination for adequate residual chlorine in water distribution system, J. of Korean Society of Env. Engineers, 32(10) 916-927.
  7. Korea Water Works Association(KWWA) (2010) Standards for water supply facilities.
  8. K-water (2014) www.kwater.or.kr
  9. Lee, H., Park, J. Kong, M. Kang, S. Kwak, P. Lee, J. (2013) A Study on calculation of the pipe wall decay constants of residual chlorine and affecting factors in reclaimed water supply system. J. of water treatment, 21(2) 15-27.
  10. Mays, L.W. (2000) Water distribution systems handbook, McGraw-Hill.
  11. Ministry of Environment(MOE) (2006) Internal report.
  12. Ministry of Environment(MOE) (2013) Water supply statistics 2012.
  13. Ministry of Environment(MOE) (2014) www.me.go.kr.
  14. Powell, J.C. Hallam, N.B. West, J.R. Forster, C.F., Simms, J. (2000) Factors which control bulk chlorine decay rates, Wat. Res. 34(1) 117-126. https://doi.org/10.1016/S0043-1354(99)00097-4
  15. Rossman, L.A. Clark, R.M. Grayman, W.M. (1994) Modeling chlorine residuals in drinkingwater distribution systems, 120(4) J. of Env. Eng. 803-820. https://doi.org/10.1061/(ASCE)0733-9372(1994)120:4(803)
  16. The Of fice of waterworks in Seoul metropolitan government(SMG) (2014) arisu.seoul.go.kr
  17. Tokyo metropolitan government(TMG), Bureau of waterworks (2014) www.waterworks.metro.tokyo.jp.
  18. Uber, J.G. Boccelli, D.L. Summers, R.S. Tryby, M.E. (2003) Maintaining distribution system residuals through booster chlorination. AWWARF.
  19. USEPA (2014) www.epa.gov.
  20. Yoo, H.J. Kim, J.W. Jeong, H.J. Lee, H.K. (2003) Chlorine residual prediction in drinking water distribution system using EPANET. Kor. J. env. hlth 29(1) 8-15.

피인용 문헌

  1. Post-Chlorination Process Control based on Flow Prediction by Time Series Neural Network in Water Treatment Plant vol.16, pp.3, 2016, https://doi.org/10.5391/IJFIS.2016.16.3.197
  2. 정수처리에서 TDS가 THMs 생성에 미치는 영향 vol.33, pp.3, 2019, https://doi.org/10.11001/jksww.2019.33.3.225