Selection of Number of Fans in an Air-Cooled Condenser of a 150 MW Thermal Power Plant according to Ambient Air Temperature

대기온도 변화에 따른 150 MW 화력발전소용 공랭식 복수기 송풍기수 선정

  • Received : 2014.10.16
  • Published : 2014.12.30

Abstract

During this study, number of fan by ambient air temperature that condenser pressure satisfies steam turbine exhaust pressure condition with intervals of $3^{\circ}C$ within the 150 MW thermal power plant site temperature range of $-17.1^{\circ}C$ to $36.7^{\circ}C$ was reviewed. An air cooled condenser changes its operating pressure influenced by cooling air circulation amount by atmospheric temperature and number of fan. For stable power plant operation, these were confirmed to maximize a quantity of air-cooled condenser fans at above or equal from design ambient temperature and to reduce an amount of circulating air to an air cooled condenser by depending on a quantity of fan considering exhaust pressure operation condition of a steam turbine at below design ambient temperature.

본 연구에서는 150 MW 화력발전소를 기준하여 발전소 건설지역의 최저 대기온도 $-17.1^{\circ}C$부터 최대 대기온도 $36.7^{\circ}C$까지를 $3^{\circ}C$의 일정한 간격으로 구분하여 복수기 압력이 증기터빈의 배압조건을 만족하는 대기온도별 송풍기 수량을 검토하였다. 공랭식 복수기는 대기온도 및 송풍기 운전수량 변화에 따른 냉각공기 순환량에 영향을 받아 운전조건이 변경이 되므로, 대기온도가 복수기 설계기준온도 이상의 경우에는 공랭식 복수기 송풍기의 운전수량을 최대로 해야 하고, 대기온도가 복수기 설계기준온도 미만의 경우에는 증기터빈 배압 운전조건을 만족하는 범위 내에서 송풍기 운전수량을 변화시켜 공랭식 복수기에 가해지는 공기 순환량을 감소시키는 것이 안정적인 발전소 운영을 하는 것임을 확인하였다.