Abstract
Daylighting has a great effect on people inside the room. It is also closely related to the lighting energy consumption. Daylight factor(DF) is a very important index for evaluation of the daylighting in overcast sky. The objective of this study is to verify the suitability of the Tregenza's Modified Split Flux formula for the calculation of the daylight factor. We compared the daylight factors calculated by two methods; one by a measurement with 1/5 scale model and the other by the Daysim program. We used variables for verification as window wall ratios(WWR) and angles of the sky visible. As a result, daylight factor calculated by Modified Split Flux is similar to the measurement when more daylight enters the inside. And error is significantly increased when the angle of the sky visible is $50^{\circ}$.