Component Analysis of Thermally Activated Building System in Residential Buildings

  • Chung, Woong June (Department of Architecture and Architectural Eng., Graduate School of Seoul National University) ;
  • Lee, Yu Ji (Department of Architecture and Architectural Eng., Graduate School of Seoul National University) ;
  • Yoo, Mi Hye (Department of Architecture and Architectural Eng., Graduate School of Seoul National University) ;
  • Park, Sang Hoon (Department of Architecture and Architectural Eng., Graduate School of Seoul National University) ;
  • Yeo, Myoung Souk (Department of Architecture and Architectural Eng., College of Eng., Seoul National University) ;
  • Kim, Kwang Woo (Department of Architecture and Architectural Eng., College of Eng., Seoul National University)
  • Received : 2014.01.12
  • Accepted : 2014.10.17
  • Published : 2014.12.30

Abstract

The packaged terminal air conditioner, the typical cooling system for the residential buildings, consumes a large amount of electricity in a short period time during peak hours. In order to reduce the peak load and conserve the electricity, the thermally activated building system can be used as a secondary system to handle the partial cooling load. However, the thermally activated building system may cause condensation and under-cooling. Thus, design of both systems should be performed with careful investigation in characteristics of both systems to amplify the advantages. Since the thermally activated building system has the time-delay effect which may cause under-cooling, the system is designed to handle the base load of the building. Hence, simple simulation with EnergyPlus was performed to observe the characteristics of cooling load in residential buildings. Once the possible range of the load handling ratio of the thermally activated building system was decided, characteristics of system was analyzed in terms of hardware component and operation parameters. The hardware components were analyzed in plant and system aspects and the operation parameter was evaluated in the thermal comfort aspect. As the load handling ratio increased, the thermal comfort increased due to the lower radiant mean temperatures. Within the range of thermal comfort, the several adjustments were made in setpoint temperature and electricity consumptions of difference cases were observed to decide which components and parameters were important for designing the systems.

Keywords

References

  1. ANSI/ASHRAE Standard 55 (2010), Thermal Environmental Conditions for human Occupancy, ASHRAE Standard
  2. Babiak J., Olesen, Bjaren W., Petras D., (2007) Low Temperature Heating and High Temperature Cooling, rehva.
  3. Chung W.J. (2011) "Applicability of Thermally Activated Building System Considering Heat Storage Characteristics" Spring Conference of Korean Institute of Architectural Sustainable Environment and Building System 2011.
  4. Kim I.M. (2010) "A Study on Types of Radiant Heating and Cooling System with Thermal Storage" Spring Conference of Korean Institute of Architectural Sustainable Environment and Building System 2010.
  5. Kim I.M. (2010), "An Experimental Evaluation of the Thermal Performance of a Thermally Activated Building System (TABS) for Residential Buildings in Korea" CLIMA2010.
  6. Koschenz M. (1999), "Interaction of an air system with concrete core conditioning", Energy and Buildings
  7. Lehmann B. (2007), "Application range of thermally activated building systems tabs" Energy and Buildings.
  8. Park, S. H. (2010) "An Experimental Evaluation on Thermal Performance of Thermally Activated Building System(TABS) For Residential Buildings" Spring Conference of Korean Institute of Architectural Sustainable Environment and Building System 2010.
  9. Park S. H. (2010), "The Effect on the Heat Output by Combination of Design Factors of Thermal ly Activated Building System(TABS)" Korean Institute of Architectural Sustainable Environment and Building System v.4 n.3 p 180-186
  10. Perez-Lombard L. (2011), "The map of energy flow in HVAC systems" Applied Energy
  11. Rijksen, D.O. (2009), "Reducing peak requirements for cooling by using thermally activated building system" Energy and Buildings.
  12. Saelens D. (2010), "Energy and comfort performance of thermally activated building systems including occupant behavior" Building and Environment