Application of a C-Type Filter Based LCFL Output Filter to Shunt Active Power Filters

  • Liu, Cong (State Key Laboratory of Advanced Electromagnetic Engineering and Technology, School of Electrical and Electronic Engineering, Huazhong University of Science and Technology) ;
  • Dai, Ke (State Key Laboratory of Advanced Electromagnetic Engineering and Technology, School of Electrical and Electronic Engineering, Huazhong University of Science and Technology) ;
  • Duan, Kewei (Electric Power Training Center, State Grid Hunan Electric Power Company) ;
  • Kang, Yong (State Key Laboratory of Advanced Electromagnetic Engineering and Technology, School of Electrical and Electronic Engineering, Huazhong University of Science and Technology)
  • Received : 2012.12.21
  • Published : 2013.11.20

Abstract

This paper proposes and designs a new output filter called an LCFL filter for application to three phase three wire shunt active power filters (SAPF). This LCFL filter is derived from a traditional LCL filter by replacing its capacitor with a C-type filter, and then constructing an L-C-type Filter-L (LCFL) topology. The LCFL filter can provide better switching ripple attenuation capability than traditional passive damped LCL filters. The LC branch series resonant frequency of the LCFL filter is set at the switching frequency, which can bypass most of the switching harmonic current generated by a SAPF converter. As a result, the power losses in the damping resistor of the LCFL filter can be reduced when compared to traditional passive damped LCL filters. The principle and parameter design of the LCFL filter are presented in this paper, as well as a comparison to traditional passive damped LCL filters. Simulation and experimental results are presented to validate the theoretical analyses and effectiveness of the LCFL filter.

Keywords

I. INTRODUCTION

Voltage source converters (VSCs) have been widely used in many application fields, such as distributed generations [1]- [3], microgrids [4], shunt active power filters (SAPFs) [5]- [7], adjustable speed drivers (ASDs) [8], uninterruptible power supplies (UPS) [9], etc. The proper implementation of close-loop current control schemes and pulse-width modulation (PWM) strategies in a VSC can insure good current output performance within its control bandwidth. However, the switching harmonic currents associated with the PWM process of the VSC still need to be attenuated by an output filter, otherwise they may cause harmonic interference and EMI problems in the grid or other facilities [10].

The output filter or grid interface filter of a VSC is essential to its output current quality. Traditionally, an inductor is connected at the ac output terminal of a VSC as an interface filter. However, a high inductance is required to obtain good harmonic attenuation performance, which may affect the dynamic characteristic and cause an over-modulation problem [5]. An LCL filter is a better solution than an L filter, because it can attenuate high-frequency harmonic well with a smaller output inductance and a reduced size and cost [5], [11]- [15]. However, a serious challenge faced by the LCL filter is its resonance problem, which may make the whole system unstable and degrade the output performance of the VSC [16], [17]. Fortunately, this LCL filter resonance problem can be solved with different damping methods, which can be classified as passive damping [18]- [20] and active damping [13], [21]- [26].

Active damping methods may require the measurement of some extra electrical variables for resonance damping control purposes, or complicated controllers are needed to alleviate the resonance problem. Some typical implementations of active damping methods are based on sensing the filter capacitor currents, voltages, or both for complete state feedback. Since active damping may increase the overall system costs and implementation complexity [26], passive damping methods seems to be more attractive in some cases.

Passive damping is implemented by adding some passive components to the original LCL filter [18]- [20]. Different passive damping configurations of the LCL filter are shown as Fig. 1 [18]. Fig. 1(a) shows the single resistor passive damping method of the LCL filter, in which a damping resistor Rd is connected in series with the filter capacitor Cf. This method is simple and straightforward, but the power losses of the damping resistor may be very high and will decrease the overall system efficiency. Moreover, the switching harmonic attenuation performance of the LCL filter may be degraded by the passive damping. Therefore, it is desirable to find some other passive damping solutions with less power losses for the LCL filter [18], [21], such as those shown as Fig. 1 (b)-(e). These methods are basically focused on reducing low frequency power losses. This is done by reducing the fundamental currents that flow through the damping resistor. Meanwhile, the switching harmonic attenuation performance may be affected.

Fig. 1.Different passive damping configurations of LCL filter.

This paper proposes and designs an new output filter for application to a three phase three wire SAPF. This new output filter is derived from a traditional LCL filter by replacing its capacitor with a C-type filter [27]- [29]. Therefore, it has an L-C-type filter-L (LCFL) structure and has been named an LCFL filter. It must be noted that the C-type filter adopted in the LCFL filter is not the same as that commonly referred to in the literature. Traditionally, C-type filters have been mainly used as independent passive power filters (PPFs) in industrial applications fields, such as iron and steel plants [27], HVDC projects [28], [29], and so on. There are also papers that discuss the applications of a C-type filter together with an APF [30]- [33]. However, in those papers, the C-type filters are connected in series or parallel with the APF to form hybrid filters, whose main purpose is reducing the rating of the APF. In this paper, the C-type filter based LCFL filter is an indivisible component of the SAPF, and it plays an important role in sweeping out the switching harmonic from the SAPF output current.

From the point of view of functionality, the LCFL filter is a kind of selective passive damped LCL filter. Initially, it was designed mainly for reducing the power losses generated by the damping resistor. The LC branch resonant frequency of the C-type filter is tuned at the switching frequency. Therefore, it can bypass most of the switching harmonic currents and significantly reduce the current flow though the damping resistor. Within other frequency ranges, the damping resistor can provide sufficient damping to alleviate resonance and make the system stable. Unlike the methods shown in Fig. 1, this kind of “selective damping” is effective in reducing power losses at the switching frequency. Theoretical analyses have shown that the LCFL filter exhibits excellent switching harmonic attenuation performance. Comparisons with the LCL filter have been presented in this paper. It can be seen that a SAPF with the proposed LCFL filter has better output current quality than a SAPF with the traditional single resistor damped LCL filter.

As a passive damping method, the LCFL filter inevitably has some drawbacks in terms of power efficiency and hardware costs when compared with the active damping methods. Although they have been reduced by the selective damping, there are still some passive damping power losses along with the LCFL filter, which will degrade the overall efficiency of the SAPF. On the other hand, the extra passive components may increase the overall weight and hardware cost. However, it should be noted that the active damping methods may not be economical. As previously mentioned, they may need some extra sensors and control algorithms, which will increase the costs in terms of both hardware and software.

This paper is organized as follows. In Section II, the proposed system configuration is briefly described. In Section III, the principle of the LCFL filter is analyzed, and its design procedure is presented. Section IV describes the main control schemes of the SAPF. Simulation and experimental results are provided in Section V and Section VI, respectively. Finally, conclusions are given in Section VII.

 

II. SYSTEM CONFIGURATION DESCRIPTION

Fig. 2 shows a system configuration diagram of the proposed three-phase three-wire SAPF. The LCFL filter is connected between the SAPF converter and the AC grid. It should be noted that the C-type filter branches of the LCFL filter are connected in delta configuration, which is quite convenient for low voltage application situations. The topology of the traditional passive damped LCL filter is also shown in Fig. 2, which will be used for comparison with the LCFL filter. A three phase diode uncontrolled rectifier with a RL-type dc side load acts as a typical nonlinear load, which will generate a large amount of (6n±1)th characteristic harmonic currents. The system parameters for the simulation and experiment are listed in Table I.

The SAPF senses the three phase voltages vg a,b,c of the point of common coupling (PCC) for system synchronization. The angular frequency ω and phase angle θg of the fundamental voltage are extracted by the phase locked loop (PLL). Three phase nonlinear load currents il a,b,c are sensed by current transformers (CT) to extracted the harmonic current references, and the grid side output currents of the SAPF igf a,b,c are detected as feedbacks of the close-loop output current control.

Fig. 2.Configuration diagram of SAPF with output filter in a three-phase three-wire system.

TABLE ISYSTEM PARAMETERS

The control scheme of the SAPF is also shown in Fig. 2. The harmonic current reference is extracted from the nonlinear load current. Firstly, the fundamental component is calculated by the recursive discrete Fourier transform (RDFT) algorithm [34], and then the harmonic current reference is obtained by simply subtracting the fundamental component from the nonlinear load current. The dc bus voltage of the SAPF converter is regulated the by a PI controller, which forms the outer loop of the control system. The output current tracking control is the inner loop, which is implemented by detecting the grid-side inductor current of the SAPF, and then taking it as a feedback signal of the close-loop current control. The current tracking control is mainly implemented in the fundamental synchronous rotating frame (SRF). A detailed description of the harmonic detection algorithm and output current control scheme will be presented in Section IV.

 

III. PRINCIPLE AND DESIGN OF THE LCFL FILTER

Fig. 3(a) shows the single-phase equivalent topology of the proposed LCFL filter that is shown in Fig. 2. For comparison, the traditional passive damped LCL filter is shown in Fig. 3(b). It must be noted that the parameters relationship between the LCFL filters shown in Fig. 3 and Fig. 2 must follow the Y-Δ transformation principle, which is: Cf=CfΔ×3, Rd=RdΔ/3, Lh=LhΔ/3, and Ch=ChΔ×3

A. C-Type Filter

The C-type filter is in the dashed line box shown in Fig. 3(a), where ZCF is the impedance of the C-type filter, which can be written as:

For the passive damped LCL filter shown in Fig. 3(b), the impedance of its RC series branch ZRC can be written as:

Fig. 3.Single-phase equivalent topologies of SAPFs with (a) the proposed LCFL filter, and (b) the traditional LCL filter.

The impedance characteristic curves of the C-type filter and the RC filter can be plotted as shown in Fig. 4 based on (1) and (2), respectively. It can be seen from the magnitude curves that the impedance magnitude of the C-type filter approaches that of the RC filter in the low frequency and high frequency ranges, when they both have the same parameters for Cf and Rd. However, the impedance magnitude of the C-type filter around the resonant frequency is much lower than that of the RC filter. This difference is caused by the Lh-Ch series resonant branch, whose impedance is nearly zero at its resonant frequency. Such an impedance characteristic gives the C-type filter better selective harmonic filtering performance around the resonant frequency fLC, which can be calculated as:

Fig. 4.Impedance characteristics of the C-type filter and RC filter as shown in Fig. 3.

B. Model of the LCFL Filter

Based on the single phase equivalent topology shown in Fig. 3(a), the plant model of the LCFL filter can be represented as shown in Fig. 5. The transfer function from the SAPF converter output voltage vf to the LCFL filter grid side current igf in the frequency domain can be written as (4), as shown at the bottom of this page.

The transfer function of the LCL filter can be written as:

where Rd is the damping resistance value of the LCL filter. Rd=0 when it is undamped.

Fig. 5.Plant model of the proposed LCFL filter.

Bode diagrams of (4) and (5) are plotted as shown in Fig. 6. The corresponding curve of an L-filter is drawn in Fig. 6, with an inductance value of:

Comparing the curves shown in Fig. 6, it can be seen that the magnitude responses of the LCFL filter and LCL filter approach that of the L-filter at the frequency range below 2.5 kHz, which means that both the LCFL filter and LCL filter can be simplified as an inductor in the low frequency range. However, their magnitude responses are quite different at the frequency range above 4.59 kHz, especially at around the switching frequency of 9.6 kHz. As shown in Fig. 6, the slope rate of the magnitude curve of the L-filter is -20 dB/dec, and the corresponding slope rate of the un-damped LCL filter is -60 dB/dec, which indicates that the un-damped LCL filter has better switching harmonic attenuation capability than the L-filter with the same output inductance. However, a resonant peak at a frequency of 4.59 kHz can be spotted in the magnitude curve of the undamped LCL filter, which may impact the system stability. Simply adding a damping resistor in series with the filter capacitor alleviates the resonant peak, but the slope rate of the magnitude curve of the damped LCL filter will be degraded to about -40 dB/dec.

Fig. 6.Bode plots of the LCFL filter and LCL filters.

Examining the magnitude curve of the proposed LCFL filter, the green line shown in Fig. 6, it can be seen that its magnitude value around the switching frequency 9.6 kHz is even lower than that of the undamped LCL filter, which indicates the excellent switching frequency harmonic attenuation capability of the LCFL filter. Moreover, no resonant peak can be spotted around the resonant frequency fres, which means that the LCFL filter can damp the resonance problem effectively. It can be concluded from the Bode plots shown in Fig. 6 that the LCFL filter has better switching harmonic alleviation ability than the LCL filter and the L-filter.

From a topology point of view, the LCFL filter can be obtained by simply adding an LC branch connected in parallel with the damping resistor of a passive damped LCL filter. This LC branch series resonance frequency is tuned at the switching frequency, so it provides a low impedance path for the switching harmonic current and significantly reduces that flow through the damping resistor. Therefore, the power losses of the damping resistor of the LCFL filter can be significantly reduced. On the other hand, for the passive damped LCL filter, all of the switching harmonic current that is filtered by the capacitor will also flow through the damping resistor, which produces a large amount of the power losses. Compared to the traditional LCL filter, the LCFL filter proposed in this paper can provide better switching ripple attenuation capability. In addition, it reduces the power losses of the damping resistor.

C. Design of the LCFL Filter

The LCFL filter can be designed by the following step-bystep design procedure.

 

IV. CONTROL SCHEME OF THE SAPF

A. Mathematical Model of the SAPF

Based on the previous analysis, it can be seen the LCFL filter behaves like an inductor at the low frequency range below 2.5 kHz. For harmonic compensation of the SAPF, the common requirement of its output current is upon to the 50th harmonic, which means that only the frequency range below 2.5 kHz needs to be considered while designing the control system. As a result, it is reasonable to simplify the LCFL filter as an inductor in low frequency range, whose inductance value is determined by (6). Therefore, the main circuit of the three-phase three-wire SAPF in the low frequency range can be simplified as shown as Fig. 7.

Fig. 7.Simplified main circuit of the three-phase three-wire SAPF at low frequency range.

Based on the KVL principle, the differential equations that describe the SAPF output current and voltage relationship is:

where, vg a,b,c are the PCC voltages, vf a,b,c are the output voltages of the SAPF, and ia,b,c are the output currents of the SAPF. L=La=Lb=Lc=300μH is the output inductance, and R is the equivalent series resistance (ESR) of the output inductor.

Equation (13) can be expressed in the d-q SRF by the synchronous rotating transformation, which yields:

which is the mathematical model of the three-phase three-wire SAPF in the d-q SRF.

B. RDFT Based Harmonic Current Extraction Algorithm

The RDFT algorithm is suitable for extracting each harmonic component from a periodical signal, which will be used for the harmonic current extraction of the SAPF. The principle of the RDFT algorithm can be described as follows:

Assume a periodic signal x(t) with a time period T, then it can be expressed as the sum of its harmonic components as:

where, h is the harmonic order, Nm is the maximum harmonic order to be considered, ω is the fundamental angular frequency, N is the sampling number in a fundamental period, τ=T/N is the sampling interval time, and Ah and Bh are the amplitudes of the real and imaginary components of the hth harmonic.

Now the fundamental component can be considered. At each sampling interval, the amplitudes of the real and imaginary components can be calculated in real-time using the latest N sampled values of the x(t), as follows:

where, k represents the newest sample point.

However, equation (16) is hard to implement in a DSP, because each calculation needs the latest N sampled values of the input signal, which will take the DSP a large amount of resources and make it unpractical for SAPF application. However, (16) can be expressed in a recursive way as follows:

Substituting (17) into (15), the fundamental component can be obtained as:

In this paper, the periodical signal is the nonlinear load current il. Using the RDFT algorithm described above, the fundamental current can be extracted from the nonlinear load current, and then the harmonic current can be obtained by subtracting the fundamental component from the nonlinear load current. The application of the RDFT can eliminate the requirement of low-pass filters in the d-q frame, and it exhibits several merits such as a fast transient response speed and excellent steady-state accuracy [34].

C. SAPF Output Current Tracking Control

The SAPF output current tracking control is implemented in the d-q frame. Since the main components of the output currents of the SAPF are harmonic currents, they are still ac quantities after the fundamental synchronous rotating transform. The traditional PI controller cannot ensure zero steady-state error tracking to the ac signals. As a result, the repetitive controller is considered, and its structure is shown in Fig.8.

Fig. 8.Diagram of repetitive controller.

The repetitive controller is based on the internal mode principle. A repetitive signal generator is inserted into the control loop, as shown in Fig. 8, and acts as the internal mode of the input signal. The repetitive controller can ensure perfect tracking to a periodic signal with zero steady-state error. However, its dynamic response is not very fast. In this paper, a PI controller and a repetitive controller are put in parallel in the SAPF output current control system, to guarantee both the current tracking dynamic response speed and steady-state accuracy [35].

 

V. SIMULATION RESULTS

Simulation of the LCFL-filter-based SAPF was conducted with Matlab/Simulink software, based on the system configuration shown in Fig. 1 and the parameters listed in Table I.

Fig. 9 shows the harmonic compensation steady-state simulation results of the LCFL-filter-based SAPF. Fig. 9(a) shows the nonlinear load current il, whose THD is 29.33%. Fig. 9(b) shows the grid current ig, whose THD is reduced to 4.42% after harmonic compensation by the SAPF. Fig. 9(c) presents the output compensation current igf of the SAPF, which is the grid side inductor current of the LCFL filter.

Fig. 9.Steady-state harmonic compensation simulation results of the LCFL-filter-based SAPF. (a) Nonlinear load current. (b) Grid current, and (c) SAPF output current.

Fig. 10 shows the waveforms and spectrums of the currents that flow through the different components of the LCFL filter. It can be seen in Fig. 10(a) that the converter side current contains a lot of switching ripples. However, they are mostly absorbed by the C-type filter, as shown as Fig. 10(b). The unwanted switching ripple currents injected into the grid are thus significantly reduced. This can be reflected in the waveform and spectrum of the grid side inductor current as shown as Fig. 10(c).

Fig. 10.Simulation waveform and spectrum of current that flow through different components of the LCFL-filter: (a) converter side inductor current, (b) C-type filter branch current, and (c) grid side inductor current.

Fig. 11 presents the currents that flow through the damping resistors of the LCFL filter and LCL filter. It can be seen from the magnitude spectrum of Fig. 11(a) that there is almost no switching frequency harmonic component in the damping resistor current of the LCFL filter. The RMS value of the damping resistor current of the LCFL filter is 1.92A. Therefore, the damping resistor power loss can be calculated as 1.922×7.5=27.6(W). The RMS value of the damping resistor current of the LCL filter is 4.39A, and the corresponding power loss is 4.392×7.5=144.5(W). It can be seen that the damping resistor power loss of the LCL filter is about 5.2 times larger than that of the LCFL filter.

Fig. 11.Simulation waveform and magnitude spectrum of damping resistor current (a) the LCFL filter, and (b) the LCL filter.

 

VI. EXPERIMENTAL RESULTS

A 66.6 kVA three-phase three-wire SAPF prototype based on the parameters listed in Table I was built in the laboratory, to validate the theoretical analyses and functionality of the LCFL filter. The control algorithm was implemented in the control board which is based on a TMS320F2812 digital signal processor (DSP). The A/D sampling frequency is set at 9.6 kHz, which is the same as the switching frequency of the SAPF converter.

Fig. 12 shows the harmonic compensation steady-state experimental results of the LCFL-filter-based SAPF. Fig. 12(a) shows the nonlinear load current waveform that contains a large amount of harmonic current, and whose THD is 28.43%. Fig. 12(b) shows the grid current after harmonic compensation by the SAPF, where the THD is reduced to 4.83%. Fig. 12(c) presents the output current of the SAPF, which is also the grid side current of the LCFL filter.

Fig. 12.Harmonic compensation steady-state experimental results of the LCFL-filter-based SAPF: (a) nonlinear load current, (b) grid current, and (c) SAPF output current.

Fig. 13 shows the currents that flow through the different components of the LCFL filter. Fig. 13(a) shows the converter-side inductor current, which contains a large amount of switching ripple. Fig. 13(b) shows the current absorbed by the C-type filter branch, whose main component is the switching harmonic current generated by the SAPF converter. Fig. 13(c) shows the grid-side inductor current. It can be seen that its waveform quality is much better than that of the converter-side inductor current.

Fig. 13.Experimental results of current waveform that flow through different components of the LCFL-filter: (a) converter side inductor current, (b) C-type filter current, and (c) grid side inductor current.

Fig. 14 compares the spectrums of the grid-side inductor currents of both the LCFL filter and LCL filter based SAPF. It can be clearly seen that the harmonic current magnitude around the switching frequency of the LCFL-filter-based SAPF is much lower than that of the LCL-filter-based SAPF, which indicates a better switching harmonic attenuation performance of the LCFL filter.

Fig. 14.Spectrums of the grid side inductor currents of (a) LCFL-filter-based SAPF, and (b) LCL-filter-based SAPF.

Fig. 15 shows the currents flowing through the damping resistors of the LCFL filter and LCL filter, which are closely related to the power losses. The RMS value of the current flow through the damping resistor of the LCFL filter is 2.08A, while its counterpart of the LCL filter is 3.37A. The damping resistor power loss of the LCL filter can be calculated as 3.372×7.5=85.2(W), and the corresponding power loss of the LCFL filter is 2.082×7.5=32.4(W). It can be seen that the damping resistor power loss of the LCFL filter is much less than that of the traditional passive damped LCL filter.

Fig. 15.Currents that flow through the damping resistors of (a) LCFL filter, and (b) LCL filter.

 

VII. CONCLUSIONS

This paper proposed and designed an output filter called an LCFL filter for application to a three-phase three-wire SAPF. This LCFL filter is derived from a traditional LCL filter by replacing its capacitor with a C-type filter, and then constructing an L-C-type filter-L (LCFL) topology. Theoretical analyses have shown that the LCFL filter can provide better switching harmonic attenuation than the traditional passive damped LCL filter. Furthermore, since the switching harmonic currents are mostly bypassed by the LC series branch of the C-type filter, the damping resistor power loss can be significantly reduced when compared to the passive damped LCL filter. The principle and parameter design of the LCFL filter have been presented, and simulation and experimental results have verified the theoretical analyses as well as the effectiveness of the LCFL filter.

References

  1. F. Blaabjerg, Z. Chen, and S. B. Kjaer, "Power electronics as efficient interface in dispersed power generation systems," IEEE Trans. Power Electron., Vol. 19, No. 5, pp. 1184-1194, Sep. 2004. https://doi.org/10.1109/TPEL.2004.833453
  2. F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, "Overview of control and grid synchronization for distributed power generation systems," IEEE Trans. Ind. Electron., Vol. 53, No. 5, pp. 1398-1409, Oct. 2006.
  3. Q.-N. Trinh and H.-H. Lee, "Advanced repetitive controller to improve the voltage characteristics of distributed generation with nonlinear loads," Journal of Power Electronics, Vol. 13, No. 3, pp. 409-418, May 2013. https://doi.org/10.6113/JPE.2013.13.3.409
  4. J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodriguez, "Control of power converters in AC microgrids," IEEE Trans. Power Electron., Vol. 27, No. 11, pp. 4734-4749, Nov. 2012. https://doi.org/10.1109/TPEL.2012.2199334
  5. Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, "Generalized design of high performance shunt active power filter with output LCL filter," IEEE Trans. Ind. Electron., Vol. 59, No. 3, pp. 1443-1452, Mar. 2012. https://doi.org/10.1109/TIE.2011.2167117
  6. S. Zhang, K. Dai, B. Xie, and Y. Kang, "Parallel control of shunt active power filters in capacity proportion frequency allocation mode," Journal of Power Electronics, Vol. 10, No. 4, pp. 419-427, Jul. 2010. https://doi.org/10.6113/JPE.2010.10.4.419
  7. H. H. Tumbelaka, L. J. Borle, C. V. Nayar, and S. R. Lee, "A grid current-controlling shunt active power filter," Journal of Power Electronics, Vol. 9, No. 3, pp. 365-376, May 2009.
  8. H. M. Suryawanshi, A. K. Kulwal, M. A. Chaudhari, and V. B. Borghate, "High power factor operation of a three-phase rectifier for an adjustable-speed drive," IEEE Trans. Ind. Electron., Vol. 55, No.4, pp. 1637-1646, Apr. 2008. https://doi.org/10.1109/TIE.2008.917110
  9. S. Jiang, D. Cao, Y. Li, J. Liu, and F. Z. Peng, "Low-THD, fast-transient, and cost-effective synchronous-frame repetitive controller for three-phase UPS inverters," IEEE Trans. Power Electron., Vol. 27, No. 6, pp. 2994-3005, Jun. 2012. https://doi.org/10.1109/TPEL.2011.2178266
  10. K. Mainali, R. Oruganti, K. Viswanathan, and A. P. Ng, "A metric for evaluating the EMI spectra of power converters," IEEE Trans. Power Electron., Vol. 23, No. 4, pp. 2075-2081, Jul. 2008. https://doi.org/10.1109/TPEL.2008.925154
  11. G. Shen, D. Xu, L. Cao, and X. Zhu, "An improved control strategy for grid-connected voltage source inverters with an LCL filter," IEEE Trans. Power Electron., Vol. 23, No. 4, pp. 1899-1906, Jul. 2008. https://doi.org/10.1109/TPEL.2008.924602
  12. I. J. Gabe, V. F. Montagner, and H. Pinheiro, "Design and implementation of a robust current controller for VSI connected to the grid through an LCL filter," IEEE Trans. Power Electron., Vol. 24, No. 6, pp. 1444-1452, Jun. 2009. https://doi.org/10.1109/TPEL.2009.2016097
  13. G. Hu, C. Chen, and S. Duan, "New active damping strategy for LCL-filter-based grid-connected inverters with harmonics compensation," Journal of Power Electronics, Vol. 13, No. 2, pp. 287-295, Mar. 2013. https://doi.org/10.6113/JPE.2013.13.2.287
  14. J. Xu, S. Xie, and T. Tang, "Systematic current control strategy with pole assignment for grid-connected LCL-filtered inverters," Journal of Power Electronics, Vol. 13, No. 3, pp. 447-457, May 2013. https://doi.org/10.6113/JPE.2013.13.3.447
  15. L. Zhou, M. Yang, Q. Liu, and K. Guo, "New control strategy for three-phase grid-connected LCL inverters without a phase-locked loop," Journal of Power Electronics, Vol. 13, No. 3, pp. 487-486, May 2013. https://doi.org/10.6113/JPE.2013.13.3.487
  16. Y. Tang, P. C. Loh, P. Wang, F. H. Choo, and F. Gao, "Exploring inherent damping characteristic of LCL-filters for three-phase grid-connected voltage source inverters," IEEE Trans. Power Electron., Vol. 27, No. 3, pp. 1433-1443, Mar. 2012. https://doi.org/10.1109/TPEL.2011.2162342
  17. D. Ricchiuto, M. Liserre, T. Kerekes, R. Teodorescu, and F. Blaabjerg, "Robustness analysis of active damping methods for an inverter connected to the grid with an LCL-filter," in Proc. IEEE ECCE, pp. 2028-2035, 2011.
  18. T. CY Wang, Z. Ye, G. Sinha, and X. Yuan, "Output filter design for a grid-interconnected three-phase inverter," in Proc. IEEE PESC, pp. 779-784, 2003.
  19. M. Liserre, F. Blaabjerg, and S. Hansen, "Design and control of an LCL-filter-based three-phase active rectifier," IEEE Trans. Ind. Appl., Vol. 41, No. 5, pp. 1281-1291, Sep./Oct. 2005. https://doi.org/10.1109/TIA.2005.853373
  20. R. Pena-Alzola, M. Liserre, F. Blaabjerg, R. Sebastian, J. Dannehl, and F. W. Fuchs, "Analysis of the passive damping losses in LCL-filter-based grid converters," IEEE Trans. Power Electron., Vol. 28, No. 6, pp. 2642-2646, Jun. 2013. https://doi.org/10.1109/TPEL.2012.2222931
  21. J. Dannehl, M. Liserre, and F. W. Fuchs, "Filter-based active damping of voltage source converters with LCL filter," IEEE Trans. Ind. Electron., Vol. 58, No. 8, pp. 3623-3633, Aug. 2011. https://doi.org/10.1109/TIE.2010.2081952
  22. Y. Lei, Z. Zhao, F. He, S. Lu, and L. Yin, "An improved virtual resistance damping method for grid-connected inverters with LCL filters," in Proc. IEEE ECCE, pp. 3816-3822, 2011.
  23. E. Wu and P. W. Lehn, "Digital current control of a voltage source with active damping of LCL resonance," IEEE Trans. Power Electron., Vol. 21, No. 5, pp. 1364-1373, Sep. 2006.
  24. M. Malinowski and S. Bernet, "A simple voltage sensorless active damping scheme for three-phase PWM converters with an LCL filter," IEEE Trans. Ind. Electron., Vol. 55, No. 4, pp. 1876-1880, Apr. 2008. https://doi.org/10.1109/TIE.2008.917066
  25. M. Liserre, A. Dell'Aquila, and F. Blaabjerg, "Genetic algorithm-based design of the active damping for an LCL-filter three-phase active rectifier," IEEE Trans. Power Electron., Vol. 19, No. 1, pp. 76-86, Jan. 2004. https://doi.org/10.1109/TPEL.2003.820540
  26. J. Dannehl, F. W. Fuchs, S. Hansen, and P. B. Thogersen, "Investigation of active damping approaches for PI-based current control of grid-connected pulse width modulation converters with LCL filters," IEEE Trans. Ind. Applicat., Vol. 46, No. 4, pp. 1509-1517, Jul./Aug. 2010. https://doi.org/10.1109/TIA.2010.2049974
  27. C. O. Gercek, M. Ermis, A. Ertas, K. N. Kose, and O. Unsar, "Design, implementation, and operation of a new C-type 2nd harmonic filter for electric arc and ladle furnaces," IEEE Trans. Ind. Applicat., Vol. 47, No. 4, pp. 1545-1557, Jul./Aug. 2011. https://doi.org/10.1109/TIA.2011.2155020
  28. M.A. Zamani, M. Moghaddasian, M. Joorabian, S.Gh. Seifossadat, and A. Yazdani, "C-type filter design based on power-factor correction for 12-pulse HVDC converters", in Proc. IECON, pp. 3039-3044, 2008.
  29. S. H. E. A. Aleem, A. F. Zobaa, and M. M. A. Aziz, "Optimal C-type passive filter based on minimization of the voltage harmonic distortion for nonlinear loads," IEEE Trans. Ind. Electron., Vol. 59, No. 1, pp. 281-289, Jan. 2012. https://doi.org/10.1109/TIE.2011.2141099
  30. Q. Tao, K. Liu, L. Zhou, and Q. Chen, "The Suppression of resonance by a new hybrid power filter," in Proc. ICIEA, 2006.
  31. Q. Chen, Z. Chen, and M. McCormick, "The application and optimization of C-type filter in a combined harmonic power filter," in Proc. IEEE PESC, pp. 1041-1045, 2004.
  32. Q. Tao, K. Liu, X. Zha, and Q. Chen, "The topology and control of a new hybrid power filter," in Proc. IEEE PESC, 2006.
  33. N. Bett, J. N. Nderu, and P. K. Hinga, "Neuro-fuzzy control technique in hybrid power filter for power quality improvement in a three-phase three-wire power system," Innovative Systems Design and Engineering, Vol. 3, No. 4, pp. 41-50, 2012.
  34. K. Borisov, H. L. Ginn III, and G. Chen, "A computationally efficient RDFT-based reference signal generator for active compensators," IEEE Trans. Power Del., Vol. 24, No. 4, pp. 2396-2404, Oct. 2009.
  35. X. Wei, K. Dai, X. Fang, P. Geng, and Y. Kang, "Performance analysis and improvement of output current controller for three-phase shunt active power filter," in Proc. IECON, pp. 1757-1761, 2006.

Cited by

  1. Adaptive DC-link Voltage Control for Shunt Active Power Filter vol.14, pp.4, 2014, https://doi.org/10.6113/JPE.2014.14.4.764
  2. High-Performance Control of Three-Phase Four-Wire DVR Systems using Feedback Linearization vol.16, pp.1, 2016, https://doi.org/10.6113/JPE.2016.16.1.351
  3. Parallel Resonance Detection and Selective Compensation Control for SAPF With Square-Wave Current Active Injection vol.64, pp.10, 2017, https://doi.org/10.1109/TIE.2017.2696461
  4. Analysis and Design of DC-link Voltage Controller in Shunt Active Power Filter vol.15, pp.3, 2015, https://doi.org/10.6113/JPE.2015.15.3.763
  5. An improved adaptive minimum dc-link voltage controller vol.13, pp.12, 2016, https://doi.org/10.1587/elex.13.20160429
  6. Topologies, generalized designs, passive and active damping methods of switching ripple filters for voltage source inverter: A comprehensive review vol.62, 2016, https://doi.org/10.1016/j.rser.2016.04.006
  7. Damping techniques for grid-connected voltage source converters based on LCL filter: An overview vol.81, 2018, https://doi.org/10.1016/j.rser.2017.07.050
  8. Improved adaptive notch filter-based active damping method for shunt active power filter with LCL-filter vol.100, pp.3, 2018, https://doi.org/10.1007/s00202-018-0685-9