Abstract

The present study has been conducted to investigate the fire combustion properties and fire behavior of an IEEE-383 qualified flame retardant cable. The reference reaction rate and reference temperature which are commonly used in pyrolysis model of fire propagation process was obtained by the thermo-gravimetric analysis of the cable component materials. The mass fraction of FR-PVC sheath abruptly decreased near temperature range of $250{\sim}260^{\circ}C$ and its maximum reaction rate was about $2.58{\times}10^{-3}$[1/s]. For the XLPE insulation of the cable, the temperature causing maximum mass fraction change was ranged about $380{\sim}390^{\circ}C$ and it has reached to the maximum reaction rate of $5.10{\times}10^{-3}$[1/s]. The flame retardant cable was burned by a pilot flame meker buner and the burning behavior of the cable was observed during the fire test. Heat release rate of the flame retardant cable was measured by a laboratory scale oxygen consumption calorimeter and the mass loss rate of the cable was calculated by the measured cable mass during the burning test. The representative value of the effective heat of combustion was evaluated by the total released energy integrated by the measured heat release rate and burned mass. This study can contribute to study the electric cable fire and provide the pyrolysis properties for the computational modeling.

Keywords

References

  1. O. K. Rahkonen and J. Mangs, Bertrand, R. and M. Rowekamp, "Fire Induced Damages to Electrical Cables and Fire Growth on Cables", EUROSAFE Forum 2002, Seminar 1, 2002.
  2. IAEA, "Experience Gained from Fires in Nuclear Power Plants: Lessons Learned", IAEA-TECDOC- 1421, 2004.
  3. EPRI/NRC-RES, "Fire PRA Methodology for Nuclear Power Facilities", NUREG/CR-6850, 2005.
  4. IEEE Power Engineering Society, "IEEE Standard for Qualifying Class 1E Electric Cables and Field Splices for Nuclear Power Generating Stations", IEEE Std 383, 2003.
  5. H. S. Lim and D. Y. Kim, "A Study on Heat-Flux Evaluation for Cable Fire Including Diagnostic Methodology for Degradation in Nuclear Power Plants", Journal of the Korean Society of Safety, Vol. 26, No. 2, pp. 20-25, 2011.
  6. S. C. Kim and S. H. Lee, "Assessment of Grid Sensitivity in the FDS Field Model to Simulate the Flame Propagation of an Electric Cable Fire", Journal of the Korean Society of Safety, Vol. 23, No. 4, pp. 30-35, 2008.
  7. J. Hietaniemi, S. Hostikka and J. Vaari, "FDS Simulation of Fire Spread - Comparison of Model Results with Experimental Data", VTT Woring Papers 1459-7683, pp. 33-38, 2004.
  8. K. McGrattan, R. McDermott, S. Hostikka and J. Floyd, "Fire Dynamics Simulator(Version 5) User's Guide", NIST Special Publication 1019-5, 2010.
  9. R. A. Bryant, T. J. Ohlemiller, E. R. Johnsson, A. Hamins, B. S. Grove, Guthrie, G. W., Maranghides, A. and Mulholland, G. W., "The NIST 3MW Quantitative Heat Release Rate Facility - Description and Procedures", NISTIR-7052, 2004.
  10. W. A. Al-Sayegh, O. Aljumaih, G. E. Andrews and H. N. Phylaktou, "Electrical Cable Fires Using the Cone Calorimeter for Toxic Gas Investigations", 6th Fire and Explosion Hazards Seminar, University of Leeds, 2010.
  11. Q. Xie, H. Zhang and L. Tong, "Experimental Study on the Fire Protection Properies of PVC sheath for old and new cables", Journal of Hazardous Materials, Vol. 179, No. 9, pp. 373-381, 2010. https://doi.org/10.1016/j.jhazmat.2010.03.015

Cited by

  1. Experimental Study of Flame Spread Characteristics of a Electric Cable Tray vol.16, pp.4, 2016, https://doi.org/10.9798/KOSHAM.2016.16.4.31
  2. A Study on the Transient State Characteristics of TFR-8 Cable caused by Over Current vol.29, pp.1, 2015, https://doi.org/10.5207/JIEIE.2015.29.1.057