DOI QR코드

DOI QR Code

Two-phase Pressure Drop in Horizontal Rectangular Channel

수평 사각 채널에서의 상 압력 강하

  • Received : 2013.03.25
  • Accepted : 2013.05.31
  • Published : 2013.06.30

Abstract

Two-phase pressure drop experiments were performed during flow boiling to deionized water in a microchannel having a hydraulic diameter of $500{\mu}m$. Tests were made in the ranges of heat fluxes from 100 to $400kW/m^2$, vapor qualities from 0 to 0.2 and mass fluxes of 200, 400 and $600kg/m^2s$. The frictional pressure drop during flow boiling is predicted by using two models; the homogeneous model that assumes equal phase velocity and the separate flow model that allows a slip velocity between two phases. From the experimental results, it is found that the two phase multiplier decreases with an increase in mass flux. Measured data of pressure drop are compared to a few available correlations proposed for macroscale and mini/microscale. Among the separated flow models, the correlation model suggested by Lee and Garimella predicted the frictional pressure drop within MAE of 47.2%, which is better than other correlations.

Keywords

References

  1. Beattie, D.R.H. and Whalley, P.B.(1982). A simple two-phase flow frictional pressure drop calculation method, Int. J. Multiphase Flow, 8, 83-87. https://doi.org/10.1016/0301-9322(82)90009-X
  2. Chisholm, D.(1983). Two-phase Flow in Pipelines and Heat Exchangers, Longman, New York.
  3. Cicchitti, A., Lombardi, C., Silvestri, M., Solddaini, G., and Zavalluilli, R.(1960). Two-phase cooling experiments pressure drop, heat transfer and burnout measurement, Energia Nucl. 7, 407-425.
  4. Dukler, A.E. and Wicks III, M., and Cleveland, R.G.(1964). Pressure drop and hold-up in two-phase flow, J. AIChE, 10, 38-51. https://doi.org/10.1002/aic.690100117
  5. Friedel, L.(1979). Improved Friction Pressure Drop Correlations for Horizontal and Vertical Two-Phase Pipe Flow, Presented at the European Two-phase Flow Group Meeting, Ispra, Italy, Paper E2, June, 18, 485-492.
  6. Lee, P.S. and Garimella, S.V.(2008). Saturated flow boiling heat transfer and pressure drop in silicon microchannel arrays, Int. J. Heat and Mass Transfer, 51, 789-806. https://doi.org/10.1016/j.ijheatmasstransfer.2007.04.019
  7. Lee, J. and Mudawar, I.(2005). Two-phase flow in high-heat-flux micro-channel heat sink for refrigeration cooling applications: Part I-pressure drop characteristics, Int. J. Heat and Mass Transfer, 48, 928-940. https://doi.org/10.1016/j.ijheatmasstransfer.2004.09.018
  8. You, S. S. ․ Lim, T. W. ․ Jeong, S. K. and Park, J. U.(2007), A Study on the microcooling Fin Fabrication Process for Enhancing Boiling Heat Transfer, Korea, Jour. Fish. Mar. Sci. Edu., 19(3), 366-372.
  9. Lim, T. W. and You, S. S.(2008), Nucleate Boiling Heat Transfer from Micro Finned Surfaces in Subcooled FC-72, Korea, Jour. Fish. Mar. Sci. Edu., 20(3), 410-415.
  10. McAdams, W.H.(1954). Heat transmission, third ed. McGraw-Hill, New York.
  11. Mishima, K. and Hibiki, T.(1996). Some characteristics of air-water two-phase flow in small diameter vertical tubes, Int. J. Multiphase Flow, 22, 703-712. https://doi.org/10.1016/0301-9322(96)00010-9
  12. Tran, T.N., Chyu, M.C., Wambsganss, M.W., and France, D.M.(2000). Two-phase pressure drop of refrigerants during flow boiling in small channels: and experimental investigation and correlation development, Int. J. Multiphase Flow, 26, 1739-1754. https://doi.org/10.1016/S0301-9322(99)00119-6

Cited by

  1. A New Correlation on Pressure Drop in Horizontal Multi Channels vol.28, pp.5, 2016, https://doi.org/10.13000/JFMSE.2016.28.5.1273
  2. A New Correlation on Heat Transfer Coefficient in Horizontal Multi Channels vol.28, pp.5, 2016, https://doi.org/10.13000/JFMSE.2016.28.5.1388