DOI QR코드

DOI QR Code

A Study on the Operating Control of a Heat Pump System with Screw Compressors

스크류 열펌프 시스템의 운전제어 방안에 관한 연구

  • Park, Jun-Tark (Department of Energy Efficiency, Korea Institute of Energy Research(KIER)) ;
  • Lee, Young-Soo (Department of Energy Efficiency, Korea Institute of Energy Research(KIER)) ;
  • Kim, Jiyoung (Department of Energy Efficiency, Korea Institute of Energy Research(KIER)) ;
  • Chae, Kyu-Jung (Environmental Technology Lab, R&BD Center, Kolon Global Corp.) ;
  • Yang, Hee-Jung (Environmental Technology Lab, R&BD Center, Kolon Global Corp.)
  • 박준택 (한국에너지기술연구원(KIER) 에너지효율연구단) ;
  • 이영수 (한국에너지기술연구원(KIER) 에너지효율연구단) ;
  • 김지영 (한국에너지기술연구원(KIER) 에너지효율연구단) ;
  • 채규정 (코오롱글로벌(주) R&BD Center 환경기술연구소) ;
  • 양희정 (코오롱글로벌(주) R&BD Center 환경기술연구소)
  • Received : 2013.01.24
  • Published : 2013.03.10

Abstract

A preliminary performance test of a 30RT 2-stage screw heat pump was carried out in order to develop a high performance large-scale unutilized energy source heat pump system, which will be used for district heating and cooling. In this study, two issues of the system operating control were investigated. The first issue is the mode switching control from 1-stage to 2-stage. A stable 2-stage heating operation is guaranteed, only if the load-side water inlet temperature is over a certain value, where the 1-stage heating operation should be done first from a cold start. The second issue is oil level control. An oil shortage problem in the low stage compressor, which depends on the degree of suction superheat, was solved by a proper oil level control scheme.

Keywords

References

  1. Lee, Y. S., Kim, J. R., Chang, K. C., Lee, W. H., Ra, H. S., and Baik, Y. J., 2004, Performance Test of 2-Stage Heat Pump System using River Water as a Heat Source, Proceedings of the SAREK, pp. 1288-1293.
  2. Kim, J. R., Lee, Y. S., Ra, H. S., and Baik, Y. J., 2005, Research on Performance Test of 2-Stage Heat Pump System using River Water as a Heat Source, Korean Journal of Air-Conditioning and Refrigerating Engineers, Vol. 35, pp. 214-219.
  3. Chang, Y. S., Lee, Y. C., and Kim, Y. G., 2003, Part-Load Performance Test of a Screw Chiller with Economizer using R22 and R407C, Korean Journal of Air-Conditioning and Refrigerating Engineers, Vol. 15, No. 15, pp. 902-909.
  4. Ahn, Y. S., Lee, D. Y., Kim, Y. I., Nam, I. W., and kim, Y. C., 1999, Simulation of a screw compressor considering leakage and superheat, Proceedings of the SAREK, pp. 1189-1193.
  5. Chang, K. C., Yoon, H. K., Park, S. R., Park, J. T., Lee, Y. S., Baik, Y. J., Ra, H. S., and Chung, M. H., 2005, An Analysis of Operation Characteristics for Heating and Cooling System Using Sewage Water, Proceedings of the SAREK, pp. 220-225.
  6. Park, C. S., Kim, B. Y., Kim, Y. C., Lee, Y. S., and Bang, K. Y., 2005, Simulation on the Heating Performance of a 2-stage Compression Heat Pump System Using River water, Korean Journal of Air- Conditioning and Refrigerating Engineers, Vol. 17, No. 11, pp. 1005-1013.
  7. Lee, Y. S. et al, 2004, Development of High Performance 2-Stage Heat Pump System using River Water as a Heat Source, Proceedings of 2nd CDRS Workshop.