DOI QR코드

DOI QR Code

제조 사업장의 환풍기 화재위험성 조사

The Survey of Fire Hazard of Fan in Manufacturing Industries

  • 김성삼 (경남대학교 소방방재공학과)
  • Kim, Sung-Sam (Dept. of Fire and Disaster Prevention Engineering, Kyungnam University)
  • 투고 : 2013.06.13
  • 심사 : 2013.08.21
  • 발행 : 2013.10.31

초록

The short circuit and overload is presented by main cause of electrical fire. However, 85% of the fan directly connected the outlet box without switch in total 110 fans as a research in manufacturing industries. In installation direction of vertical type fans which was placed on the horizontal surface, only 39 vertical type fans were placed on vertical surface and 71 fans were placed on the horizontal type. The installation direction of the fans warns of the risk of the fire hazard due to the motor stall to the user manual of the maker. However, it is the representative nonconformity example of construction which the people or builder disregards. In addition, the condition of ground connection with the earth leakage prevention was investigated in grounding of 5 fans, non-grounding of 105 fans. The double insulation structure is generally used for small fan and it can't connect ground wire as electric plug of non-grounding type. However, industrial iron fan needs ground wire for electric leakage and to protect against electric shock.

키워드

참고문헌

  1. Seung-Bok Choi, et. al., "Identifying a ventilation fan with flesh eyes", KIFI, Vol. 4, No 1, pp. 70-74, 2004.
  2. KS C 9304, "Ventilating Fans", pp. 6-12, 2002.
  3. Sun-Ho Choi, Geon-Tae Lee, "An Experimental Study on the Kitchen Ventilation System Effectiveness by Character of Static Pressure Loss of Each System Component in Apartment Building", AIK, Vol. 28, No. 3, pp. 269-276, 2012.
  4. J. Park, "Design of multipurpose ventilator for a vehicle using air-multiplier", KSPE Spring Annual Conference, pp. 1131-1132, 2010.
  5. Hyun-Rok Cha, et. al., "Inverter Motor Drive System Development for High Static Pressure Ventilation Fan", KIEE Summer Annual Conference, pp. 1193-1194, 2008.
  6. Jun-Won Song, et. al., "Study on Selection of Optimal Bathroom Ventilating fans Based on Measurements of Performance Appraisal and Flow Resistance in Exhaust Duct", SAREK Summer Annual Conference, pp. 672-680, 2002.
  7. Seung-Bin Lim, et. al., "Design of High efficiency 2phase Brushless DC Motor for Ventilation Fan", KIEE Autumn Annual Conference, pp. 17-19, 2009.
  8. B. J. Rho, et. al., "Fundamental Design and Test of Seam Blade in Ventilation Fan", KSME Autumn Annual Conference, pp. 1-5, 2006.
  9. Pil-Dong Song, Jin-Sik Ham, "A Study on the Ventilation Performance Estimation of Marketing Ventilation Fan Used in the Apartment House Kitchen", KHousing Annual Conference, pp. 315-320, 2002.
  10. Hyeog-Soo Kim, et. al., "The Analysis of the Fire Hazard According to Layer Short-Circuit of Motor Winding for the Fan", KIFSE Anual Conference, pp.135-139, 2000.
  11. Sung-Ho Hong, et. al., "A Experimental Study on the Electrical Fire Hazards Analysis of Electric Fan", KIFSE Autumn Annual Conference, pp. 344-349, 2007.
  12. Chun-Ha Lee, et. al., "A Study on the Fire Cause Analysis of Motor Damage", KIFSE. Vol. 21. No. 4, pp. 59-64, 2007.
  13. John D. DeHaan, "Kirk's Fire Investigation", Dooyangsa, pp. 556-560, 2011.
  14. Jung-Il Lee, "Fire investigation business', Junghunsa, pp. 520-523, 2009.
  15. Jin-Man Choi, "The Fire Investigation Introduction", Sungandang, pp. 228-235, 2010.
  16. S. T. Kwon, "Core Professional Engineer Fire Protection", Yeamoonsa, pp. 67-75, 2007.
  17. Chung-Seog Choi, et. al., "Electrical Fire Engineering", DongHwa Publishing, pp. 165-166, 329-330, 2000.
  18. H. S. Joe, et. al., "Study on the Mechanism, Properties & State of the Ignitible, and Fire Investigation Technique to Electric & Ventilating Fans", KIFI Annual Conference, pp. 109-125, 2008.
  19. http://www.nema.go.kr/nema_cms_iba/show_nema/boa rd/board1/view.jsp?cNo=393720&c_relation=25&check_the_code=1&check_the_num=135&check_up_num=110& pageNo=1
  20. http://www.nema.go.kr/nema_cms_iba/show_nema/boa rd/board1s/view.jsp?cNo=337241&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113 &pageNo=1
  21. http://www.nema.go.kr/nema_cms_iba/show_nema/boa rd/board1s/view.jsp?cNo=420933&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113 &pageNo=1
  22. http://www.nema.go.kr/nema_cms_iba/show_nema/boa rd/board1s/view.jsp?cNo=421070&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113 &pageNo=1
  23. Robert A. Yereance, Todd Kerkhoff, "Electrical Fire Analysis", Charles C. Thomas, pp. 191-193, 266-271, 2010.
  24. Durham, Marcus O. et. al., "Electrical Failure Analysis", Dream point Publishers, pp. 47-48, 2011.
  25. Jeong-Tae Jang, "A Study on the Countermeasure and Analysis Cause of Electrical Fire", CEM-TP, Vol. 7. No. 2. pp. 157-168. 2011.
  26. Sung-sam Kim, "Fire Cause Analysis of Ventilation Fan through the Fire Events", KIFSE Spring Annual Conference, pp. 186-187, 2013.