DOI QR코드

DOI QR Code

A Study on the Operation Characteristic of Induction Generator in the Small Hydropower Plant

소수력 발전소에 적용하는 유도발전기의 동작 특성

  • Received : 2013.02.19
  • Accepted : 2013.04.17
  • Published : 2013.05.01

Abstract

In this study, we described voltage fluctuation characteristics of distribution line during starting and normal operation condition of the small hydro generators. Based on these theories, we scrutinized the starting and operating characteristics of induction generators installed in two small hydro power plants that is connected to the distribution line and researched necessary factors when selecting the generator type. The type of turbines and capacity of generators are different. One is below 1,000kW and the other is above 1,000kW. Two generators are tested during starting, and it acts as motor not generator at the instant that the machine is connected to the grid. After connecting to the grid, the machine rotates above synchronous speed before converting to the generator mode. Therefore the characteristic of the generator during starting is same as it of motor.

Keywords

References

  1. K-water, "Detailed design report for Daechong Small Hydro Power Plant", 2005
  2. K-water, "Detailed design report for Yong Dam Small Hydro Power Plant", 2001
  3. Young-Kuk Kim, "A Study for selection of generator type in the small hydropower plant by analyzing the power flow of the distribution line the plant is linked",Gangneung-Wonju University Master's thesis, 2013.02
  4. J. Ramachandran et al., "Dynamic behavior of single-phase induction generators during disconnection and re-connection to the GRID", 16th PSCC, Glasgow, Scotland, 2008. 6
  5. K. S. Pankaj, J. P. Nelson, "Application Guidelines for Induction Generators," in Proc. International Conference on Electrical Machines and Drives, Milwaukee, Wisconsin, May 18-21, 1997, Paper WC1/5.1 - WC1/5.3.
  6. M. Godoy Simoes & Felix A. Farret, "Renewable Energy Systems-Design and Analysis with Induction Generators", CRC Press, 2004
  7. Jong-Gyeum Kim, "Characteristics Analysis of 3-phase Induction Generator at the Unbalanced Load Operation", KIEE, Vol.56, No.3, pp. 123-128, 2007.9
  8. Jong-Gyeum Kim, Young-Jeen Park, Il-Jung Kim, Young-Kuk Kim, "Characteristics Analysis of Induction Generator with a Change in Rotor Speed", KIEE, Vol.60, No.12, pp.2225-2229, 2011. 12 https://doi.org/10.5370/KIEE.2011.60.12.2225
  9. Jack J. Fritz, "Small and Mini Hydropower Systems", McGraw-Hill Book Company, USA, 1984.

Cited by

  1. A Study on the Application of Micro Hydro Power Generator at the Water Treatment Plant vol.28, pp.9, 2014, https://doi.org/10.5207/JIEIE.2014.28.9.067
  2. Efficiency Analysis for Water Turbine Generator of Agricultural Reservoir vol.62, pp.9, 2013, https://doi.org/10.5370/KIEE.2013.62.9.1223
  3. A comparison of the operating characteristics of the synchronous generator and induction generator applied to the small hydroelectric power plant vol.63, pp.2, 2014, https://doi.org/10.5370/KIEEP.2014.63.2.055
  4. Analysis for Voltage Fluctuation and Power Flow at the Grid-Connected Time of Squirrel-Cage Induction Generator vol.28, pp.6, 2014, https://doi.org/10.5207/JIEIE.2014.28.6.045
  5. Operating Characteristic Analysis of the Induction Generator by the Reactor Starting vol.63, pp.3, 2014, https://doi.org/10.5370/KIEEP.2014.63.3.138