Abstract

The most common power quality problems in distribution systems are related to unbalanced voltage sags. Voltage sags must be detected quickly and corrected in a minimum amount of time. One of the most widely used methods for sag detection is based on the d-q transformation. This method has the disadvantage of missing the detection of unbalanced faults, because this method uses a voltage sag level signal obtained from the average of 3 phases for sag detection. In this paper, an adaptive filter sag detection method is proposed for Dynamic Voltage Restorers (DVR) under unbalanced fault conditions. The proposed DVR controller is able to detect balanced, unbalanced and single phase voltage sags. A novel reference voltage generation method is also presented. To validate the proposed control methods, a 3-phase DSP controlling a DVR prototype with a power rating of 1.5-kVA has been developed. Finally, experimental results are presented to verify the performance of the proposed control methods.

Keywords

References

  1. P. Daehler, and R. Affolter, "Requirements and solutions for dynamic voltage restorer, case study," IEEE Power Engineering Society Winter Meeting, Vol. 4, pp. 2881-2885, 2000.
  2. F. B. Ajaei, S. Afsharnia, A. Kahrobaeian, and S. A. Farhangi, "Fast and effective control scheme for the dynamic voltage restorer," IEEE Trans. Power Del., Vol. 26, pp. 2398-2406, Oct., 2011.
  3. A. Teke, K. Ç. Bayindir, and M. Tumay, "Fast sag/swell detection method for fuzzy logic based dynamic voltage restorer," IET Gener. Transm. Distrib., Vol. 4, pp. 1-12, Jan., 2010. https://doi.org/10.1049/iet-gtd.2009.0423
  4. H. Ezoji, A. Sheikholeslami, M. Tabasi and M. M. Saeednia. "Simulation of dynamic voltage restorer using hysteresis voltage control," European Journal of Scientific Research, Vol. 27, No 1, pp.152-166, 2009.
  5. D. M. Lee, T. G. Habetler, R. G. Harley, T. L. Keister, and J. R. Rostron. "A voltage sag supporter utilizing a PWM-switched autotransformer," IEEE Trans. Power Electron., Vol. 22, No 2, pp. 626-635, Mar., 2007. https://doi.org/10.1109/TPEL.2006.890004
  6. C. Fitzer, M. Barnes, and P. Green. "Voltage sag detection technique for a dynamic voltage restorer," IEEE Trans. Ind. Appl., Vol. 40, No. 1, pp. 203-212, Jan. 2004. https://doi.org/10.1109/TIA.2003.821801
  7. H. J. Jung, I. Y. Suh, B. S. Kim, R. Y. Kim, S. Y. Choi, and J. H. Song. "A study on DVR control for unbalanced voltage compensation," IEEE Applied Power Electronics Conference and Exposition, Vol. 2, pp. 1068-1073, 2002.
  8. G. M. Karimi, and M. R. A. Iravani, "A nonlinear adaptive filter for online signal analysis in power systems: applications," IEEE Trans. Power Del., Vol. 17, No. 2, pp. 617-622, Apr. 2002. https://doi.org/10.1109/61.997949
  9. G. M. Karimi and M. R. Iravani, "A new phase-locked loop (PLL) system," IEEE Midwest Symposium, Proceedings of the Circuits and Systems, Vol. 1, pp. 421-424, 2001.
  10. T. Jimichi, H. Fujita, and H. Akagi. "Design and experimentation of a dynamic voltage restorer capable of significantly reducing an energy-storage element," IEEE Trans. Ind. Appl., Vol. 44, No 3, pp. 817-825, June 2008. https://doi.org/10.1109/TIA.2008.921425
  11. IEEE519, "IEEE recommended practices and requirements for harmonic control in electrical power systems," 1992.

Cited by

  1. Performance analysis of multiconverter unified power quality conditioner with an EPLL-based controller at medium voltage level vol.26, pp.12, 2016, https://doi.org/10.1002/etep.2306
  2. Fast and precise voltage sag detection method for dynamic voltage restorer (DVR) application vol.130, 2016, https://doi.org/10.1016/j.epsr.2015.08.002