DOI QR코드

DOI QR Code

Comprehensive Field Measurement of Indoor Air and Thermal Quality in Naturally Ventilated Office Building with Double-Skin Façade

  • Ito, Kazuhide (Interdisciplinary Graduate School of Engineering Science, Kyushu University) ;
  • Shiraishi, Yasuyuki (Department of Environmental Space Design, The University of Kitakyushu)
  • Published : 2013.12.31

Abstract

Double-Skin Façade (DSF), which is a kind of passive indoor environmental control technique, is effective way to control environmental loads while maintaining the transparency especially in perimeter zone and hence the adoption example of DSF keep increasing recently. The objective of this study was to perform a field survey of air quality environment with natural ventilation through DSF and thermal environment within office building with six stories during a mild climate period in Japan. Moreover, to understand the comprehensive environmental performance of the target building, questionnaire survey was conducted to subjectively evaluate the productivity and satisfaction with the environmental factors in office space. In this field measurement, there was a positive correlation between the DSF internal ventilation flow and the amount of solar radiation on the DSF normal surface; the primary driving force for ventilation in the DSF was considered to be the buoyancy force caused by solar radiation. The results of questionnaire survey with regard to productivity level indicated the need for improvement in the thermal (temperature) and spatial environment (room size and furniture placement).

Keywords