Abstract

This paper propose seamless transfer operation between grid-connected and stand-alone mode in the three-phase inverter for microgrid. The inverter operates grid-connected mode and stand-alone mode. Grid-connected mode is the inverter connected to grid and stand-alone mode is to deliver energy to the load from inverter at grid fault. When conversion from gird-connected to stand-alone mode, the inverter changes current control to voltage control. When grid restored, the inverter system is conversion from stand-alone to grid-connected mode. In this case, load phase and grid phase are different. Therefore, synchronization is essential. Thus Seamless transfer operation stand-alone to grid-connected mode. In this paper, propose sealmless transfer operation between grid-connceted and stand-alome mode, and this method is verified through simulation and experiment.

Keywords

References

  1. Remus Teodorescu, Marco Liserre, Pedro Rodriguez "Grid Convertersfor Photovoltaic and Wind Power Systems", WILEY IEEE, 2011.
  2. R. Lasseter, et. al., "White Paper on Integration of Distributed Energy Resources - The CERTS MicroGrid Concept", Office of Power Technologies of the IS Department of Energy, April 2002.
  3. IEEE Power &Energy Magazine, may/june 2008. Microgrid
  4. Jae-Hun Jung, Eui-Cheol Nho, In-Dong Kim, Heung-Geun Kim, Tae-Won Chun and Nam-Sup Choi, "Seamless Control Mode Transfer of a PCS for Islanding Mode Operation" Power Electronics and ECCE Asia (ICPE & ECCE), 2011 IEEE 8th International Conference on, pp. 2658-2662, 2011.
  5. Hyosing Ki,, Taesik Yu and Sewan Choi, "Indirect current control algorithm for utility interactive inverters in distributed generation systems", IEEE Transactions on Power Electronics, Vol. 23, No. 3, pp. 1342-1347, May 2008. https://doi.org/10.1109/TPEL.2008.920879
  6. K. Macken, M. Bollen, and R. Belmans, "Mitigation of Voltage Dips Through Distributed Generation System", IEEE Trans on Industry Aplications, Vol. 40, No. 6, pp. 1686-1693. 2004. https://doi.org/10.1109/TIA.2004.836302
  7. M.P. Kazmierkowski and L. Malesani, "Current control techniques for three-phase voltage-source PWM converters: a survey," IEEE Transactions on Power Electronics, Vol. 45, No. 5, pp. 691-703, Oct. 1998. https://doi.org/10.1109/16.661230
  8. R. Tirumala, N. Mohan and C. Henze, "Seamless Transfer of Grid-Connected PWM inverters between Utility-Interactive and Stand-Alone Modes", Applied Power Electronics Conference and Exposition (APEC), pp. 1081-1086, 2002.
  9. Z. Yao. L. Xiao and Y. Yan, "Seamless Transfer of Single-Phase Grid-Interctive Inverters Between Grid-Connected and Stand-Alone Modes", IEEE Transactions on Power Electronics, Vol. 25, No. 6, pp. 1597-1603, June 2010. https://doi.org/10.1109/TPEL.2009.2039357
  10. Shengli Huang, Li Kong and Haiping Xu, "Control algorithm research on seamless transfer for distributed resource with a LCL filter", Electric Utility Deregulation and Restructuring and Power Technologies conference(DRPT 2008), pp. 2810-2814, April 2008.

Cited by

  1. A Study on the Efficiency Improvement Method of Photovoltaic System Using DC-DC Voltage Regulator vol.17, pp.7, 2016, https://doi.org/10.5762/KAIS.2016.17.7.704
  2. Renewable Energy Configuration Plan of Micro Grid in Gapa Island vol.34, pp.2, 2014, https://doi.org/10.7836/kses.2014.34.2.016