Evaluation of Thermal Comfort and Energy Performance for the Radiant Floor Cooling System with Dedicated Outdoor Air System in Apartment Building

공동주택에서 바닥 복사냉방시스템과 외기전담시스템의 통합 적용 시 열 쾌적 및 에너지 성능 평가

  • Received : 2013.06.05
  • Published : 2013.11.25

Abstract

In this study, thermal comfort and energy performance of the Radiant Floor Cooling System integrated with Dedicated Outdoor Air System(RFCS-DOAS) was analyzed and compared with the existing system, Packaged Air Conditioner with Energy Recovery Ventilator(PAC-ERV). As a result, the room temperature maintained within the range of $25{\sim}27^{\circ}C$ with both of PAC-ERV and RFCS-DOAS. Since the minimum floor surface temperature was $20^{\circ}C$ and the dew-point temperature was from $14^{\circ}C$ to $16^{\circ}C$, the condensation on the surface did not occur. In the aspect of the thermal comfort, minimum value of PMV was -0.62 and maximum PPD was 12.5% for PAC-ERV, which was out of recommended range. However, RFCS-DOAS could maintain the PMV and PPD within the recommended range. In addition, the total energy consumption during continuous operation in the PAC-ERV was 1,098 kWh which were about 1.5 times more than 717kWh, the total energy consumption of the RFCS-DOAS, and during intermittent operation, the total energy consumption in the PAC-ERV showed 730kWh which were about 1.8 times more than 407kWh, the total energy consumption of the RFCS-DOAS. So, the energy consumption ratio of the PAC-ERV to RFCS-DOAS during continuous operation was lower than that during intermittent operation.

Keywords

Acknowledgement

Supported by : 한국연구재단

References

  1. 오혜원, 정창호, 이진영, 여명석, 김광우, 공동주택 바닥 복사 냉방 시스템을 위한 제습형 보조냉방기의 대표실 적용 평가, 한국건축친환경설비학회 추계학술발표대회, 25(5), 2010
  2. Stanley A. Mumma, Kurt M. Shank, Achieving Dry Outsid e Air an Energy Efficient Manner, ASHRAE Transactions, 107(1), 2001
  3. Stanlet A Mumma, Kurt M.Shank, Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipm ent, ASHRAE Transactions, 107(1), 2001
  4. Stanlet A Mumma, Overview of Integrating Dedicated Out Air Systems with Parallel Terminal Systems, ASHRE Tran sactions, 107(1), 2001
  5. Stanlet A Mumma, Dedicated Outdoor Air in Parallel with Chilled Ceiling System, Engineered Systems, 2001(11)
  6. Stanlet A Mumma, Integration of Hydrnic Thermal Transp ort with Fire Suppresson Systems, ASHRAE Transactions, 107(1), 2001
  7. 殷平, 冰蓄冷低溫送風系統設計方法(1): 室內設計參數, 舒适感, 室內空機品疾, 暖通空調, 34(5), 2004
  8. Jea-Weon Jeong, Energy Conservation Benefits of a Dedica ted Outdoor Air System with Parallel Sensible Cooling by Ceiling Radiant Panels, ASHRAE Transactions, 2003
  9. 정재원, 김민휘, 김진효, 권오현, 외기전담시스템 기반 초고층 공동주택 중앙 공급식 환기시스템의 적정 급기조건 및 에너지 절감효과 분석, 대한건축학회논문집, 25(06), 2009
  10. ASHRAE, 2005ASHRAE Handbook Fundamentals, 2005
  11. 이승언, 건물에서의 결로 발생 원인과 대책, Journal of the KGBC, 4(02), 2004
  12. 이승복, 원종서, 바닥 복사냉난방 시스템의 유형별 에너지 성능 평가, 대한건축학회논문집, 21(3), 2005
  13. 정창호, 이진영, 백승효, 여명석, 김광우, 공동주택 거주 실험을 통한 바닥 복사냉방시스템의 사용자 운전 특성, 대한건축학회학술발표대회 논문집, 2009
  14. 김용이, 윤혜림, 여명석, 시뮬레이션을 통한 바닥 복사냉방시스템의 공급유량 및 냉수온도 제어에 관한 연구, 대한설비공학회논문집, 13(6), 2001
  15. 김동우, 주거용 건축물의 룸 에어컨디셔너 실내기 유형별 취출성능 평가에 관한 연구, 영남대학교 석사학위논문, 영남대학교, 2008
  16. 신민우, 염철민, 한화택, 장경진, 윤영현, 최선호, 온도 감지 디퓨져의 간극 변화에 따른 기류분포 성능, 대한설비공학회 동계학술발표대회 논문집, 2003