DOI QR코드

DOI QR Code

A Study on the Characteristics of the Electric Field and Electromagnetic Loss according to Bus Bar Size for a cost-effective 24kV High Voltage Switchgear

비용 효율이 높은 24kV급 고압배전반 개발을 위한 Bus Bar 사이즈에 따른 전·자기 손실 특성 분석

  • 홍종기 (한국교통대 첨단과학기술대 전기공학과) ;
  • 허정일 (한국교통대 첨단과학기술대 전기공학과) ;
  • 남석호 (한국교통대 첨단과학기술대 전기공학과) ;
  • 강형구 (한국교통대 첨단과학기술대 전기공학과)
  • Received : 2012.10.31
  • Accepted : 2012.11.21
  • Published : 2012.12.01

Abstract

The analysis on the bus bar effect is conducted to develop a cost effective 24kV/2,000A switchgear. The temperature enclosures and bus bars could rise due to several heat sources such as eddy current losses and copper losses. Therefore, a study on the characteristics of the electric field intensity and electromagnetic loss according to the bus bar size in a bus bar compartment is essential to design a electrically reliable high voltage switchgear. It is investigated that the electromagnetic influence to the temperature rising and the dielectric stability according to various bus bar sizes by using finite element method(FEM). The electric field intensity and electromagnetic loss according to various bus bar sizes are calculated to design a reliable and a high voltage switchgear. As results, it is found that the electromagnetic loss and the dielectric stability of bus bar could be determined by a bus bar size. It means that a cost effective 24kV/2,000A high voltage switchgear could be developed by selecting the proper size of a bus bar. Also, it is recognized that the electromagnetic characteristics according to various bus bar sizes in order to design an electrically stable high voltage switchgear when the enclosure size is determined as a fixed value. Futhermore, studies on the various nominal voltage class and bus bar sizes will be conducted to develop a cost effective high voltage switchgear.

Keywords

References

  1. 이방욱, 강종성, 손중만, 최원준, 서정민, "대전류 통전시 배전반내의 열적 현상에 관한 연구", 대한전기학회추계학술대회 논문집, pp.1051-1053., 1999.
  2. 배준한, 김해준, "전력기기용 Al/Cu 복합 부스바의 통전용량 설계 및 특성 평가", 대한전기학회 논문지, pp.682-632, 2006., Vol.55, No.12
  3. Yasuo nishikore, Soji Kojima, and Teruya Kouno, "A Study of the Field Utilization Factor and the Maximum Electric Field at Sparkover of the standard Sphere Gaps", Electrical Engineering in Japan, Vol.139, No.4, pp. 399-404, 2002.
  4. 남석호, 강형구 "친환경 고압배전반 개발을 위한 dry air의 압력별 절연내력 특성 분석에 관한 연구", 대한전기학회 논문지, pp.1560-1565, 2011., Vol.60, No.8 https://doi.org/10.5370/KIEE.2011.60.8.1560
  5. "한국물가정보", 2012.10